Det-Tronics Protect IR X3302 Instructions Manual Download Page 6

95-8576

4

3.3

EMI/RFI Interference

The  X3302  is  resistant  to  interference  by  EMI  and  RFI, 

and is EMC Directive compliant.  It will not respond to a 5 

watt walkie-talkie at distances greater than 1 foot.  Do not 

operate a walkie-talkie within 1 foot of the X3302.

Carbon Containing Fires

The X3302 is a multiple spectrum IR device with detection 

limited to flames that produce water vapor as a by-product 

of  combustion.    These  include  hydrogen,  ammonia, 

arsine, silane, and light hydrocarbons such as methane 

and methanol.  Some lighter carbonaceous fuels may be 

detectable by the X3302, but heavier carbon containing 

substances  that  burn  with  a  dark  yellow-orange  flame 

and emit dense sooty smoke may not be sensed with this 

device.  Other fuels that are not detectable include sulfur 

and burning metals.

ImPORTaNT SafETy NOTES

WarnIng

Do not open the detector assembly in a hazardous 

area when power is applied.  The detector contains 

limited serviceable components and should never 

be opened.  Doing so could disturb critical optical 

alignment  and  calibration  parameters,  possibly 

causing  serious  damage.   This  type  of  damage 

could be undetected and could result in failure to 

see a fire and/or false alarm.

CaUtIon

The wiring procedures in this manual are intended 

to  ensure  proper  functioning  of  the  device  under 

normal  conditions.    However,  because  of  the 

many  variations  in  wiring  codes  and  regulations, 

total  compliance  to  these  ordinances  cannot  be 

guaranteed.    Be  certain  that  all  wiring  complies 

with  the  NEC  as  well  as  all  local  ordinances.    If 

in  doubt,  consult  the  authority  having  jurisdiction 

before  wiring  the  system.    Installation  must  be 

done by a properly trained person.

CaUtIon

To  prevent  unwanted  actuation  or  alarm, 

extinguishing  devices  must  be  disabled  prior  to 

performing system tests or maintenance.

attEntIon

Remove  the  protective  cap  from  the  front  of  the 

detector before activating the system.

attEntIon

Observe  precautions  for  handling  electrostatic 

sensitive devices.

INSTallaTION

DETECTOR pOSITIONING

Detectors  should  be  positioned  to  provide  the  best 

unobstructed view of the area to be protected.  The following 

factors should also be taken into consideration:

Identify all high risk fire ignition sources.

• 

Be sure that enough detectors are used to adequately 

• 

cover the hazardous area.
Be sure that the unit is easily accessible for cleaning 

• 

and other periodic servicing.
Locate  and  position  the  detector  so  that  the  fire 

• 

hazard(s)  are  within  both  the  field  of  view  and 

detection range of the device.  Refer to Appendix for 

specific information.
Multispectrum  IR  detectors  are  less  likely  than 

• 

other detectors to false alarm to non-flame infrared 

sources, as verified by the data shown in the “False 

Alarm  Immunity”  table  (page  19)  in  the  Appendix.  

However,  in  some  instances,  sustained  modulation 

of these sources will cause a level of desensitization 

resulting  in  diminished  detection  range  (refer  to 

“Modulated Source” table [page 20] in the  Appendix).  

For this reason, the X3302 should be sited/located to 

avoid these sources if there is likely to be frequent, 

sustained  modulation  of  IR  sources  such  as  those 

shown.  It is important to point out that these same 

sources  have  no  effect  on  sensitivity  if  there  is  no 

modulation  (refer  to  “Unmodulated  Source”  table 

[page 20] in the  Appendix).
The detector should be aimed downward at least 10 

• 

to 20 degrees to allow lens openings to drain.  See 

Figure  1.   

The  detector  should  be  positioned  so 

that its field of view does not cover areas outside 
the hazardous area.

  This will minimize the possibility 

of false alarms caused by activities outside the area 

requiring protection.
For  best  performance,  the  detector  should  be 

• 

mounted on a rigid surface in a low vibration area.
Dense fog, rain or ice can absorb IR radiation and 

• 

reduce the sensitivity of the detector.
For  ATEX  installations,  the  X3302  detector  housing 

• 

must be electrically connected to earth ground.

Summary of Contents for Protect IR X3302

Page 1: ...Instructions 95 8576 Protect IR Multispectrum IR Flame Detector X3302 3 3 Rev 4 09 95 8576 ...

Page 2: ...nstallation 4 Detector Positioning 4 Detector Orientation 5 Protection Against Moisture Damage 5 Wiring Procedure 6 Setting Device Network Addresses EQP Model Only 12 Startup Procedure 13 Fire Alarm Test 13 Troubleshooting 13 Maintenance 14 Cleaning Procedure 14 oi Plate Removal 14 Periodic Checkout Procedure 14 Clock Battery 14 Features 15 Specifications 15 Replacement Parts 17 Device Repair And ...

Page 3: ...urveillance of hazardous materials that produce mostly water vapor and little or no CO2 in the combustion process The detection capability of the X3302 is double that of traditional UV and UVIR detectors At the same time it attains complete solar resistance and insensitivity to artificial lights lightning and blackbody radiation which still plague other detection technologies The detector has Divi...

Page 4: ...the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output i e loss of operating power LON SLC Output The EQP model is designed for use exclusively with the Det Tronics Eagle Quantum Premier system The detector communicates with the system controller over a digital communication network or LON SLC Local Operating Network Signalling Line Circuit Th...

Page 5: ... communication is not available on the EQP model data logging Dataloggingcapabilityisalsoprovided Statusconditions such as normal power down general and oi faults pre alarm fire alarm time and temperature are recorded Each event is time and date stamped along with the temperature and input voltage Event data is stored in non volatile memory when the event becomes active and again when the status c...

Page 6: ...rom the front of the detector before activating the system Attention Observe precautions for handling electrostatic sensitive devices INSTALLATION Detector Positioning Detectors should be positioned to provide the best unobstructedviewoftheareatobeprotected Thefollowing factors should also be taken into consideration Identify all high risk fire ignition sources Be sure that enough detectors are us...

Page 7: ...ill not come in contact with the electrical connections or components of the system The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer If conduit is used drains must be installed at water collection points to automatically drain accumulated moisture Conduit breathers should be installed at upper locations to ...

Page 8: ... should be performed only by qualified personnel Detector Mounting Install the swivel mounting bracket assembly on the wall The installation surface should be free of vibration and suitable to receive 1 4 inch M6 screws with a length of at least 1 inch 25 mm and have sufficient capacity to hold the detector and bracket weight Refer to Figure 3 for dimensions Relay and 4 20 mA Output Models Follow ...

Page 9: ... and install the EOL resistor as 3 shown in Figure 6 Maintain a 3 8 inch 10 mm minimum gap between 4 the resistor body and the terminal block or any other neighboring parts NOTE All cable entry devices and blanking elements shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of u...

Page 10: ... 25 24 23 22 21 SPARE SPARE RS 485 A RS 485 B MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 EEx d Wiring Option 2255A FIRE ALARM PANEL X3302 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WIT...

Page 11: ... mA Current Output Sinking 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC D2258 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X3302 IR DETECTOR 24 VDC Figure 11 X3302 Detector Wired for Isolated 4 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC D2259 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4...

Page 12: ...dresses section of this manual for switch setting procedure Check all field wiring to be sure that the proper 5 connections have been made Replace the device cover 6 Make the final sighting adjustments and ensure that 7 the mounting bracket hardware is tight NOTE Refer to the Eagle Quantum Premier system manual number 95 8533 for information regarding power and network communication cable requirem...

Page 13: ...OMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A CH 4 CH 8 CONTROLLER 24 VDC 4 2 24 VDC 3 1 B 52 49 A 53 50 TxD A 59 56 RxD B 58 55 GND GND 57 54 SHIELD 51 48 COM2 COM1 P1 P7 P9 P8 P4 P5 1 5 5 13 1 5 6 14 2 6 7 15 2 6 8 16 3 7 9 17 3 7 10 18 4 8 11 19 4 8 12 20 P2 P3 C 45 NO 46 NC 47 P6 FAULT GND 5...

Page 14: ...to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB Least Significant Bit See Figure 16 The device s LON address is equal to the added value...

Page 15: ... to the Maintenance section for complete information regarding cleaning of the detector viewing windows Check input power to the unit 3 If the fire system has a logging function check the 4 fire panel log for output status information See Table 3 for information regarding 4 to 20 mA output Turn off the input power to the detector and check all 5 wiring for continuity Important Disconnect wiring at...

Page 16: ...d Det Tronics window cleaning solution If a stronger solution is needed isopropyl alcohol may be used Oi plate Removal Loosen the two captive screws then grasp the 1 oi plate by the visor and remove it from the detector See Figure 17 Thoroughly clean the 2 oi plate reflective surfaces holding it by its edges to avoid leaving fingerprints on the inside reflective surface Re install the 3 oi plate E...

Page 17: ...ation clears after 0 5 second device is ready to indicate an alarm condition after 30 seconds OUTPUT RELAYS Fire Alarm relay Form C 5 amperes at 30 vdc The Fire Alarm relay has redundant terminals and normally open normally closed contacts normally de energized operation and latching or non latching operation Fault relay Form A 5 amperes at 30 vdc The Fault relay has redundant terminals and normal...

Page 18: ...4 ATEX 137104 DEMKO 04 ATEX 137104 T6 Tamb 55 C to 60 C T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C T5 Tamb 55 C to 75 C IP66 T4 Tamb 55 C to 125 C IP66 Conforms with Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC Explosive Atmosphere Directive 94 9 EC NOTE Operational performance verified from 40 C to 75 C note An optional third party addressable module can only ...

Page 19: ... oz grease for detectors non silicon 006097 001 Q1201 Laser 007240 001 Q1116A1001 Air Shield AL 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 007290 001 Q9033B Stainless Steel Swivel Mount Assembly is for aluminum and stainless steel detectors 007290 002 Q9033A Aluminum Swivel Mount Assembly is for aluminum detectors only 007307 001 oi plate for X3301 requires inspector connector to calib...

Page 20: ... and 4 20 mA 14 Eagle Quantum Premier 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 Relay 4 20 mA and HART TYPE THREAD TYPE 4M 4 PORT METRIC M25 4N 4 PORT 3 4 NPT TYPE MATERIAL A Aluminum S Stainless Steel 316 MODEL DESCRIPTION X3302 Multispectrum IR Flame Detector Detectors are always Class I Div 1 X3302 MODEL MATRIX ...

Page 21: ... to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 2000 NOTE Actual response times of the EQP Model may vary The following performance criteria were verified OPTICAL INTEGRITY TEST The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50 of its detection range verifying that ...

Page 22: ...N A N A Arc welding 20 6 No alarm No alarm 70 w sodium vapor lamp 10 3 No alarm No alarm 250 w mercury vapor lamp 10 3 No alarm No alarm 300 w incandescent lamp 10 3 No alarm No alarm 500 w shielded quartz halogen lamp 15 5 No alarm No alarm 1500 w electric quartz heater 10 3 No alarm No alarm Two 34 w fluorescent lamps 5 1 5 No alarm No alarm Fuel Size Flow Rate Distance feet m Avg Horiz Response...

Page 23: ...nt lamp 10 3 100 SLPM 100 30 5 2 1500 w electric radiant heater 10 3 100 SLPM 100 30 5 2 500 w shielded quartz halogen lamp 15 4 6 100 SLPM 100 30 5 3 Sunlight direct 50 SLPM 50 15 2 2 Sunlight direct 100 SLPM 50 15 2 2 False Alarm Souce Modulated Distance feet m Fire Source Hydrogen Distance feet m Average Response Time seconds Two 34 w fluorescent lamps 5 1 5 100 SLPM 100 30 5 3 70 w sodium vapo...

Page 24: ...te 0 15 45 15 30 30 DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45 FROM HORIZONTAL 0 15 15 30 45 30 45 50 ft 50 ft 40 ft 40 ft 30 ft 30 ft 20 ft 20 ft 10 ft 70 ft 70 ft 60 ft 60 ft Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 1 x 1 ft FM Approvals Description and Performance Report Continued NOTE FM Approvals minimum requirements are response distance meas...

Page 25: ...r service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved Detector Electronics Corporation 6901 West 110th Street Minneapolis MN 55438 USA T 952 941 5665 or 800 765 3473 F 952 829 8750 W http www det tronics com E det tronics det tronics com X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety System F...

Reviews: