Design Dynamics VTD-18NV-JHB Owner'S Operation And Installation Manual Download Page 6

www.fmiproducts.com

114370-02H

6

VENTING SPECIFICATIONS FOR 

INSTALLATION

The fireplace chimney flue and vent must be 

drafting properly. To check the vent for proper 

drafting: Light a tightly rolled newspaper on 

one end and place it at the inside front edge 

of the fireplace. Observe the smoke and be 

sure  the  vent  is  properly  drawing  it  up  the 

chimney. If the smoke spills out into the room, 

extinguish the flame and remove any obstruc

-

tion until proper venting is achieved.

The chimney flue must have a minimum free air 

opening of 43" during operation of this log set. 

A damper clamp is provided to fix the damper 

in position.

The minimum flue sizes shown in Figure 2 are 

based on a 6' chimney height using round pipe. 

Your minimum flue size will vary based on input 

rate and chimney height. Refer to the 

National 

Fuel Gas Code ANSI Z223.1/NFPA 54, Section 

6.6

, for details.

For Massachusetts Residents Only

Installation of this vented gas log set in the 

Commonwealth  of  Massachusetts  requires 

the damper be permanently removed or 

welded in the fully open position.

INSTALLING DAMPER CLAMP

Secure the damper stop clamp to the edge 

of the damper as shown in Figure 4, page 7. 

If for any reason this clamp doesn't work on 

your fireplace, another suitable clamp or per

-

manent stop must be installed, or the damper 

blade must be cut or removed.

INSTALLATION

Continued 

MODEL

BURNER

BTU 

INPUT

MIN. VENT

 

OPENING

VTD-18NV-JHB

VTD-18PV-JHB 18" Ramp 59,000 8" dia.

VTD-24NV-JHB

VTD-24PV-JHB 24" Ramp 69,000 8" dia.

VTD-30NV-JHB

VTD-30PV-JHB 30" Ramp 74,000 8" dia.

MINIMUM FIREBOX SIZES

MODEL

FRONT  WIDTH

BACK  WIDTH*

DEPTH

HEIGHT

VTD-18NV-JHB

VTD-18PV-JHB

28"

16"

14"

18"

VTD-24NV-JHB

VTD-24PV-JHB

29 

3

/

4

" 20"

15 

1

/

2

" 18"

VTD-30NV-JHB

VTD-30PV-JHB

36"

27"

18"

18"

*At depth indicated

BURNER ORIFICE

LOG 

SIZE

NATURAL

PROPANE/LP

INCHES

NO.

INCHES

NO.

18"

0.1495

25

0.0935

42

24"

0.1570

22

0.0980

40

30"

0.1660

19

0.1015

38

SPECIFICATIONS (W.C.)

FUEL INLET PRESSURE

MANIFOLD 

PRESSURE

MIN.

MAX.

NG

5"

10.5"

3.5

LP

11"

14"

10

Figure 3 - Specifications

Figure 2 - Technical Information Charts

 WARNING: Do not place lava 

rocks and log scraps on burner.

CHECK GAS TYPE

Use the correct gas type (natural or propane/

LP) for your unit. If your gas supply is not cor-

rect, DO NOT install this into your fireplace. 

See the dealer where you bought the appli

-

ance for proper type. 

 WARNING: This appliance is 

equipped for either natural gas 

or propane/LP gas but not both. 

Gas type is indicated on the rat

-

ing plate. Field conversion is not 

permitted.

INSTALLATION AND CLEARANCES

The charts in Figure 2 indicate technical 

information regarding the installation of your 

gas log set. Please make sure that all of the 

specifications  shown  are  applicable  before 

installation is attempted.

FLUE OPENING SPECIFICATIONS

Note: This vented appliance must be installed 

only in a solid-fuel burning fireplace construct

-

ed of noncombustible material. The fireplace 

must include a flue and venting system with 

the minimum openings shown in Figure 3.

Summary of Contents for VTD-18NV-JHB

Page 1: ...touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the appliance CONSUMER Retain this manual f...

Page 2: ... with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING This appliance is for installation only in a solid fuel burning masonry or UL127 factory built fireplace constructed of noncombustible material and connected to a working flue See page 6 for minimum flue opening WARNING This is a gas fired heater It uses air oxygen from the room in which it is ...

Page 3: ...edforusewithtypeofgas indicated on rating plate WARNING Donotallowfans toblowdirectlyintothefireplace Avoidanydraftsthatalterburner flame patterns Due to high temperatures the appliance should be located out oftrafficandawayfromfurniture and draperies SAFETY Continued Do not place clothing or other flammable material on or near the appliance Never place any objects on the heater Appliance base ass...

Page 4: ...he creation of soot follow the instructions in Cleaning and Maintenance page 13 8 The installation and provisions for com bustion and ventilation air must conform with the National Fuel Gas Codes ANSI Z233 1 NFPA 54 Air for Combustion and Ventilation 9 To prevent performance problems do not use propane LP fuel tank of less than 100 lb capacity propane LP units only 10 Do not run log set where flam...

Page 5: ...no matches batteries or other sources to light appliance OPTIONAL ACCESSORIES VTD HLCN P Converts valve from ON OFF to HI LO OFSM RCN P Converts valve from ON OFF to HI LO for use with hand held ON OFF remote included OF RC Converts ON OFF valve for use with hand held ON OFF remote See Accessories page 19 INSTALLATION WARNING Before installing in a solid fuel burning fireplace the chimney flue and...

Page 6: ...UT MIN VENT OPENING VTD 18NV JHB VTD 18PV JHB 18 Ramp 59 000 8 dia VTD 24NV JHB VTD 24PV JHB 24 Ramp 69 000 8 dia VTD 30NV JHB VTD 30PV JHB 30 Ramp 74 000 8 dia MINIMUM FIREBOX SIZES MODEL FRONT WIDTH BACK WIDTH DEPTH HEIGHT VTD 18NV JHB VTD 18PV JHB 28 16 14 18 VTD 24NV JHB VTD 24PV JHB 29 3 4 20 15 1 2 18 VTD 30NV JHB VTD 30PV JHB 36 27 18 18 At depth indicated BURNER ORIFICE LOG SIZE NATURAL PR...

Page 7: ...nce if allowed by local codes sealant resistant to propane LP gas not provided 1 Apply pipe joint sealant lightly to male threads of gas fitting not provided Con nect approved flexible gas hose to inlet side of gas control valve see Figure 5 Figure 5 Attaching Flexible Gas Hose to Gas Control Valve Flexible Gas Hose If Allowed by Local Codes Gas Control Valve INSTALLATION Continued 2 Position appl...

Page 8: ...ec tor if allowed by local codes provided An equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the optional equipment shutoff valve from your dealer For propane LP units the installer must supply an external regulator The external regulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If ...

Page 9: ... 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its individual equipment shutoff valve from gas supply piping system Pressure in excess of 1 2 psig will damage appliance regulator 2 Cap off open end of gas pipe where equip ment shutoff valve was connected 3 Pressurize supply piping system by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near g...

Page 10: ...n main gas valve located on or near gas meter for natural gas or open pro pane LP supply tank valve 3 Make sure control knob of appliance is in the OFF position 4 Check all joints from equipment shutoff valve to gas control see Figure 9 page 9 or Figure 10 Apply noncorrosive leak detection fluid to all joints Bubbles form ing show a leak 5 Correct all leaks at once 6 Light appliance see Operation ...

Page 11: ...n This will light pilot If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for repairs Until repairs are made light pilot with match To light pilot with match see Manual Lighting Procedure page 12 8 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob If cont...

Page 12: ...of orange flame If burner flame pattern is incorrect as shown in Figure 13 turn appliance off see To Turn Off Gas to Appliance page 12 see Troubleshooting page 13 MANUAL LIGHTING PROCEDURE 1 Follow steps 1 through 6 under Lighting Instructions page 10 2 Depress control knob and light pilot with match 3 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release contr...

Page 13: ... in PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 Pilot is clogged 7 Gas regulator setting is not correct Whenignitorbuttonispressed there is no spark at pilot Whenignitorbuttonispressed there is spark at pilot but no ignition 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding pi...

Page 14: ...ob is released One or both burner does not light after ODS pilot is lit Delayed ignition of burner Burner backfiring during combustion 1 Press in control knob fully 2 After pilot lights keep con trol knob pressed in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas company B ...

Page 15: ...ers are lit Whitepowderresidueforming within burner box or on adja cent walls or furniture Remote does not function Appliance produces a click ing ticking noise just after burners are lit or shut off 1 Check burner for dirt and debris If found clean burner see Cleaning and Maintenance page 12 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO posit...

Page 16: ...ners chemi cals new carpet etc See IMPORTANT statement above 2 Low fuel supply propane LP only 3 Gas leak See Warn ing statement at top of page 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warn ing statement at top of page 2 Control valve or gas con trol defective 1 Foreign matter between control valve and burner 2 Gas leak See Warn ing st...

Page 17: ...e Gas Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure in of water Max 10 5 W C Min 5 0 W C VTD 18PV JHB Rating Variable 59 000 Btu Hr Type Gas Propane LP Ignition Piezo Manifold Pressure 10 W C Inlet Gas Pressure in of water Max 14 W C Min 11 W C VTD 24PV JHB Rating Variable 69 000 Btu Hr Type Gas Propane LP Ignition Piezo Manifold Pressure 10 W C Inlet Gas Pressure in of water...

Page 18: ...ropane LP units propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP or natural gas supplier TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact FMI PRODUCTS LLC at 1 866 328 4537 When calling please have your model and serial numbers of your heater ready You can also visit our web ...

Page 19: ...ess listed on the back page of this manual LAVA ROCK GA6060 Order when additional rock is desired 1 8 lb bag DAMPER CLAMP GA6080 Permanently opens chimney flue damper for vented operation ON OFF REMOTE CONVERSION KIT OF RC Converts ON OFF valve for use with hand held ON OFF remote HI LO CONVERSION KIT VTD HLCN NG VTD HLCP LP Converts valve from ON OFF to HI LO ON OFF HI LO REMOTE CONVERSION KIT OF...

Page 20: ...www fmiproducts com 114370 02H 20 PARTS MODELS VTD 18NV JHB VTD 24NV JHB VTD 30NV JHB 2 10 11 26 27 28 20 13 7 9 13 19 1 8 12 3 5 6 4 12 5 24 29 22 18 13 23 14 17 15 16 13 29 21 25 12 12 ...

Page 21: ...98 01 Switch 1 16 103284 02 Wire Harness 1 17 103784 01 ON OFF Extension Knob 1 18 14512 Valve MV NG 1 14513 Valve MV LP 1 19 112804 05 Valve Bracket 1 20 114395 01 Pilot Bracket 1 114395 02 Pilot Bracket 1 21 116910 01 Brass 3 8 NPT Coupling 1 22 117005 01 Shroud 1 23 117005 02 Face Plate 1 24 14264 Elbow 90 Brass 3 8M x 3 8 FLRE 1 25 901062 01 Brass Elbow 1 26 901075 01 Screw PH 8 x 0 25 2 27 90...

Page 22: ..._____________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 23: ..._____________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ________________________________...

Page 24: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs associated with warranty repairs unless expressly covered by this warranty are not reimbursable under this warranty and are the responsibility of the owner Excluded f...

Reviews: