D100-04-00
1
I56-1015-000
2151A Low Profile
Photoelectronic Plug-in
Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
Before Installing
Please thoroughly read the System Sensor manual I56-
407,
Guide for Proper Use of System Smoke Detectors
,
which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Cop-
ies of this manual are available at no charge from System
Sensor. Please also refer to CAN/ULC-S524-M91,
Stan-
dard for the Installation of Fire Alarm Systems
, and CEC
Part 1, Sec. 32.
NOTICE:
This manual should be left with the owner/user
of this equipment.
IMPORTANT:
The detector used with this base must be
tested and maintained regularly following CAN/ULC-S536
requirements. The detector used with this base should be
cleaned at least once a year.
General Description
The 2151A low-profile photoelectronic detector uses a
state-of-the-art optical sensing chamber. This detector
is designed to provide open area protection and to be
used with compatible ULC-listed control panels only. The
capability of plugging the detector into a variety of special
bases makes it more versatile than equivalent direct-wired
models.
Specifications
Size
Height:
1.7 inches (43 mm)
Diameter:
4.0 inches (101 mm)
Weight:
3.6 oz. (102 g)
Operating Voltage:
10 to 32 VDC
Max. Avg. Standby Current:
120uA
Operating Temperature Range:
0° to 49°C (32° to 120°F)
Operating Humidity Range:
10% to 93% Relative Humidity noncondensing
Latching Alarm:
Reset by momentary power interruption.
Two LEDs on each detector provide local 360° visible
alarm indication. They flash every ten seconds indicating
that power is applied and the detector is working properly.
The LEDs latch on in alarm. Remote LED annunciator
capability is standard and may be implemented through
an optional accessory RA400ZA. The alarm can be reset
only by a momentary power interruption. These detectors
may be tested by activating the internal reed switch with a
magnet.
Base Selection And Wiring Guide
Refer to the installation instructions for the Plug-in De-
tector Bases for base selection and wiring instructions.
System Sensor has a variety of detector bases available
for this smoke detector, including 2-wire applications with
and without relays and/or current limiting resistors, 4-wire
and 120VAC applications ( see list below ).
All bases are provided with screw terminals for power,
ground, remote annunciator connections and relay con-
tact connections, if applicable. The electrical ratings for
each detector-base combination are also included in the
base installation instructions.
Adapter Base Selection Guide
Base Model
Loop
Current
Alarm
Nominal
Current Draw
Number
Type
Limit Resistor
Contact Type
Voltage
on Alarm (mA)
B110LP
2-wire*
No
—
12/24VDC
10–100**
B112LPA
4-wire
Yes
Form A&C
24VDC
14–39
B114LPA
4-wire
Yes
Form A&C + A Supy.
120VAC
75 mA AC Max
B116LPA
2-wire*
No
Form C
24VDC
12–100**
B401
2-wire*
No
—
12/24VDC
10–100**
*Functionality contingent on panel compatibility **Must be limited by control panel †Flangeless base
Relay Contact Ratings:
Resistive or Inductive (60% power factor) load.
Form A:
2.0A at 30 VAC/DC
Form C:
0.6A at 110VDC, 2.0A at 30VDC - 1.0A at 125VAC, 2.0A at 30VAC