TroublesHooTIng

Continued 

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, 
there  is spark  at pilot  but no 
ignition.

1. Gas  supply  turned  off  or 

equipment  shutoff  valve 
closed.

2. Control knob not in PILOT 

position.

3. Control knob not pressed in 

while in PILOT position.

4. Air  in  gas  lines  when  in

-

stalled.

5. Pilot  adjustment  screw 

closed.

6. Pilot is clogged.

7. Low gas pressure.

1. Turn on gas supply or open 

equipment shutoff valve.

2. Turn control knob to PILOT 

position.

3. Press in control knob while 

in PILOT position.

4. Continue holding down con

-

trol knob. Repeat igniting op

-

eration until air is removed.

5. Adjust  pilot  flame  for  ap

-

proximately 2" blue flame.

6. Clean  pilot  (see 

Cleaning 

and Maintenance

, page 14) 

or replace pilot assembly.

7. Replace gas control.

Pilot  lights  but  flame  goes 
out  when  control  knob  is 
released.

1. Control  knob  not  fully 

pressed in.

2. Control knob not pressed in 

long enough.

3. Equipment shutoff valve not 

fully open.

4. Pilot  flame  not  touching 

thermocouple,  which  al

-

lows thermocouple to cool, 
causing  pilot  flame  to  go 
out. This problem could be 
caused  by  one  or  both  of 
the following:

  A) Low gas pressure
  B) Dirty or partially clogged 

pilot 

5. Thermocouple  connection 

loose at control valve.

6. Thermocouple damaged.
7. Control valve damaged.

1. Press in control knob fully.

2. After pilot lights, keep con

-

trol  knob  pressed  in  30 
seconds.

3. Fully open equipment shut

-

off valve.

4. A) Contact local natural gas 

company.

 

  B) Clean pilot (see 

Cleaning 

and Maintenance

, page 14) 

or replace pilot assembly.

5. Hand tighten until snug, then 

tighten 1/4 turn more.

6. Replace thermocouple.
7. Replace control valve.

Burner  does  not  light  after 
pilot is lit.

1. Burner orifice clogged.
2. Inlet  gas  pressure  is  too 

low.

3. Thermocouple  leads  dis

-

connected  or  improperly 

connected.

1. Clean burner orifice.
2. Contact  local  natural  or 

propane/LP gas company.

3. Reconnect leads.

Delayed ignition burner.

1. Pilot  flame  needs  adjust

-

ing.

2. Wrong pilot orifice.

1. Adjust  pilot  flame  for  ap

-

proximately 2" blue flame.

2. Replace pilot orifice set.

Summary of Contents for VVDA30R

Page 1: ...not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this o...

Page 2: ...shock and carbon monoxide poisoning DANGER Carbonmonoxide poisoning may lead to death Carbon Monoxide Poisoning Early signs of carbon monoxide poisoning resemble the flu with headaches dizziness or n...

Page 3: ...Continued flamepatterns Ceilingfanscancreatedrafts that alter burner flame patterns Altered burner patterns can increase sooting 9 Do not use a blower insert heat exchang er insert or other accessory...

Page 4: ...to convert to propane LP gas use WARNING The Massachu setts State Board requires all installations be performed by a Licensed Plumber or Gas Fit ter Massachusetts state code requires all vent dampers...

Page 5: ...he flame and remove any obstruc tion until proper venting is achieved Burner Orifice LOG SIZE Natural Propane LP In Num CLR In Num CLR 18 SA DA 0 129 30 Green 0 073 49 Red 24 SA 0 141 28 Yellow 0 086...

Page 6: ...er 5 W C to 10 5 W C Pressure CSA Design Certified Equipment Shutoff Valve With 1 8 NPT Tap Approved Flexible Gas Hose no longer than 36 if required by local codes Damper Damper Clamp Damper Manufactu...

Page 7: ...ose equipment shutoff valve see Figure 5 2 Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter 3 Check all joints from gas meter to eq...

Page 8: ...7 Removing Installing Thermocouple Pilot and Piezo Ignitor Cover Figure 8 Remove Burner Inlet Fitting Burner Inlet Fitting for Natural Gas Burner Pan 7 Using thread sealant resistant to the ac tion o...

Page 9: ...e see Figure 12 with pro pane LP pilot orifice with red stripe 3 Replace and tighten pilot line to bracket 4 Reattach pilot and piezo ignitor assembly to valve cover with screws previouly removed see...

Page 10: ...ons included with ac cessory Connect wires as shown in Figure 13 You will need to route wiring away from gas control and log set in a way which prevents direct radiant heat on wires No Optional Access...

Page 11: ...r because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building...

Page 12: ...er by the edge of the burner pan to look for flame If needed keep pressing ignitor button until pilot lights O F F P I L O T O N Figure 17 Control Knob and Ignitor Button Location Shown as Supplied No...

Page 13: ...del HRC201 Hold the control button on the hand held remote until burner turns on Hold the control button again until burner turns off To Lock press both buttons on hand held remote control until light...

Page 14: ...clean and clear of debris Occasionally you may use a soft bristle brush to clean logs Periodically inspect the air mixer and burner tube for foreign matter blocking the air inlet and flame holes Once...

Page 15: ...ssage of air gas across irregular surfaces 2 Excessive gas pressure on natural gas units 1 Relieve any tight bends or kinks in gas supply line 2 Have inlet gas pressure checked by a qualified ser vice...

Page 16: ...long enough 3 Equipment shutoff valve not fully open 4 Pilot flame not touching thermocouple which al lows thermocouple to cool causing pilot flame to go out This problem could be caused by one or bo...

Page 17: ...king ticking noise just after burner is lit or shut off 1 Metal expanding while heating or contracting while cooling 1 This is normal with most log sets If noise is excessive contact qualified service...

Page 18: ...desatech com 901273 01H 18 Parts Models VVSA18R VVSA24R VVDA18R VVDA24R and VVDA30R FVSA18R FVSA24R FVDA18R FVDA24R and FVDA30R I L 3 15 18 21 16 13 24 6 4 17 22 20 17 14 23 10 7 5 5 9 9 11 12 1 19 2...

Page 19: ...0 01 Grate Steps 2 901431 01 Grate Steps 2 10 901243 01 Log Grate 1 901243 02 Log Grate 1 901246 01 Log Grate 1 901246 02 Log Grate 1 901246 03 Log Grate 1 11 901681 01 Burner STrap 1 12 901078 01 Nut...

Page 20: ...R 13 VC Top Log 1 9 901587 01 901587 01 901587 01 VCR 9 Top Log 1 10 901625 03 901626 03 Bottom Rear 1 11 901583 01 901584 01 Bottom Front 1 12 901541 02 901541 02 CPR 13 VR Top Log 1 13 901580 01 901...

Page 21: ...901614 01 901614 01 FS15 Top Log 1 9 901623 02 FR14 Top Log 1 10 901625 01 901626 01 Bottom Rear Log 1 11 901635 01 901636 01 Bottom Front Log 1 12 901620 01 901620 01 FR12L Top Log 1 13 901622 01 90...

Page 22: ...of this product If they can t supply original replacement part s call DESA Heating LLC at 1 866 672 6040 for referral information A list of authorized dealers can be found by visiting www desatech co...

Page 23: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 24: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: