background image

www.desatech.com

114924-01B

14

OBSERVED PROBLEM

ODS/pilot lights but flame goes 

out  when  control  knob  is  re-

leased

Burner does not light after ODS/

pilot is lit

Delayed ignition of burner

Burner  backfiring  during  com-

bustion

REMEDY

1. Press in control knob fully

2. After ODS/pilot lights, keep 

control knob pressed in for 30 

seconds

3. Wait one minute for safety in-

terlock system to reset. Repeat 

ignition operation

4. Fully open equipment shutoff 

valve

5. A)  Contact  local  natural  or  

      propane/LP gas company

 

  B)  Clean  ODS/pilot  (see  

           

Cleaning and Maintenance,  

     

page 12) or replace ODS/ 

       pilot assembly

6. Hand tighten until snug, then 

tighten 1/4 turn more

7. Replace pilot assembly

8. Replace control valve

1. Contact  local  natural  or 

propane/LP gas company

2. Clean burner(s) (see 

Cleaning 

and Maintenance

, page 12) or 

replace burner orifice(s)

3. Replace burner orifice(s)

4. Put  remote  selector  in  ON 

position

5. See 

Wiring  Diagram

,  page 

11)

1. Contact  local  natural  or 

propane/LP gas company

2. Clean burner(s) (see 

Cleaning 

and Maintenance

, page 12)

1. Clean  burner  (see 

Cleaning 

and Maintenance

, page 12) or 

replace burner orifice

2. Replace damaged burner

3. Replace gas regulator

POSSIBLE CAUSE

1. Control  knob  not  fully 

pressed in

2. Control knob not pressed in 

long enough

3. Safety interlock system has 

been triggered

4. Equipment shutoff valve not 

fully open

5. Pilot  flame  not  touching 

thermocouple, which allows 

thermocouple  to  cool, 

causing  pilot  flame  to  go 

out. This problem could be 

caused by one or both of the 

following:

  A) Low gas pressure

  B) Dirty or partially clogged 

     ODS/Pilot

6. Thermocouple  connection 

loose at control valve

7. Thermocouple damaged

8. Control valve damaged

1. Inlet gas pressure is too low

2. Burner orifice(s) clogged

3. Burner  orifice(s)  diameter 

too small

4. Remote  selector  in  OFF 

position (Remote use only)

5. Wire disconnected from gas 

control (Remote use only)

1. Manifold  pressure  is  too 

low

2. Burner orifice(s) clogged

1. Burner orifice is clogged or 

damaged

2. Damaged burner

3. Gas regulator defective

TROUBLESHOOTING

Continued

Summary of Contents for Firewerks MVO18VNA

Page 1: ...any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor...

Page 2: ...s ANSI Z233 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation This appliance may be installed in an aftermarket per manently located manufactured mobile home where not prohibited by local codes...

Page 3: ...though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this log set WARNING Do not place log scraps or...

Page 4: ...en in place and fully closed Unless provided by other means screens shall have openings for introduction of combustion air 8 If replace has glass doors never operate with glass doors closed If you ope...

Page 5: ...ot to be used with vented decorative appliances INSTALLATION WARNING A quali ed ser vice person must install heater Follow all local codes WARNING Before installing in a solid fuel burning replace the...

Page 6: ...re place constructed of noncombustible material and connected to a working ue The replace chimney must have a permanent vent opening to outside with minimum openings shown in Figure 3 Figure 2 Technic...

Page 7: ...read inlet connection to the control valve CAUTION Never connect propane LP unit directly to the propane LP supply This unit re quiresanexternalregulator not supplied Install the external regulator be...

Page 8: ...is not installed or is installed wrong heater may not run properly CAUTION Avoid damage to gas control Hold gas control with wrench when connecting it to gas piping and or ttings Figure 7 Gas Connect...

Page 9: ...oints Propane LP Gas Only Figure 10 Checking Gas Joints Natural Gas Only Equipment Shutoff Valve Gas Meter Control Valve Location Pressure Testing Appliance Gas Connections 1 Open equipment shutoff va...

Page 10: ...been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information col umn 1 2 Make sure switch is in OFF position 3 Be sure gas line shut off valve is OPEN 4 Press in and turn control knob clo...

Page 11: ...hand held remote was on when selector switch was last turned off You can now turn the burner on and off with the hand held remote control unit OPERATING APPLIANCE Continued Figure 13 Setting the Sele...

Page 12: ...attern Yellow Flames with Orange Streaks CLEANING AND MAINTENANCE WARNING Turn off the ap pliance and allow to cool before cleaning CAUTION You must keep control areas burners and cir culating air pas...

Page 13: ...in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is in correct When ignitor button is pressed there is no spark at ODS pilot When igni...

Page 14: ...page 11 1 Contact local natural or propane LP gas company 2 Clean burner s see Cleaning and Maintenance page 12 1 Clean burner see Cleaning and Maintenance page 12 or replace burner ori ce 2 Replace d...

Page 15: ...ate burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installation clearances see page 6 4 Clean burners see Cleaning and Mainte...

Page 16: ...nding while heating or contracting while cooling 1 Appliance burning vapors from paint hair spray glues cleaners chemicals new carpet etc See IMPORTANT statement above 2 Low fuel supply propane LP onl...

Page 17: ...lit burners will have delayed ignition propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP or natural gas supplier TECHNICAL SERVICE You may...

Page 18: ...www desatech com 114924 01B 18 ILLUSTRATED PARTS BREAKDOWN MVO24VNA MVO24VPA MVO18VNA MVO18VPA 1 2 3 4 5 6 17 16 15 7 8 9 10 11 12 14 13...

Page 19: ...1 111807 02 111807 01 111807 02 Valve 1 10 112376 01 103778 01 112376 01 103778 01 Pilot Assembly 1 11 111828 01 111818 01 111828 01 111828 01 Brass Fitting 2 12 114930 02 114930 02 114930 01 114930 0...

Page 20: ...The heater MUST be installed by a quali ed installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original conditi...