RFI Jumper 

RFI Jumper: The AC motor drive may emit the electrical noise. The RFI jumper is used to suppress 

the interference (Radio Frequency Interference) on the power line. 

Main power isolated from earth:

 

If the AC motor drive is supplied from an isolated power (IT power), the RFI jumper must be cut off. 

Then the RFI capacities (filter capacitors) will be disconnected from ground to prevent circuit damage 

(according to IEC 61800-3) and reduce earth leakage current. 

 

CAUTION!

 

1. 

After applying power to the AC motor drive, do not cut off the RFI jumper. Therefore, 

please make sure that main power has been switched off before cutting the RFI jumper. 

2. 

The gap discharge may occur when the transient voltage is higher than 1,000V. Besides, 

electro-magnetic compatibility of the AC motor drives will be lower after cutting the RFI 

jumper. 

3. 

Do NOT cut the RFI jumper when main power is connected to earth. 

4. 

The RFI jumper cannot be cut when Hi-pot tests are performed. The mains power and 

motor must be separated if high voltage test is performed and the leakage currents are 

too high. 

5. 

To prevent drive damage, the RFI jumper connected to ground shall be cut off if the AC 

motor drive is installed on an ungrounded power system or a high resistance-grounded 

(over 30 ohms) power system or a corner grounded TN system. 

 

1.1.5 Remove Instructions 

Summary of Contents for VFD-E

Page 1: ......

Page 2: ...sing environment 4 Store within an air pressure range of 86 kPA to 106kPA 5 DO NOT place on the ground directly It should be stored properly Moreover if the surrounding environment is humid you should...

Page 3: ...motor drive MODEL V FD007E23A INPUT 3PH 200 240V 50 60Hz 5 1A OU TPUT 3PH 0 240V 4 2A 1 6kVA 0 75kW 1HP FREQUEN CY RANGE 0 1 400Hz Serial Number Bar Code AC Drive Model Input Spec Output Spec Output...

Page 4: ...tion factory Production week T Taoyuan W Wujiang Model 230V 3 phase 1HP 0 75kW If the nameplate information does not correspond to your purchase order or if there are any problems please contact your...

Page 5: ...ad cover Case body Control board cover Output terminals U T1 V T2 W T3 7 5 15HP 5 5 11kW Frame C Input terminals R L1 S L2 T L3 Case body Keypad cover Control board cover Output terminals U T1 V T2 W...

Page 6: ...01 00 to P01 02 for details Switch to ON for free run to stop refer to P02 02 Switch to ON for setting frequency source to ACI P 02 00 2 ACI terminal ACI AVI2 switch Mounting port for extension card N...

Page 7: ...43C VFD015E23C 43C A A1 0 25 2hp 0 2 1 5kW VFD002E11T 21T 23T VFD004E11T 21T 23T 43T VFD007E21T 23T 43T VFD015E23T 43T A A2 0 25 2hp 0 2 1 5kW VFD002E11P 21P 23P VFD004E11P 21P 23P 43P VFD007E21P 23P...

Page 8: ...the RFI jumper Therefore please make sure that main power has been switched off before cutting the RFI jumper 2 The gap discharge may occur when the transient voltage is higher than 1 000V Besides el...

Page 9: ...rectly Remove UVW Terminal Cover For Frame B Frame C and Frame D it only needs to turn the cover light to open the cover For frame A it doesn t have cover and can be wired directly Remove Fan For Fram...

Page 10: ...llowed Atmosphere pressure 86 106 kPa Installation Site Altitude 1000m Operation Vibration 20Hz 9 80 m s2 1G max 20 50Hz 5 88 m s2 0 6G max Temperature 20 C 60 C 4 F 140 F Relative Humidity 90 no cond...

Page 11: ...C motor drive dust collector Air extracting apparatus Control panel CAUTION 1 Operating storing or transporting the AC motor drive outside these conditions may cause damage to the AC motor drive 2 Fai...

Page 12: ...aw dust metal particles etc from adhering to the heatsink 8 When installing multiple AC more drives in the same cabinet they should be adjacent in a row with enough space in between When installing on...

Page 13: ...after connecting in parallel 5 Only the same power system and capacity can be connected in parallel 6 It is recommended to connect 5 AC motor drives in parallel no limit in horsepower but these 5 dri...

Page 14: ...0 5 98 50 0 1 97 4 5 0 18 5 2 0 20 5 2 0 20 A A2 72 0 2 83 56 0 2 20 155 0 6 10 143 0 5 63 111 5 4 39 9 5 0 37 5 3 0 21 NOTE Frame A A1 VFD002E11A 21A 23A VFD004E11A 21A 23A 43A VFD007E21A 23A 43A VF...

Page 15: ...S2 H1 W W1 D1 D2 S1 Unit mm inch Frame W W1 H H1 D D1 D2 S1 S2 B1 100 0 3 94 89 0 3 50 174 0 6 86 162 0 6 38 152 0 5 98 50 0 1 97 4 0 0 16 5 5 0 22 5 5 0 22 NOTE Frame B B1 VFD007E11A VFD015E21A VFD02...

Page 16: ...ame C H H1 W1 W S1 S2 D D1 D2 Unit mm inch Frame W W1 H H1 D D1 D2 S1 S2 C1 130 0 5 12 116 0 4 57 260 0 10 24 246 5 9 70 169 2 6 66 78 5 3 09 8 0 0 31 6 5 0 26 5 5 0 22 NOTE Frame C C1 VFD055E23A 43A...

Reviews: