Det-Tronics Protect IR X3302 Instructions Manual Download Page 5

3

95-8576

3.3

Magnetic 

oi

 / Manual 

oi

The  detector  also  incorporates  both  magnetic 

oi

  and 

manual 

oi

 features that provide the same calibrated test 

as the automatic 

oi

, and in addition actuates the Alarm 

relay to verify output operation for preventive maintenance 

requirements.    These  features  can  be  performed  at 

any time and eliminate the need for testing with a non-

calibrated external test lamp.

CaUtIon

These  tests  require  disabling  of  all  extinguishing 
devices  to  avoid  release  resulting  from  a 
successful test.

The magnetic 

oi

 test is performed by placing a magnet by 

the marked location (mag 

oi

) on the outside of the detector.  

The manual 

oi

 test is accomplished by connecting the 

oi

 

lead (terminal 22) to power supply minus via an external 

switch. The magnet or switch must be held in place for 

a minimum of 6 seconds to complete the test. Either of 

these test methods activates the calibrated IR emitters.  

If  the  resulting  signal  meets  the  test  criteria,  indicating 

that greater than half of the detection range remains, the 

Alarm relay changes state, the indicating LED changes 

to red, and the 4-20 mA current output goes to 20 mA.  

This condition remains until the magnet is removed or the 

switch is released, regardless of whether the relays are 

set for latching or non-latching operation

If less than half of the detection range remains, no alarm 

is produced and a fault is generated.  The fault indication 

can  be  reset  by  momentarily  applying  the  magnet  or 

manual 

oi

 switch.

NOTE

Refer  to  the  Appendix  for  FM  verification  of 
Det-Tronics’ Optical Integrity 

oi

 function.

COMMUNICATION

The  X3302  is  furnished  with  an  RS-485  interface  for 

communicating status and other information with external 

devices.  The RS-485 supports MODBUS protocol, with 

the detector configured as a slave device.

NOTE

The  EQP  model  uses  LON/SLC  communication.   
RS-485  communication  is  not  available  on  the 
EQP model.

DATA LOGGING

Data logging capability is also provided.  Status conditions 

such as normal, power down, general and 

oi

 faults, pre-

alarm,  fire  alarm,  time  and  temperature  are  recorded.  

Each  event  is  time  and  date  stamped,  along  with  the 

temperature and input voltage.  Event data is stored in 

non-volatile  memory  when  the  event  becomes  active, 

and again when the status changes.  Data is accessible 

using the RS-485 port or the EQP controller.

INTEGRAL wIRING COMpARTMENT

All  external  wiring  to  the  device  is  connected  within 

the  integral  junction  box.    The  screw  terminals  accept 

wiring from 14 to 24 AWG.  The detector is furnished with 

four conduit entries, with either 3/4 inch NPT or 25 mm 

threads.

GENERal aPPlICaTION 

INfORmaTION

RESpONSE ChARACTERISTICS

Response  is  dependent  on  distance,  type  of  fuel, 

temperature of the fuel, and time required for the fire to 

come to equilibrium.  As with all fire tests, results must be 

interpreted according to an individual application.  See 

Appendix for fire test results.

IMpORTANT AppLICATION CONSIDERATIONS

In applying any type of sensing device as a fire detector, 

it is important to know of any conditions that can prevent 

the  device  from  responding  to  fire,  and  also  to  know 

what other sources besides fire can cause the device to 

respond.

welding

Arc  welding  should  not  be  performed  within  20  feet  of 

the  detector.    Gas  welding  mandates  system  bypass, 

since the gas torch is an actual fire.  Arc welding rods 

can contain organic binder materials in the flux that burn 

during the welding operation and are detectable by the 

X3302.  Welding rods with clay binders do not burn and 

will  not  be  detected  by  the  X3302.    However,  system 

bypass is always recommended, since the material being 

welded may be contaminated with organic substances 

(paint,  oil,  etc.)  that  will  burn  and  possibly  trigger  the 

X3302.

Artificial Lighting

The X3302 should not be located within 3 feet of artificial 

lights.  Excess heating of the detector could occur due to 

heat radiating from the lights.

Summary of Contents for Protect IR X3302

Page 1: ...Instructions 95 8576 Protect IR Multispectrum IR Flame Detector X3302 3 3 Rev 4 09 95 8576 ...

Page 2: ...nstallation 4 Detector Positioning 4 Detector Orientation 5 Protection Against Moisture Damage 5 Wiring Procedure 6 Setting Device Network Addresses EQP Model Only 12 Startup Procedure 13 Fire Alarm Test 13 Troubleshooting 13 Maintenance 14 Cleaning Procedure 14 oi Plate Removal 14 Periodic Checkout Procedure 14 Clock Battery 14 Features 15 Specifications 15 Replacement Parts 17 Device Repair And ...

Page 3: ...urveillance of hazardous materials that produce mostly water vapor and little or no CO2 in the combustion process The detection capability of the X3302 is double that of traditional UV and UVIR detectors At the same time it attains complete solar resistance and insensitivity to artificial lights lightning and blackbody radiation which still plague other detection technologies The detector has Divi...

Page 4: ...the nature of the fault condition impairs the ability of the detector to generate or maintain an alarm output i e loss of operating power LON SLC Output The EQP model is designed for use exclusively with the Det Tronics Eagle Quantum Premier system The detector communicates with the system controller over a digital communication network or LON SLC Local Operating Network Signalling Line Circuit Th...

Page 5: ... communication is not available on the EQP model data logging Dataloggingcapabilityisalsoprovided Statusconditions such as normal power down general and oi faults pre alarm fire alarm time and temperature are recorded Each event is time and date stamped along with the temperature and input voltage Event data is stored in non volatile memory when the event becomes active and again when the status c...

Page 6: ...rom the front of the detector before activating the system Attention Observe precautions for handling electrostatic sensitive devices INSTALLATION Detector Positioning Detectors should be positioned to provide the best unobstructedviewoftheareatobeprotected Thefollowing factors should also be taken into consideration Identify all high risk fire ignition sources Be sure that enough detectors are us...

Page 7: ...ill not come in contact with the electrical connections or components of the system The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer If conduit is used drains must be installed at water collection points to automatically drain accumulated moisture Conduit breathers should be installed at upper locations to ...

Page 8: ... should be performed only by qualified personnel Detector Mounting Install the swivel mounting bracket assembly on the wall The installation surface should be free of vibration and suitable to receive 1 4 inch M6 screws with a length of at least 1 inch 25 mm and have sufficient capacity to hold the detector and bracket weight Refer to Figure 3 for dimensions Relay and 4 20 mA Output Models Follow ...

Page 9: ... and install the EOL resistor as 3 shown in Figure 6 Maintain a 3 8 inch 10 mm minimum gap between 4 the resistor body and the terminal block or any other neighboring parts NOTE All cable entry devices and blanking elements shall be certified to E generation or ATEX standards in type of explosion protection increased safety e or flameproof enclosure d as applicable suitable for the conditions of u...

Page 10: ... 25 24 23 22 21 SPARE SPARE RS 485 A RS 485 B MAN Oi 4 20 mA 4 20 mA 4 20 mA REF 4 20 mA REF COM AUX N O AUX N C AUX Figure 7 EEx d Wiring Option 2255A FIRE ALARM PANEL X3302 DETECTOR ALARM ALARM 24 VDC WIRING NOTES 1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING THE FAULT RELAY COIL IS ENERGIZED AND THE NORMALLY OPEN N O AND COMMON COM CONTACTS ARE CLOSED 2 ALARM RELAY IS NORMALLY DE ENERGIZED WIT...

Page 11: ... mA Current Output Sinking 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC D2258 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4 20 mA 4 20 mA 24 VDC 24 VDC 29 28 27 26 25 24 23 22 21 MAN Oi X3302 IR DETECTOR 24 VDC Figure 11 X3302 Detector Wired for Isolated 4 to 20 mA Current Output Sourcing 24 VDC 4 TO 20 mA PLC 600 Ω MAX AT 24 VDC D2259 Oi TEST1 9 8 7 6 5 4 3 2 1 19 18 17 16 15 14 13 12 11 4...

Page 12: ...dresses section of this manual for switch setting procedure Check all field wiring to be sure that the proper 5 connections have been made Replace the device cover 6 Make the final sighting adjustments and ensure that 7 the mounting bracket hardware is tight NOTE Refer to the Eagle Quantum Premier system manual number 95 8533 for information regarding power and network communication cable requirem...

Page 13: ...OMMON C C SUPPLY A A CH 1 CH 5 IN OUT B B COMMON C C SUPPLY A A CH 2 CH 6 IN OUT B B COMMON C C SUPPLY A A CH 3 CH 7 IN OUT B B COMMON C C SUPPLY A A CH 4 CH 8 CONTROLLER 24 VDC 4 2 24 VDC 3 1 B 52 49 A 53 50 TxD A 59 56 RxD B 58 55 GND GND 57 54 SHIELD 51 48 COM2 COM1 P1 P7 P9 P8 P4 P5 1 5 5 13 1 5 6 14 2 6 7 15 2 6 8 16 3 7 9 17 3 7 10 18 4 8 11 19 4 8 12 20 P2 P3 C 45 NO 46 NC 47 P6 FAULT GND 5...

Page 14: ...to the network address switches For hazardous areas the area must be de classified before attempting disassembly of the device Always observe precautions for handling electrostatic sensitive devices The address number is binary encoded with each switch having a specific binary value with switch 1 being the LSB Least Significant Bit See Figure 16 The device s LON address is equal to the added value...

Page 15: ... to the Maintenance section for complete information regarding cleaning of the detector viewing windows Check input power to the unit 3 If the fire system has a logging function check the 4 fire panel log for output status information See Table 3 for information regarding 4 to 20 mA output Turn off the input power to the detector and check all 5 wiring for continuity Important Disconnect wiring at...

Page 16: ...d Det Tronics window cleaning solution If a stronger solution is needed isopropyl alcohol may be used Oi plate Removal Loosen the two captive screws then grasp the 1 oi plate by the visor and remove it from the detector See Figure 17 Thoroughly clean the 2 oi plate reflective surfaces holding it by its edges to avoid leaving fingerprints on the inside reflective surface Re install the 3 oi plate E...

Page 17: ...ation clears after 0 5 second device is ready to indicate an alarm condition after 30 seconds OUTPUT RELAYS Fire Alarm relay Form C 5 amperes at 30 vdc The Fire Alarm relay has redundant terminals and normally open normally closed contacts normally de energized operation and latching or non latching operation Fault relay Form A 5 amperes at 30 vdc The Fault relay has redundant terminals and normal...

Page 18: ...4 ATEX 137104 DEMKO 04 ATEX 137104 T6 Tamb 55 C to 60 C T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C T5 Tamb 55 C to 75 C IP66 T4 Tamb 55 C to 125 C IP66 Conforms with Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC Explosive Atmosphere Directive 94 9 EC NOTE Operational performance verified from 40 C to 75 C note An optional third party addressable module can only ...

Page 19: ... oz grease for detectors non silicon 006097 001 Q1201 Laser 007240 001 Q1116A1001 Air Shield AL 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 007290 001 Q9033B Stainless Steel Swivel Mount Assembly is for aluminum and stainless steel detectors 007290 002 Q9033A Aluminum Swivel Mount Assembly is for aluminum detectors only 007307 001 oi plate for X3301 requires inspector connector to calib...

Page 20: ... and 4 20 mA 14 Eagle Quantum Premier 15 Relay and Pulse 16 Addressable Module Only Third Party Type 23 Relay 4 20 mA and HART TYPE THREAD TYPE 4M 4 PORT METRIC M25 4N 4 PORT 3 4 NPT TYPE MATERIAL A Aluminum S Stainless Steel 316 MODEL DESCRIPTION X3302 Multispectrum IR Flame Detector Detectors are always Class I Div 1 X3302 MODEL MATRIX ...

Page 21: ... to 75 C Automatic Fire Alarm Signaling Performance verified per FM 3260 2000 NOTE Actual response times of the EQP Model may vary The following performance criteria were verified OPTICAL INTEGRITY TEST The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces resulting in a loss of approximately 50 of its detection range verifying that ...

Page 22: ...N A N A Arc welding 20 6 No alarm No alarm 70 w sodium vapor lamp 10 3 No alarm No alarm 250 w mercury vapor lamp 10 3 No alarm No alarm 300 w incandescent lamp 10 3 No alarm No alarm 500 w shielded quartz halogen lamp 15 5 No alarm No alarm 1500 w electric quartz heater 10 3 No alarm No alarm Two 34 w fluorescent lamps 5 1 5 No alarm No alarm Fuel Size Flow Rate Distance feet m Avg Horiz Response...

Page 23: ...nt lamp 10 3 100 SLPM 100 30 5 2 1500 w electric radiant heater 10 3 100 SLPM 100 30 5 2 500 w shielded quartz halogen lamp 15 4 6 100 SLPM 100 30 5 3 Sunlight direct 50 SLPM 50 15 2 2 Sunlight direct 100 SLPM 50 15 2 2 False Alarm Souce Modulated Distance feet m Fire Source Hydrogen Distance feet m Average Response Time seconds Two 34 w fluorescent lamps 5 1 5 100 SLPM 100 30 5 3 70 w sodium vapo...

Page 24: ...te 0 15 45 15 30 30 DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45 FROM HORIZONTAL 0 15 15 30 45 30 45 50 ft 50 ft 40 ft 40 ft 30 ft 30 ft 20 ft 20 ft 10 ft 70 ft 70 ft 60 ft 60 ft Field of View at Indicated Distance in Feet for Methanol at Very High Sensitivity 1 x 1 ft FM Approvals Description and Performance Report Continued NOTE FM Approvals minimum requirements are response distance meas...

Page 25: ...r service marks of others Copyright Detector Electronics Corporation 2010 All rights reserved Detector Electronics Corporation 6901 West 110th Street Minneapolis MN 55438 USA T 952 941 5665 or 800 765 3473 F 952 829 8750 W http www det tronics com E det tronics det tronics com X3301 Multispectrum IR Flame Detector PointWatch Eclipse IR Combustible Gas Detector Eagle Quantum Premier Safety System F...

Reviews: