47
Modbus
Offset
Register
Description
46038
6037
Positive kVAR L1
Individual Phase Positive Instantaneous Reactive
Powers (kVAR)
46039
6038
Positive kVAR L2
"
46040
6039
Positive kVAR L3
"
46050
6049
Positive Displacement PF L1
Individual Phase Positive Displacement Power Factors
(dPF); Register is 100x actual value (If the Individual
dPF (44050) is positive, this register will contain that
value else it will be zero)
46051
6050
Positive Displacement PF L2
"
46052
6051
Positive Displacement PF L3
"
46053
6052
Positive Apparent PF L1
Individual Phase Positive Apparent Power Factors
(aPF); Register is 100x actual value (If the Individual
aPF(44053) is positive, this register will contain that
value else it will be zero)
46054
6053
Positive Apparent PFL2
"
46055
6054
Positive Apparent PF L3
"
46080
6079
Positive kW System Avg
Equals Positive KWH_SYSTEM_L&M ÷
(TimeSinceReset_L&M seconds /3600 seconds/Hr)
(resettable)
Negative Power Measurement Registers
Modbus
Offset
Register
Detailed Description
47001
7000
Negative kWh System LSW
System Negative True Energy LSW (kWh, resettable)
47002
7001
Negative kWh System MSW
System Negative True Energy MSW (kWh, resettable)
47003
7002
Negative kW System
System Negative Instantaneous Negative True Power
(kW) (net sum of all individual kWs, if sum is positive
value=0)
47006
7005
Negative kW System Max
System Highest Instantaneous Negative Draw Since
Reset (kW, resettable)
47007
7006
Negative kW System Min
System Lowest Instantaneous Negative Draw Since
Reset (kW, resettable)
47008
7007
Negative kVARh System LSW
System Negative Reactive Energy LSW (kVARh,
resettable)
47009
7008
Negative kVARh System MSW
System Negative Reactive Energy MSW (kVARh,
resettable)
47010
7009
Negative kVAR System
System Instantaneous Negative Reactive Power
(kVAR) (net sum of all individual kVARs, if sum is
positive value=0)
47014
7013
Negative Displacement PF
System
System Negative Displacement Power Factor (dPF);
Register is 100x actual value (If the System dPF
(44014) is Negative, this register will contain that
value else it will be zero)
47015
7014
Negative Apparent PF System
System Negative Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is Negative, this register will contain that
value else it will be zero)
Summary of Contents for PowerScout 3
Page 19: ...15 Figure IV 1 Single Phase Two Wire N white L1 black L2 red L3 blue ...
Page 20: ...16 Figure IV 2 Single Phase Three Wire N white L1 black L2 red L3 blue ...
Page 21: ...17 Figure IV 3 Three Phase Three Wire Delta N white L1 black L2 red L3 blue ...
Page 22: ...18 Figure IV 4 Three Phase Four Wire Wye N white L1 black L2 red L3 blue ...
Page 23: ...19 Figure IV 5 Three Phase Four Wire Delta N white L1 black L2 red L3 blue ...