20
Belt Length
25” to 50”
51” to 70”
71” to 110”
Deflection
0.25”
0.375”
0.625”
Specified Belt Deflection
Figure 10 - Specified Belt Deflection Table
HP
0.5
1
1.5
2
3
5
7.5
10
15
20
25
30
40
1 Belt
3
7
12
Belt Deflection Force
2 Belts
7
12
3 Belts
12
2 Belts
5 - 6
8 - 9
New Belt Force (lbs.)
Used Belt Force (lbs.)
1 Belt
2 - 2.5
5 - 6
9 - 10
3 Belts
8 - 9
Figure 11 - Belt Deflection Force Table
3.2
System Operation Modes
OPTIONAL O/A Box with
2-Position Damper
F
I
L
T
E
R
F
I
L
T
E
R
F
I
L
T
E
R
COMPRESSOR
Hot Gas Reheat Coil
Condensate Drain
Evaporator Coil
OPTIONAL Temperature Sensor
Humidity Sensor
OPTIONAL Remote Condenser
Figure 12 - LW Options that Impact System Operation Modes
Desert Aire - LW Manual
Summary of Contents for LW
Page 2: ...2 ...
Page 6: ...6 Desert Aire LW Manual ...
Page 26: ...26 Desert Aire LW Manual ...
Page 32: ...32 Desert Aire LW Manual ...