APPENDIX B: VERIS H8035/H8036 EMULATION
The PowerScout
™
meter can be used as a direct replacement for the Veris, Inc. H8035/H8036 Series of
networked power meters. This mirroring of the Veris Modbus register assignments makes replacement with a
PowerScout
™
simple. However, because the number of parameters that the Veris meters measure is less than
half of what the PowerScout
™
can measure, the other Modbus registers described in Table 1 need to be used if
the additional capabilities of the PowerScout
™
are desired.
Table B1: Veris Emulation Modbus Register Assignments*
Modbus Addr.
Offset Description
Units
Comments
40001
System Total True Energy, LSW
kWh
Multiplier Required,
Resetable
40002
System Total True Energy, MSW
kWh
Multiplier Required,
Resetable
40003
System Total True Power
kW
Multiplier Required
40004
System Total Reactive Power
kVAR
Multiplier Required
40005
System Total Apparent Power
kVA
Multiplier Required
40006
System Total Apparent Power Factor
PF
Multiplier Required
40007
Average Line to Line Voltage
Volts
Multiplier Required
40008
Average Line to Neutral Voltage
Volts
Multiplier Required
40009
Sum of Line Currents
Amps, X1
Multiplier Required
40010
L1 Phase True Power
kW
Multiplier Required
40011
L2 Phase True Power
kW
Multiplier Required
40012
L3 Phase True Power
kW
Multiplier Required
40013
L1 Phase Apparent Power Factor
aPF
Multiplier Required
40014
L2 Phase Apparent Power Factor
aPF
Multiplier Required
40015
L3 Phase Apparent Power Factor
aPF
Multiplier Required
40016
L1 – L2 Voltage
Volts
Multiplier Required
40017
L2 – L3 Voltage
Volts
Multiplier Required
40018
L3 – L1 Voltage
Volts
Multiplier Required
40019
L1 – Neutral Voltage
Volts
Multiplier Required
40020
L2 – Neutral Voltage
Volts
Multiplier Required
40021
L3 – Neutral Voltage
Volts
Multiplier Required
40022
L1 Current
Amps
Multiplier Required
40023
L2 Current
Amps
Multiplier Required
40024
L3 Current
Amps
Multiplier Required
40025
System Average Demand
kW
Multiplier Required
Variable Window,
Resetable
40026
System Minimum Inst. Demand
kW
Multiplier Required, 500mS
40027
System Maximum Inst. Demand
kW
Multiplier Required, 500mS
*All values are 16 bit, unsigned integers. The PowerScout
™
does not currently support the Veris floating point registers.
Consult DENT Instruments for availability.