Figure 40
Unbalanced Data Bus
The addition of 2 repeaters (Figure 41) can solve this problem. The repeaters look like short stubs to the main
bus, and at the same time they create 2 new buses that have all the same characteristics as the main bus. Each
leg must have termination resistors to balance the new data bus.
Figure 41
Data Bus using two repeaters
Be sure to check the equipment being installed. Some manufacturers include a built-in terminating resistor
that can be selected by a jumper or dipswitch. Detcon Model 880 has such a jumper located on the FA-isonet
card. The jumper is labeled “120 ohm Term.”
Detcon 600 series gas sensors and DA1 modules do not include this resistor, and therefore, if one of these
devices is the last on the RS-485 bus, a discrete 120 ohm resistor should be placed across the “A” and “B”
terminals on the connector board. Figure 42 illustrates the wiring scheme of a repeater when used in a wiring
bus with DA-1 devices.
Figure 42
Repeater wiring diagram