background image

www.desatech.com

108795-01V

9

INSTALLING TRANSITION PIPE AND 
STARTER COLLAR

The transition pipe and starter collar shown 
in  Figure  9  are  supplied  with  the  fireplace, 
unattached  and  ready  for  installation.  Re-
move  starter  collar  and  set  aside.  Slide 
transition  pipe  over  vent  collar  and  attach 
with  a  minimum  of  three  screws.  Replace 
starter collar over transition pipe and attach 
using four screws located on leg stands (five 
used on model M42). To install B-vent piping, 
slide the first piece of B-vent over transition 
pipe and attach with either a minimum of two 
screws or other means approved by the vent 
manufacturer.

Figure 9 - Installing Transition Pipe and 

Starter Collar

B-Vent Piping

Transition Pipe

Starter Collar

Vent Collar

Pre-INstallatIoN PreParatIoN

Continued

VeNtING INstallatIoN

60° or greater. The total vertical height in this 
example represents the minimum height of 8 
feet and therefore the allowable lateral is 6 
feet when the 75% rule applies. If the lateral 
length  must  exceed  75%  then  the  system 
must be sized in accordance with Category I 
venting tables.

Example 2:

 Shows a multiple offset each at 

45° of inclination. Multiple offsets are permit-
ted if they do not exceed 45° of inclination. The 
total lengths of the two offsets are not required 
to meet the 75% allowable rule.

Example 3: 

Shows a single offset at 45° of 

inclination and therefore the lateral length at 
10 feet of offset does not have to meet the 
75% rule.
In each case the offsets must be supported 
and  firestops  must  be  positioned  wherever 
the vent must pass through a sub-floor, ceil-
ing joist or an attic overhang. The vent pipe 
must terminate vertically into a listed type vent 
cap  and  extend  a  sufficient  height  through 
an approved roof flashing, roof jack or a roof 
thimble. At all points listed clearances must 
be maintained.
Vent  terminations  must  be  located  in  ac-
cordance with height and proximity rules of 
NFPA No. 54. These rules apply to vents at 
12" diameter or less and require a minimum 
height in accordance with the roof pitch and a 
minimum of 8 ft. distance from a vertical wall 
or obstruction (see Figure 11, page 10).

A B-type venting system must be connected 
to the appliance for venting to the outside of 
the building.
The following section is provided as a guide 
to a standard B-type vent installation.
Standing codes requirements concerning B-
type vent installations may vary within your 
state,  province  or  local  codes  jurisdiction. 
Therefore, it is recommended that you check 
with  your  local  building  codes  for  specific 
requirements  or  in  absence  of  local  codes, 
follow Section 7.0 of the current 

National Fuel 

Gas Code ANSI Z223.1/NFPA 54

.

This  gas  appliance  must  be  vented  to  the 
outdoors only and may not be terminated into 
an attic space or into a chimney flue servicing 
a solid fuel burning appliance.
This  appliance  may  be  vented  through  a 
manufactured chimney system or a masonry 
chimney  using  a  B-vent  adapter  or  a  chim-
ney  liner  system  if  all  are  listed,  inspected 
and approved by local codes and/or building 
authorities.
The examples shown in Figure 10, page 10 
are  typical  of  most  B-vent  installations  and 
codes practices.

Example  1:

  Shows  the  minimum  allowable 

system height and lateral offset for a 60° or 
greater inclination. Code specifies that offsets 
at  60°  or  greater  are  considered  horizontal 
and  must  follow  the  75%  rule  for  lateral  to 
total vertical system height. Codes also allow 
only  one  offset  in  the  total  system  when  at 

Summary of Contents for VM36B

Page 1: ...t any appliance Do not touch any electrical switch Do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach...

Page 2: ...e may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by state or local codes This appliance is only for use with the type of gas indi cated on the ra...

Page 3: ...to excessive lint and dust from carpeting bedding material etc Turn off the gas valve and pilot light before cleaning fireplace 10 Have venting system inspected annually by a qualified service person...

Page 4: ...ms are packed inside the firebox Remove before positioning firebox into framing Transition Collar For vent connection Ceramic Log Pack Shrink wrapped on cardboard Three 3 plastic bags containing lava...

Page 5: ...sting ofthegassupplypipingsystemattestpressures equal to or less than 1 2 psig 3 5 kPa For the purpose of input adjustment two pressure taps for IN and OUT pressures are provided on the gas control va...

Page 6: ...ximum Supply Pressure 13 WC 3 23 kPa 13 WC 3 23 kPa Orifice Size 52 51 S T P Q R X Outside Air Kit Location Optional K 7 J I M L V 13 5 1 5 Glass Door Optional W O N Alternate Gas Supply Inlet 7 G H F...

Page 7: ...le components in relation to fireplace opening Spacer 3 7 6 cm 1 1 2 3 8 cm Max B 6 15 2 cm A 12 22 9 cm Combustible Materials Header Figure 5 Mantel Clearances Side View Cross Section M36 B H M36P B...

Page 8: ...to the flexible gas line Note If 1 2 NPT black iron pipe does not mate with fitting at the end of flexible gas line remove fitting and replace with a 37 flare 3 4 12 1 2 NPT female fitting WARNING Wh...

Page 9: ...minate vertically into a listed type vent cap and extend a sufficient height through an approved roof flashing roof jack or a roof thimble At all points listed clearances must be maintained Vent termi...

Page 10: ...nspected for damage and proper installation It is not recommended that this appliance be common vented with an existing gas burning appliance Note Before connecting this appliance to an existing vent...

Page 11: ...E This appliance is equipped with a vent safety shutoff switch which will shut down the appliance in the case of a venting problem Do not bypass the vent safety switch If theapplianceshouldshutdown co...

Page 12: ...g optional wireless hand held remote control the wall switch is no longer operational Installing Receiver 1 Remove front refractory access panel by lifting up and angling out of firebox open ing see F...

Page 13: ...and Held Remote Control Unit Battery Cover 9 Volt Battery Terminal Wires Remote Control Unit Battery Housing Installation Continued DESAHeating LLC recommends that a black iron gas line be routed from...

Page 14: ...ear leaks can be detected and corrected Donotuseanopenflameforleak testing and do not operate any appliance if a leak is detected Installation Continued Complete your gas installation by connect ing i...

Page 15: ...5 into notch on left of log 2 see Figure 27 Rest lower end of log 5 on grate as shown in Figure 28 6 Insert lower end of log 6 between first two grate fingers as shown in Figure 28 and position upper...

Page 16: ...e upper end of log 5 into notch on top inner right of log 1 see Figure 31 Rest lower end of log 5 on middle grate finger as shown in Figure 32 6 Place log 6 into notch on top right of log 1 see Figure...

Page 17: ...tion Figure 34 Sealing Between Appliance and Framing Installing optional GLASS DOOR Accessory CAUTION Use only glass doors certified for use with this appliance Note Glass door may be heavy for some i...

Page 18: ...pin is free of clip 2 Fully fold frame assembly and slide upper edge towards center of firebox opening until guide pins are free of frame rail see Figure 37 CAUTION Always operate the appliance with t...

Page 19: ...l Knob in the PILOT position Position Indicator Gas Control Knob Pilot Adjustment Screw FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these instructions exactly a fire or explosio...

Page 20: ...remote control unit IMPORTANT Do not leave selector switch in the REMOTE or ON position when pilot is not lit This will drain the battery 2 Press control button on hand held remote to turn burner on...

Page 21: ...to excessive lint from carpeting bedding mate rial pet hair etc It is imperative that the control compartments burners and circulating air sys tem be kept clean WARNING The logs can be hot Handle onl...

Page 22: ...t part number Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Parts Under Warranty Contact authorized dealers of this product If the...

Page 23: ...tch wires defective or too long 2 Thermopile not generating sufficient voltage 1 Pilot flame may be too low causing safety pilot to drop out 2 Improper venting or exces sive blockage REMEDY 1 Check to...

Page 24: ...If no spark and electrode wire is properly connected replace ignitor 2 Using a match light pilot If pilot lights turn off pilot and trigger the red button again If pilot lights an improper gas air mi...

Page 25: ...LP gas low fuel supply 3 Gas leak See Warning statement at top of page 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas...

Page 26: ...odels M36 B H M36P B H M42 B H M42P B H VM36 B H VM36P B H VM42 B H and VM42P B H 43 21 1 10 11 6 8 8 22 25 13 4 14 45 17 3 44 40 39 41 42 9 7 46 19 47 7 47 20 5 16 12 15 25 33 31 28 32 27 11 24 18 38...

Page 27: ...bly 1 23 20042 20042 Air Kit Cover 1 24 106948 02 107823 02 Smoke Deflector 1 25 20027 20027 Brick Liner Retainer 2 26 107796 01 107796 02 Grate Assembly 1 27 107742 01 107742 02 Burner Pan 1 28 10779...

Page 28: ...6 02 108171 02 Rear Refractory Herringbone M36H M42H 1 106660 01 107816 01 Rear Refractory Std Brick VM36B VM42B 1 108166 01 108171 01 Rear Refractory Herringbone VM36H VM42H 1 15 106661 02 107818 02...

Page 29: ...VM36P B H KEY NO PART NUMBER DESCRIPTION QTY 107999 01 Log Set 1 108724 01 Right Front 9 Split Log 1 2 901098 01 Rear Log 1 3 108720 01 Top Right Log 11 3 4 1 4 108721 01 Top Right Log 16 1 5 108722 0...

Page 30: ...01 Left Front Log 11 1 2B 108839 01 Right Front Log 15 3 4 Round 1 3 108722 01 Top Left Log 13 1 2 Y Log 1 4 108838 01 Inside Top Left Log 15 3 4 Split 1 5 108721 01 Inside Top Right Log 16 1 6 10872...

Page 31: ...For M36 B H M36P B H M42 B H and M42P B H BL36 36 Refractory Standard Brick BL42 42 Refractory Standard Brick BL36H 36 Refractory Herringbone Brick BL42H 42 Refractory Herringbone Brick For VM36 B H...

Page 32: ...ns furnished with this product This warranty covers the cost of part s required to restore this product to proper operating condition and an allowance for labor when provided by a DESA Heating LLC Aut...

Reviews: