background image

111923-01B

For more information, visit www.desatech.com

For more information, visit www.desatech.com

13

13

INSTALLATION FOR VERTICAL TERMINATION

Note:

 Vertical restrictor must be installed in all vertical installations.

1.

Determine the route your vertical venting will take. If ceiling
joists, roof rafters, or other framing will obstruct the venting
system, consider an offset (see Figure 19) to avoid cutting load
bearing members. 

Note:

 Pay special attention to these instal-

lation instructions for required clearances (air space) to com-
bustibles when passing through ceilings, walls, roofs, enclo-
sures, attic rafters, etc. Do not pack air spaces with insulation.
Also note maximum vertical rise of the venting system and
any maximum horizontal offset limitations.

2.

Set the fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the fireplace exit flue. Mark
the center point where the vent will penetrate the ceiling. Drill
a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating
hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.

VENTING INSTALLATION
INSTRUCTIONS

Continued

Flat Ceiling Installation

1.

Cut a 10 

3

/

4

" square hole in the ceiling using the locating hole as

a center point. The opening should be framed to 10 

3

/

4

"x10 

3

/

4

"

(273mm x 273mm) inside dimensions, as shown in Figure 9 on
page 8 using framing lumber the same size as the ceiling joists.
If the area above the ceiling is an insulated ceiling or a room,
nail firestop from the top side. This prevents loose insulation
from falling into the required clearance space. Otherwise, in-
stall firestop below the framed hole. The firestop should be in-
stalled with no less than three nails per side (see Figure 20).

Figure 19 - Offset with Wall Strap and 45

°

 Elbows

Figure 20 - Installing Firestop

If area above is not a room, install
firestop below framed hole.

If area above is a room, install
firestop above framed hole.

2.

Assemble the desired lengths of pipe and elbows necessary to
reach from the fireplace flue up through the firestop. Be sure
all pipe and elbow connections are fully twist-locked (see Fig-
ure 8, page 8).

3.

Cut a hole in the roof using the locating hole as a center point.
(Cover any exposed open vent pipes before cutting hole in roof.)
The 10 

3

/

4

"x10 

3

/

4

" hole must be measured on the horizontal;

actual length may be larger depending on the pitch of the roof.
There must be a 1" clearance from the vent pipe to combustible
materials. Frame the opening as shown in Figure 9, page 8.

4.

Connect a section of pipe and extend up through the hole.

Note:

 If an offset is needed to avoid obstructions, you must

support the vent pipe every 3 feet. Use wall straps for this
purpose (see Figure 19). Whenever possible, use 45

°

 elbows

instead of 90

°

 elbows. The 45

°

 elbow offers less restriction to

the flow of the flue gases and intake air.

5.

Place the flashing over the pipe section(s) extending through
the roof. Secure the base of the flashing to the roof and fram-
ing with roofing nails. Be sure roofing material overlaps the
top edge of the flashing as shown in Figure 19. There must be
a 1" clearance from the vent pipe to combustible materials.

6.

Continue to add pipe sections until the height of the vent cap
meets the minimum building code requirements described in
Figure 7 on page 6.

 Note

: You must increase vent height for

steep roof pitches. Nearby trees, adjoining rooflines, steep
pitched roofs, and other similar factors may cause poor draft
or down-drafting in high winds. Increasing the vent height may
solve this problem.

7.

Twist-lock the vent cap onto the last section of vent pipe.

Note:

 If the vent pipe passes through any occupied areas above the first

floor, including storage spaces and closets, you must enclose pipe. You
may frame and sheetrock the enclosure with standard construction
material. Make sure and meet the minimum allowable clearances to
combustibles. Do not fill any of the required air spaces with insulation.

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

45

°

 Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Summary of Contents for K36N SERIES

Page 1: ...des This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used WARNING If the informati...

Page 2: ...nting system Itbringsinfreshairforcombustionthroughtheouterpipeand combustion gases are exhausted through the inner pipe If the glass door assembly and venting pipe are not properly seated connected a...

Page 3: ...Do not use this fireplace to cook food or burn paper or other objects 13 Do not use any solid fuels wood coal paper cardboard etc in this fireplace Use only the gas type indicated on fireplace namepl...

Page 4: ...ocation for your fireplace and termination cap When deciding the location of your fireplace follow these rules Do not connect this fireplace venting to a chimney flue serving a separate solid fuel bur...

Page 5: ...ight above the fireplace Note Noncombustible mantels may discolor PRE INSTALLATION PREPARATION Continued NOTICE This fireplace is intended for use as supple mental heat Use this fireplace along with y...

Page 6: ...nlet 72 inches 182 9cm minimum L clearance above paved side walk or a paved driveway located on public property 84 inches 213 3cm minimum M clearance under veranda porch deck 12 inches 30 5cm minimum...

Page 7: ...ttic spaces Install horizontal venting with a 1 4 rise for every 12 of run toward the termination VENTING INSTALLATION INSTRUCTIONS NOTICE Read these instructions completely be fore attempting install...

Page 8: ...sh pipe sections together and twist one section clockwise approxi mately one quarter turn until the sections are fully locked see Figure 8 Note Horizontal runs of vent must be sup ported every three f...

Page 9: ...standoff Bolt the vent cap to the stand off Apply non hardening mastic around outside edge of stand off Position the standoff cap assembly in the center of the 10 3 4 square hole and attach to exteri...

Page 10: ...ermination Figure 13 Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed Siding Standoff Screws High Wind Termination Apply Mastic to Outside Edge of Standoff Exterio...

Page 11: ...l rise on building exterior Any installation using snorkel termination to achieve one foot above ground Snorkel terminations are available for installations requiring a vertical rise on the exterior o...

Page 12: ...ce Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H1 Horizontal H2 5 min 2 max 6 max 6 min 4 max 12 max 7 min 6 max 18 max 8 min 8 max 20 max 20 max 8 max 20 max Figure 17 Horizontal T...

Page 13: ...above is a room install firestop above framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop Be sure all pipe and elbow conn...

Page 14: ...Elbow Vertical V Horizontal H 5 min 2 max 6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Figure 22 Vertical Venting Configuration Using One 90 Elbow Vertical Round High Wind Termination Shown Note...

Page 15: ...0 feet Canada When installing this fireplace at an elevation above 2000 feet in the USA you may need to decrease the input rating by changing the existing burner orifice to a smaller size Reduce input...

Page 16: ...retaining the green ground wire is tight Figure 25 Blower Model BK Magnetic Strips Exhaust Port Screw Green Ground Wire Spade Terminals Side View Lower Firebox Cavity Blower Location PARTS LISTS FOR V...

Page 17: ...V A C B l o w e r M o t o r B l a c k B l a c k B l a c k O f f Figure 27 Location of Wiring Diagram Decal Model May Vary From Illustration Wiring Diagram Decal 12 in Front of Blower FIREPLACE INSTAL...

Page 18: ...rnal regulator not supplied Install the external regulator between the fireplace and propane LP supply Figure 30 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank Exter...

Page 19: ...gas con trols If sediment trap drip leg is not installed or is installed wrong fireplace may not run properly Figure 31 Gas Connection CSA Design Certified Equipment Shutoff Valve with 1 8 NPT Tap 3 M...

Page 20: ...ints from propane LP supply tank or gas meter to equipment shutoff valve see Figure 34 for propane LP or Figure 35 for natural gas Apply noncorrosive leak detec tion fluid to all joints Bubbles formin...

Page 21: ...emote control unit 2 Attach terminal wires to a 9 volt alkaline battery not included Place battery into the battery housing 3 Replace battery cover onto remote control unit Figure 39 Installing Alkali...

Page 22: ...tall logs lava rock and ember material 10 Close glass door and lock latches on top and bottom of door and replace screen See Removing Replacing Glass Door steps 5 and 6 11 Close top and bottom louvers...

Page 23: ...these pieces loosely and sparingly directly onto the exposed front section of the burner see Figure 49 This will create the glowing ember appearance as the flame touches the ember material Do not bloc...

Page 24: ...e following 1 Turn gas control knob clockwise to the PILOT position 2 Set selector switch in the OFF position MANUAL LIGHTING PROCEDURE 1 Remove glass door see Removing Replacing Glass Door pages 21 a...

Page 25: ...and Held Remote On or Off and Allows You to Choose the Manual Setting Selects Auto Setting Increases Room Temperature in AUTO Mode Locks System to Prevent Accidental Ignition Digital Display Shows Tem...

Page 26: ...lot will remain lit IMPORTANT To turn the pilot off turn the gas control knob on the heater to the OFF position WARNING Do not connect the thermostat to a power source Electrical shock and or a fire h...

Page 27: ...ndling or removing broken glass Do not remove if glass is hot Keep children and pets away from glass WARNING Donotoperatefireplacewiththeglass door removed cracked or broken CAUTION Do not vacuum if p...

Page 28: ...ogged pilot 5 Thermocouple connection loose at con trol valve 6 Thermocouple damaged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Kee...

Page 29: ...a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance page 27 or replace burner orific...

Page 30: ...PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas odor during combustion Dark residue on logs or inside of fireplace REMEDY 1...

Page 31: ...You may have further questions about installation operation or troubleshooting If so contact DESA s Customer Service Depart mentat1 866 672 6040 Whencalling pleasehaveyourmodeland serial numbers of y...

Page 32: ...information visit www desatech com 32 ILLUSTRATED PARTS BREAKDOWN Models V K36N V K36NH V K36P V K36PH ILLUSTRATED PARTS BREAKDOWN MODELS V K36N V K36NH V K36P V K36PH 6 7 20 17 18 13 2 12 19 8 1 4 11...

Page 33: ...4 108011 01 Top Louver Assembly 1 5 108011 02 Bottom Louver Assembly 1 6 Fireplace Top 1 7 Fireplace Top Insulation 1 8 Fireplace Surround 1 9 109082 01 Heat Shield 1 10 111958 01 Log Set 1 10 1 1119...

Page 34: ...nformation visit www desatech com 34 1 2 3 4 5 12 12 7 15 10 12 13 9 11 TPTH TPTH TP TP TH TH 5 6 12 17 14 8 16 ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY FOR MODELS V K36N V K36NH V K36P V K36PH ILL...

Page 35: ...y Burner 1 2 111311 01 Grate Base 1 3 111313 01 Burner Base Bottom 1 4 26808 Valve Bracket 1 5 11107 Screw 10 32 x 1 4 PPH Zinc 4 6 111310 01 Firebox Bottom 1 7 11102 Screw 8 32 x 3 8 PPH Zinc 2 8 111...

Page 36: ...M KIT Rolled Louvers Only Not Shown LT36B Rolled Louver Trim Kit Brushed Brass LT36P Rolled Louver Trim Kit Platinum LT36PB Rolled Louver Trim Kit Polished Brass DEFLECTION HOODS Not Shown HD36 Hood B...

Page 37: ...Completed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35...

Page 38: ...111923 01B For more information visit www desatech com For more information visit www desatech com 38 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Page 39: ...___________________________________________________________ _______________________________________________________________________________________________ ____________________________________________...

Page 40: ...ansportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE...

Reviews: