For more information, visit www.desatech.com

4

PRODUCT FEATURES

These are a few facts that can help you understand and enjoy your
direct-vent fireplace:

• The venting system may be routed to the outside of your home

in several ways. It may vent through the roof (vertical) or it may
vent to an outside/exterior wall (horizontal). The vent pipe in-
stallation is very important to allow for proper operation. You
must follow the venting instructions very carefully for either
vertical or horizontal applications.

• This fireplace may be installed in any room of your house provided

all local codes and these installation instructions are followed.

• This fireplace does not require electricity to operate.

• Only the blower requires electricity if installed and if you plan

to install the blower at a later date, do not forget to wire the
outlet at the bottom of the fireplace when framing.

• A piezo ignitor and ceramic electrode create spark to ignite the

pilot light. It does not require any matches, batteries or any other
sources of ignition to light the pilot.

• Each time you turn on your fireplace, you may notice some

amount of condensation on the inside of the fireplace glass. This
is normal and will disappear after 10-20 minutes of operation.

• Your direct-vent gas fireplace system (fireplace and venting) is a

balanced and sealed gas operating unit. It requires approximately
10-20 minutes of operating time before the flame pattern stabilizes.

PRE-INSTALLATION
PREPARATION

LOCATION AND SPACE REQUIREMENTS

Determine the safest and most efficient location for your DESA
direct-vent fireplace. Make sure that rafters and wall studs are not
in the way of the venting system. Choose a location where the heat
output is not affected by drafts, air conditioning ducts, windows or
doors. Figure 2 shows some common locations. Be aware of all
restrictions and precautions before deciding the exact location for
your fireplace and termination cap.

When deciding the location of your fireplace, follow these rules:

• Do not connect this fireplace venting to a chimney flue serving

a separate solid-fuel burning fireplace or appliance.

• Due to high temperatures, do not locate this fireplace in high traf-

fic areas, windy or drafty areas, or near furniture or draperies.

• Proper clearances must be maintained.

• If your fireplace is to be installed directly on carpeting, vinyl

tile, or any combustible material other than wood, it must be
installed on a metal or wood panel extending the full width and
depth of the fireplace. See Figure 3.

• Your fireplace is designed to be used in zero clearance installa-

tions. Wall or framing material can be placed directly against
any exterior surface on the back, sides, or top of your fireplace,
except where standoff spacers are integrally attached. If stand-
off spacers are attached to your fireplace, these spacers can be
placed directly against wall or framing material. See framing
details on page 5.

• If you plan on installing a television or entertainment center re-

cessed above your fireplace, it is recommended that you main-
tain a minimum 18" above top of louver opening.

• When locating termination cap, it is important to observe the

minimum clearances shown in Figure 7, page 6.

• If recessing into a wall, you can avoid extra framing by position-

ing your fireplace against an already existing framing member.

• Do not recess termination cap into a wall or siding.

• You may paint the termination cap with 450ºF (232ºC) heat-

resistant paint to coordinate with the exterior finish.

• There must not be any obstruction such as bushes, garden sheds,

fences, decks, or utility buildings within 24" from the front of
the termination cap.

• Do not locate termination cap where excessive snow or ice build

up may occur. Be sure to clear vent termination area after snow
falls to prevent accidental blockage of venting system. When
using snow blowers, do not direct snow towards vent termina-
tion area.

PRODUCT FEATURES
PRE-INSTALLATION PREPARATION

Location and Space Requirements

Figure 2 - Common Fireplace Locations

Flush with a wall

Through exterior wall
enclosed in a chase

Corner
installation

Figure 3 - Fireplace Bottom Dimensions

D

RW

FW

23 

1

/

4

"

48"

36 

1

/

4

"

Summary of Contents for Victorian V42EN-A Series

Page 1: ...ion adjustment alteration service or maintenance can cause injury orpropertydamage Refertothis manual for correct installation and operational procedures For assistance or additional infor mation cons...

Page 2: ...Itbringsinfreshairforcombustionthroughtheouterpipeand combustion gases are exhausted through the inner pipe If the glass door assembly and venting pipe are not properly seated connected and sealed car...

Page 3: ...e this fireplace to cook food or burn paper or other objects 13 Do not use any solid fuels wood coal paper cardboard etc in this fireplace Use only the gas type indicated on fireplace nameplate 14 Thi...

Page 4: ...he location of your fireplace follow these rules Do not connect this fireplace venting to a chimney flue serving a separate solid fuel burning fireplace or appliance Due to high temperatures do not lo...

Page 5: ...s tible mantels may discolor PRE INSTALLATION PREPARATION Continued NOTICE This fireplace is intended for use as supple mental heat Use this fireplace along with your pri mary heating system Do not in...

Page 6: ...inlet 72 inches 1829mm minimum L clearance above paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck 12 inches 305mm minimum N...

Page 7: ...ng ceilings or attic spaces Install horizontal venting with a 1 4 rise for every 12 of run toward the termination VENTING INSTALLATION INSTRUCTIONS NOTICE Read these instructions completely be fore at...

Page 8: ...of adjacent pipes Push pipe sections together and twist one section clockwise approximately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent must be suppo...

Page 9: ...ff Position the standoff cap assembly in the center of the 10 3 4 square hole and attach to exterior wall with wood screws provided see Figure 11 The siding standoff must sit flush against the exterio...

Page 10: ...chart with critical minimum and maximum dimensions which MUST be met IMPORTANT Rememberthatahorizontalrunofventingmust have a 1 4 rise for every 12 of run toward the termination Figure 13 Typical Hori...

Page 11: ...throughwall over 12 horizontal pipe Basement installation where one foot clearance from ground to termination is possible SNORKEL TERMINATION INSTALLATION Recommended Applications Installations requir...

Page 12: ...max 12 max 7 min 6 max 18 max 8 min 8 max 20 max 20 max 8 max 20 max 45 Elbow Figure 18 Horizontal Termination Configuration for Venting Using Two 90 Elbows with Termination at 90 with Fireplace Figu...

Page 13: ...oom install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all pipe and elbow connections are f...

Page 14: ...wo90 Elbows Vertical Round High Wind Termination Shown VENTING INSTALLATION INSTRUCTIONS Installation for Vertical Termination Cont Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5...

Page 15: ...nting Kits and Components Note Install restrictor into inner collar of fireplace as shown 45 Elbow PARTS LISTS FOR VENTING KITS AND COMPONENTS DESA 5 8 Pipe Vent Kits Number Description P58 6 6 Sectio...

Page 16: ...rmly pushing the two female terminals at the end of the power cord onto the two spade terminals on the blower motor see Figure 25 page 17 2 Attach green ground wire from power cord to blower hous ing...

Page 17: ...ach and make all connections DO NOT trim excessive length away Just enable enough to make all connections securely 3 Place the blower against the lower rear wall of the firebox outer wrapperwiththeexh...

Page 18: ...ne LP Only Propane LP Supply Tank External Regulator Vent Pointing Down FIREPLACE INSTALLATION Continued FIREPLACE INSTALLATION Installing Optional Blower Accessory Cont Installing Gas Piping To Firep...

Page 19: ...pple Tee Joint Sediment Trap Drip Leg Natural From Gas Meter 5 5 W C to 10 5 W C Pressure Propane LP From External Regulator 11 W C to 14 W C Pressure The CSA design certified equipment shutoff valve...

Page 20: ...Figure 34 for propane LPor Figure 35 for natural gas Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak Correct all leaks at once Pressure Testing Fireplace Gas Connecti...

Page 21: ...before removing glass door or louvers Spring Latch Removing Glass Door If replacement of glass is necessary the entire assembly glass and frame must be replaced If glass is broken wear gloves and tape...

Page 22: ...et cool before installing brick liner This brick liner kit is optional You may purchase brick liner from your local retailer or see Accessories page 37 CAUTION Always handle brick panels with two hand...

Page 23: ...erly 8 Place lava rock along sides and front of firebox bottom in ar eas that are visible only It is not necessary to use all of the lava rock provided NOTICE Do not put lava rock on burner or under b...

Page 24: ...eady to use 5 Close lower louver panel Figure 47 Installing the WRC Remote Receiver Fireplace Receptacle Remote Control Receiver Extension Cord Ignition Module Plug Figure 48 Installing Battery into B...

Page 25: ...e appears at pilot If lighting the appliance for the first time each season it may take several attempts before the supply gas can reach the pilot and main burners If the appliance will not stay lit a...

Page 26: ...ve any dust dirt or other obstructions that will hinder the flow of air BURNER FLAME PATTERN Burner flames will be steady not lifting or floating Flame patterns will be different from unit to unit and...

Page 27: ...be used CLEANING AND MAINTENANCE CAUTION Wear gloves and safety glasses while handling or removing broken glass Do not remove if glass is hot Keep children and pets away from glass WARNING Donotopera...

Page 28: ...and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your gas supplier to check pressure 5 Have a qualified technician replace pi lot line 6 Replace control...

Page 29: ...ial OBSERVED PROBLEM Fireplace produces a clicking ticking noise just after burner is lit or shut off Slightsmokeorodorduringinitialoperation Gas odor even when control knob is in OFF position Gas odo...

Page 30: ...ch com 30 ILLUSTRATED PARTS BREAKDOWN Models V42EN A VV42ENSB 1 VV42ENHB 1 V42EP A VV42EPSB 1 VV42EPHB 1 ILLUSTRATED PARTS BREAKDOWN MODELS V42EN A VV42ENSB 1 VV42ENHB 1 V42EP A VV42EPSB 1 VV42EPHB 1...

Page 31: ...6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 02 109082 02 109082 02 Heat Shield 1 10 108778 01 108778 01 108778 01 Log Set 1 10 1 109396 01 109396 01 109396 01 Front...

Page 32: ...ED PARTS BREAKDOWN Models V42EN A VV42ENSB 1 VV42ENHB 1 V42EP A VV42EPSB 1 and VV42EPHB 1 ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY FOR MODELS V42EN A VV42ENSB 1 VV42ENHB 1 V42EP A VV42EPSB 1 AND VV...

Page 33: ...Line 1 15 11107 Screw 10 32 x 1 4 PPH Zinc 4 16 26808 Valve Bracket 1 17 26827 Switch Bracket 1 18 11147 Screw 10 24 x 1 2 PPH Zinc 2 19 11186 Screw 8 32 x 1 Zinc 4 20 14115 Spade Tongue Connector 1...

Page 34: ...ntact your local gas supplier TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact DESA s Customer Service Depart mentat1 866 672 6040 Whencal...

Page 35: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35...

Page 36: ...111907 01D For more information visit www desatech com For more information visit www desatech com 36 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Page 37: ...ss FPD42P Filligree Panel Kit Platinum FPD42PB Filligree Panel Kit Polished Brass LOUVER TRIM KIT Rolled Louvers Only Not Shown LT42B Rolled Louver Trim Kit Brushed Brass LT42P Rolled Louver Trim Kit...

Page 38: ...ansportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE...

Reviews: