INPUT/OUTPUT - DESCRIPTION AND EXAMPLES OF WIRING
Inputs
Pin Name
Description
Connection
1 Rmt Start
(remote start)
To run the tool forward.
to connect
to COM to
enable
2 Reverse
(remote reverse)
To run the tool in reverse.
3 Enable A
To allow the tool A to run if enabled.
To stop immediately the tool if disabled.
4 Enable B
To allow the tool B to run if enabled.
To stop immediately the tool if disabled.
5 Enable REV
To allow the tool to reverse if enabled.
6 Reset Batch
To reset the batch count to zero.
7 Pset 1
To select Pset 1.
8 Pset 2
To select Pset 2.
9 Pset 3
To select Pset 3.
10 Pset 4
To select Pset 4.
11 Pset 5
To select Pset 5.
12 No Ack
To unlock the tool when the report is NOK.
13 Rev PRE RUN
(Pre-run reverse)
To allow the tool to run in reverse mode when the "Pre-run
reverse" feature is activated.
14 Com
Common ground.
Outputs
Pin Name
Description
Connection
1
OK
Activated when the tightening
report is "OK".
Signal is "on" until next tool start with a
minimum time of 0.5 sec.
2 Gnd
-
"On": short pin 1 - Pin 2.
3
NOK
Activated when the tightening
report is "NOK".
Signal is "on" until next tool start with a
minimum time of 0.5 sec.
4 Gnd
-
"On": short pin 3 - Pin 4.
5
OK batch
Activated when the batch is
complete.
Signal is "on" until next tool start with a
minimum time of 0.5 sec.
6 Gnd
-
"On": short pin 5 - Pin 6.
7 Run Fwd
Activated when the tool is
running forward.
Signal is "on" as long as the tool is running
forward.
8 Gnd
-
"On": short pin 7 - Pin 8.
9 Run Bwd
Activated when the tool is
running backwards.
Signal is "on" as long as the tool is running
reverse.
10 Gnd
-
"On": short pin 9 - Pin 10.
11
VDC Out
24 VDC
250 mA maximum.
12 VDC jumper modification :
12 Gnd
V-
To connect to pin 11 to output.
13 -
N/A
N/A
14 -
N/A
N/A