(1) Turn "OFF11 the circuit breaker o f the load.
c5rcuit bl,eaker ofthe loaci
5-4 Shutdown
(2) Turn "OFF" the circuit breaker ofthe machine.
c i r c u i t b r e a k e r o f t h e m a c h i n e
(3) Set the throttle lever in " START/IDLING" position and
put the machine in cooling operation for about 5 minutes.
(4) Set the starter switch in "STOP" position. The engine will
stop immediately.
(5) Remove the key fiom the starter switch and keep it at
hand.
(6) After engine is shut down, turn the fuel filter cock
sideways to "CLOSE".
(7) Check the amount o f fuel. Supply additional fuel if
necessary.
(8) Check for leakage of oil, foel and water.
SEE
~^h~j|lOFF
starter switch
s
>