background image

PENETRAT�NG  THE  ROOF 

To  maintain  a  ]-inch  clearance  to  the  pipe  on 

roof with  a 

pitch,  a rectangular opening must be  cut. 

STEP 

1:  Determine  the  center  point  through  which  the  pipe 

will penetrate the roof. 

STEP 

2:  Detem1ine the  center point  of the  roof.  Pitch  is  the 

distance  the  roof drops  over  a given  span,  usually  12  inches. 

A 6/12  pitch  means  that  th  

:oof 

drops  6 inches  for  each  12 

inches  one measure horizontally down  f

r

om the roof rafters. 

STEP 

3:  Use  the roof opening  chart (figure  11)  to  determine 

the conect opening length and  flashing required. 

STEP 

4: 

Remove  the  shingles  around  the  opening measured 

and cut out this  section. 

STEP 

5: 

Add  the  next  sections  of the  pipe  until  the  end 

penetrates  the  roofline.  Check  to  see  that  the  proper 

clearances  are  maintained.  Extend  chimney  by  adding 

sections  of double  wall  pipe  until  pipe  is  a minimum  of 30 

inches above the highest point of the  roof cutout.  Tem1ination 

and  chimney  must  extend  a minimum  of 36  inches  above  the 

highest point where it passes through roof. 

PITCH 

SLOPE 

OPENING  "A"  MAX 

USE  FLASHING 

(deqrees) 

/inches) 

MODEL  NO. 

FLAT 

15 

V6F-8DM 

0-6/12 

26.6 

16  • 1/8 

V6F-8DM 

6112  - 12/12 

45.0 

20  • 3/8 

V12F-8DM 

Figure 11 

ROOF OPENING CHART 

FLASHING INSTALLATION  (V6F-8DM 

or 

Vl2F-8DM) 

Determine the  flashing to  be  used with the roof opening chart. 

Slide flashing over pipe until base is  flat against roof.  Replace 

as  many shingles as needed to  cover exposed area  and  flashing 

base.  Secure  in  position  by  nailing  through  shingles  (see 

figure  12). 

DO  NOT NAIL THROUGH  FLASHING  CONE. 

- 6 -

£NS'fALLING  FLASHING  ON 

A METAL 

ROOF 

When  installing the flashing on  a metal  roof,  it is  required that 

putty  tape  be  used  between  the  flashing  and  the  roof  The 

flashing must  be  secured  to  the  roof using #8  x ¾"  screws  and 

then  sealed  with  roof coating  to  prevent  leakage  through  the 

screw  holes.  A roof coating must  also  be  applied  around  the 

perimeter of the flashing to  provide a proper seal. 

·-

-

:. 

···:

"="'

  --

Figure 12 

FLASHING  INSTALLATION 

STORM  COLLAR INST ALLA. TION  (SCI  or  SC2) 

Place  storm  collar  over  pipe  and  slide  down  until  it  is  snug 

against the open  edge of the  flashing (see figure  J 3).  Use  SCJ 

for  all  round  terminations  and  SC2  for  all  tem1inations  with 

slip  sections.  Apply waterproof caulk around the perimeter of 

the collar to  provide 

_a 

proper seal. 

Figure 13 

STORM  COLLAR 

For more information, 

1

1

isit wwmtfcsatech.com 

Summary of Contents for VS36(1)

Page 1: ...This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z2 l 60 Z2 l 84 or RGA 2 72 standards QLfor use with a vent free gas log heater approved to ANS Z2 l l l 2 standard A DESA hood must be installed when using a vent f r ee gas log heater see Accessories p 12 WARNING Always leave glass doors fully opened or fully closed when operating this...

Page 2: ...IMNEY PIPE AND OFFSET INSTALLATION PG 45 8 FIRESTOP SPACERS PG 5 _ 9 FLASHING AND TERMINATION PG 6 7 10 FINISHING YOUR FIREPLACE PG 7 11 MANTELS PG 8 12 GLASS DOORS PG 8 l3 GAS LINE INSTALLATJONS PG 9 14 DAMPER OPERATION PG JO 15 TECHNICAL SERVICE PG 10 16 ILLUSTRATED PARTS PG 11 1 la I7 REPLACEMENT AND TECHNICAL PARTS PG 12 1 For more i11formatio11 visit www dcsatcch com ...

Page 3: ... packaging prior to use 2 This fireplace is not intended o b e used z s 2 substitute for a furnace to heat rn er tire home Use for supplemental heat onl This wood buming fireplace complies with UL 127 CAN ULS S610 M87 standard as a FACTORY BUILT FIREPLACE FOR CANADA The authmity ha ing jurisdiction such as the municipal building department fire department etc should be contacted before installatio...

Page 4: ...door installations the fireplace enclosure must allow for adequate drainage and f r esh air ventilation It is recommended that a sealed corrosion resistant catch pan with provision for drainage be installed under the f ir eplace within the fireplace enclosure I r j j I I Figure I 4 r 1 li ii I I 1 Ii I I i I I CORNER INSTALLATION 3 figure 2 3791 COR l l ER INSTALLATION HEARTH EXTENSION A Mah exten...

Page 5: ...l t L 1 t l _ l Figur e 5 i I l iH l _ rt r t t S 1 _ t 1 LINEAL GAIN For Canada use chimney parts designated HT When connecting chimney directly to the fireplace th iru ie flue pipe section iimst _be installed first ith the lanc if sid_ up The outer pipe s ection ean then be installed over the tlije pipe section with the he1J1med end up Press down _on each pipe ection until the lances _securely e...

Page 6: ... 97 1 1 53 1 4 101 2 1 56 1 4 106 1 4 2 59 1 0 111 1 2 1 1 1 61 3 4 115 1 2 2 1 64 314 120 3 4 2 1 68 1 4 127 1 2 70 130 2 1 1 74 1 4 137 1 2 1 2 1 76 3 4 1 1 1 2 1 2 1 79 3 4 146 3 4 4 I clAL Figure 7 CEILING SUPPORT PIPE FIRESTOP SPACERS V3600FS 8DM Firestop spacers are required at each point where the chimney penetrates a floor space Their purpose is to establish and maintain the required clear...

Page 7: ...hes MODEL NO FLAT 0 1 5 V6F 8DM 0 6 12 26 6 16 1 8 V6F 8DM 6112 12 12 45 0 20 3 8 V12F 8DM Figure 1 1 ROOF OPENING CHART FLASHING INSTALLATION V6F 8DM or Vl2F 8DM Determine the flashing to be used with the roof opening chart Slide flashing over pipe until base is flat against roof Replace as many shingles as needed to cover exposed area and flashing base Secure in position by nailing through shing...

Page 8: ...chase style termination chosen In a multiple chase installation be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another We suggest that terminations be separated at least 24 inches center to center and stacked at vertical height difference of 18 inches see figure 15 Figure 15 MULTIPLE CHASE INSTALLATION NOTE If a decorative shroud is to b...

Page 9: ...is built or if the combustion air gate is not completely open The following tips should be followed to assure that both the fireplace and the glass door retain their beauty and function properly Both the flue damper and the glass doors must be fully opened before starting the fir e This will provide sufffcient combustion air and maintain safe temperatures iil the firebox _ _ IL_V CL l FU CE C T Fi...

Page 10: ...raming to provide rigidity for threaded end STEP 4 Repack insulation around gas line and into sleeve opening Seal any gaps berween gas line and refractory knockout hole with refr actory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired 9 Figure 20 f P C E J c F 1 F L t r I L hf ___ _ L c 1 1 I v t c GAS LINE JNSTALLATION CAUTION All gas piping and connect...

Page 11: ...air kit handle is located at the left hand side ofthe fireplace see figure 21 Pulling the handle out will free the outside air door to open Pushing the handle in will lock the door close l O ii WARNING Risk of fire Replace grate with DESA model 111028 01 grate only This grate has been designed to keep the operation of your fireplace safe and efficient FOR FURTHER OPERATING GUIDELINES INSTRUCTIONS ...

Page 12: ...ILLUSTRATED PARTS 12 r7 _ 25 11 a For more informatinn visit www desatech com ...

Page 13: ...BLY 1 106694 01 I06694 01 l06694001 106694 0l_ l 06694 0I _ i 06694 0 I 19 AIR KJT DOOR ASSEMBLY J l06703 01 l06703 01 I06703 01 106703 01 l06703 01 r66103 20 FACE WELDMENT 1 l 10901 01 l 10901 01 l 10901 01 l I0901 01 110901 01 110901 Dl 21 AJR DEFLECTOR l 110892 01 110892 0L J l0892 0 l lJ 0892 0 I I I0892 01 l 1089f61 22 FIREPLACE TOP INSULATION 1 107768 01 107768 01 l07768 01 l07768 01 107768 ...

Reviews: