Chapter 4 Parameters
|
VFD-L-I Series
4-2
Revision July 2009, SW V1.1
4.1 Summary of Parameter Settings
: The parameter can be set during operation.
Group 0 User Parameters
Pr.
Explanation
Settings
Factory
Setting
NOTE
00-00 Identity Code of the AC Motor Drive
1: Reserved
#
2:
Reserved
3:
200W
4:
Reserved
5:
Reserved
6:
Reserved
00-01 Rated Current Display of the AC
Motor Drive
200W: 1.6A
##.#
00-02 Parameter Reset
10: All parameters are reset to
factory settings
0
00-03 Start-up Display Selection
0: Display the frequency command
value (LED F)
1: Display the actual output
frequency (LED H)
2: Multifunction display, see Pr.00-
04
3: Display output current (LED A)
0
00-04 Content of Multi-Function Display
0: Display User-Defined Unit (u)
1: Display Counter Value (C)
2: Display Process Operation (1=tt)
3: Display DC-BUS Voltage (U)
4: Display output voltage (E)
0
00-05 User-Defined Coefficient
0.1 to 160
1.0
00-06 Software Version
Read-only
#.#
00-07 Password Input
0 to 999
0
00-08 Password Set
0 to 999
0
Group 1 Basic Parameters
Pr. Explanation
Settings
Factory
Setting
NOTE
01-00
Maximum Operation Frequency
(Fmax)
50.0 to 400 Hz
100.0
01-01 Maximum Voltage Frequency (Fbase) 10.0 to 400.00 Hz
60.0
01-02 Maximum Output Voltage (Vmax)
2.0V to 255.0V
220.0
01-03 Mid-Point Frequency (Fmid)
1.00 to 4000 Hz
1.00
01-04 Mid-Point Voltage (Vmid)
2.0V to 255.0V
12.0
01-05 Minimum Output Frequency (Fmin)
1.00 to 60.00 Hz
1.00
01-06 Minimum Output Voltage (Vmin)
2.0V to 255.0V
12.0
01-07 Output Frequency Upper Limit
1 to 110%
100
01-08 Output Frequency Lower Limit
0 to 100%
0.0
01-09 Accel Time 1
0.10 to 600.00 Sec
1.00