BLUE-FLAME VENT-FREE PROPANE/LP AND

NATURAL GAS GREENHOUSE CO2 GENERATOR

TROUBLESHOOTING

Note:

  All troubleshooting items are listed

in order of operation.

 WARNING: Turn off and

unplug appliance and let cool
before servicing. Only a quali-
fied service person should ser-
vice and repair appliance.

 CAUTION: Never use a wire,

needle, or similar object to clean
ODS/pilot. This can damage ODS/
pilot unit.

OBSERVED PROBLEM

When ignitor button is pressed, there is no
spark at ODS/pilot

When ignitor button is pressed, there is
spark at ODS/pilot but no ignition

ODS/pilot lights but flame goes out when
control knob is released

Burner does not light after ODS/pilot is lit

POSSIBLE CAUSE

1.

Ignitor electrode positioned wrong

2.

Ignitor electrode broken

3.

Ignitor electrode not connected to igni-
tor cable

4.

Ignitor cable pinched or wet

5.

Broken ignitor cable

6.

Bad piezo ignitor

1.

Gas supply turned off or manual shutoff
valve closed

2.

Control knob not in PILOT position

3.

Control knob not pressed in while in
PILOT position

4.

Air in gas lines when installed

5.

Depleted gas supply (Propane/LP Only)

6.

ODS/pilot is clogged

7.

Gas regulator setting is not correct

1.

Control knob not fully pressed in

2.

Control knob not pressed in long enough

3.

Manual shutoff valve not fully open

4.

Thermocouple connection loose at con-
trol valve

5.

Pilot flame not touching thermocouple,
which allows thermocouple to cool,
causing pilot flame to go out. This
problem could be caused by one or both
of the following:
A) Low gas pressure
B) Dirty or partially clogged ODS/

pilot

6.

Thermocouple damaged

7.

Control valve damaged

1.

Burner orifice is clogged

2.

Burner orifice diameter is too small

3.

Inlet gas pressure is too low

REMEDY

1.

Replace ignitor

2.

Replace ignitor

3.

Reconnect ignitor cable

4.

Free ignitor cable if pinched by any
metal or tubing. Keep ignitor cable dry

5.

Replace ignitor cable

6.

Replace piezo ignitor

1.

Turn on gas supply or open manual
shutoff valve

2.

Turn control knob to PILOT position

3.

Press in control knob while in PILOT
position

4.

Continue holding down control knob.
Repeat igniting operation until air is
removed

5.

Contact local propane/LP gas company

6.

Clean ODS/pilot (see Cleaning and
Maintenance
, page 11) or replace ODS/
pilot assembly

7.

Replace gas regulator

1.

Press in control knob fully

2.

After ODS/pilot lights, keep control
knob pressed in 30 seconds

3.

Fully open manual shut-off valve

4.

Hand tighten until snug, then tighten 1/4
turn more

5.

A) Contact local gas company

B) Clean ODS/pilot (see Cleaning and
Maintenance
, page 11) or replace ODS/
pilot assembly

6.

Replace thermocouple

7.

Replace control valve

1.

Clean burner (see Cleaning and Main-
tenance
, page 11) or replace burner
orifice

2.

Replace burner orifice

3.

Contact local gas company

Summary of Contents for RN30E-CAN

Page 1: ...reference BLUE FLAME VENT FREE PROPANE AND NATURAL GAS GREENHOUSE CO2 GENERATOR OWNER S OPERATION AND INSTALLATION MANUAL WARNING This is an unvented gas firedappliance Itusesair oxygen from the spac...

Page 2: ...plate This appliance is not convertible for use with other gases 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors 3 If you smell gas shut off gas s...

Page 3: ...ADEQUATE VENTILATION Unconfined Space Can Gas Code B 149 1 and 2 M95 Section 6 3 3 states An appliance installed for the production of carbon dioxide in a green house may take its combustion air from...

Page 4: ...ace 50 cu ft 51 2 or 51 200 maximum Btu Hr the space can support 3 Add the Btu Hr of all fuel burning appliances in the space CO2 generator ______________________ Btu Hr Gas water heater _____________...

Page 5: ...n or Canadian Gas Code B 149 1 and 2 M95 Section 7 2 and 7 3 and or appli cable local codes for required size of venti lation grills or ducts WARNING Rework work sheet adding the space of the adjoinin...

Page 6: ...ction and service where strong wind gusts from an open door or ventilator can not blow directly into appliance 16 3 4 Figure4 MountingClearancesAsViewed From Front of Appliance INSTALLATION NOTICE A q...

Page 7: ...d walls do not pop open wings 5 Place mounting bracket onto wall Line up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten scr...

Page 8: ...Only Never connect appliance directly to the propane LP supply This appliance requires an external regulator notsupplied Installthe external regulator between the applianceandpropane LPsupply Figure 1...

Page 9: ...s joints Bubbles form ing show a leak 5 Correct all leaks at once TestPressuresEqualToorLessThan 1 2 PSIG 1 Close manual shutoff valve see Fig ure 14 2 Pressurize supply piping system by ei therusingc...

Page 10: ...ing Instructions 3 With control knob pressed in strike match Hold match to pilot until pi lot lights 4 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release contro...

Page 11: ...Figure21showsanincorrectburner flame pattern The incorrect burner flame patternshowsyellowtippingoftheflame It also shows the flame higher than 1 2 the heat shield height Ifburnerflamepatternisincorre...

Page 12: ...ly open 4 Thermocoupleconnectionlooseatcon trol valve 5 Pilotflamenottouchingthermocouple which allows thermocouple to cool causing pilot flame to go out This problemcouldbecausedbyoneorboth of the fo...

Page 13: ...ir passageways on appliance blocked 4 Dirtyorpartiallycloggedburnerorifice REMEDY 1 Contact local gas company 2 Clean burner see Cleaning and Main tenance page 11 or replace burner orifice 1 Clean bur...

Page 14: ...essure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at...

Page 15: ...nternational s Technical Service Department at 1 800 323 5190 SPECIFICATIONS RP30E CAN RN30E CAN Btu Variable 15 000 30 000 15 000 30 000 Type Gas Propane LP Only Natural Only Ignition Piezo Piezo Pre...

Page 16: ...UE FLAME VENT FREE PROPANE LP AND NATURAL GAS GREENHOUSE CO2 GENERATOR 1 2 4 5 6 6 7 8 8 9 10 11 12 15 17 19 21 22 23 20 26 25 18 14 16 24 3 13 ODS PILOT 10 1 10 2 ILLUSTRATED PARTS BREAKDOWN RP30E CA...

Page 17: ...01 Thermocouple 1 10 2 098594 01 Ignitor Electrode 1 11 103447 01 Burner 1 12 099387 05 3 16 Pilot Tubing 1 13 103845 03 Injector L P 1 103845 04 Injector N G 1 14 099066 01 Mounting Bracket 1 15 099...

Page 18: ...are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installatio...

Reviews: