background image

Model number: DI240I

 

 

 

Diagram C 

Screws 

Diagram B 

Installation Sketch 

 

  Wiring Instructions 

 

 

 TERMINAL: 
 

I-Connect  : Interconnection 

 

       : Neutral 

 

E-Loop       : No wiring 

       : Active

 

 
 
 
 

 

 

CAUTION 

• 

All interconnected smoke alarms must be supplied from the same circuit. 

• 

A common Neutral must be used for Interconnect to function. 

• 

The maximum number of interconnected alarms you can have is 24. 

• 

The maximum wiring length between the first and last alarm is 150m. 

• 

DO NOT connect the interconnect wires to Live or Neutral. 

• 

Use a minimum of 1.5 mm

250V insulated wire for all wiring, including interconnecting wiring. 

 

  

How to Mount Y our Alarm 

 

1.  

Turn off AC power. 

2.  Pick the location for your alarm. 

3.  Place the base bracket in the installation position, mark the installation holes of the bracket with a pencil. 

4.  Drill two installation holes 5 mm in diameter and insert the two plastic plugs into holes using a hammer (See 

diagram A). 

5.  Connect Live, Neutral and Interconnection wires according to the wiring instructions. 

6.  Attach the base to the plastic plugs and tightly fix the screws into the plastic plugs (See diagram B). 

7.  Close the alarm (See diagram C). 

 

WARNING: 

Follow these installation instructions to avoid injury.   

 

 

 

 

 
 
 
 
 

 

Diagram D 

 
 

 

 

 
 
 
 
  

Maintenance and Cleaning 

 

This alarm requires periodic cleaning to remove dust, dirt, and debris. 

Use a vacuum cleaner with the soft brush, vacuum all sides and covers of smoke alarm device. 

 

 

Holes 

Plastic plugs 

Diagram A 

Diagram C 

Reviews: