Pr.
Explanation
Settings
Factory
Setting
NOTE
05-16
PLC Forward/ Reverse
Motion
00 to 32767 (00: FWD, 01: REV)
00
05-17
Time Duration of 1st
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-18
Time Duration of 2nd
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-19
Time Duration of 3rd
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-20
Time Duration of 4th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-21
Time Duration of 5th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-22
Time Duration of 6th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-23
Time Duration of 7th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-24
Time Duration of 8th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-25
Time Duration of 9th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-26
Time Duration of 10th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-27
Time Duration of 11th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-28
Time Duration of 12th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-29
Time Duration of 13th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-30
Time Duration of 14th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
05-31
Time Duration of 15th
Step Speed
00 to 65500 sec or 00 to 6550.0 sec
00
00: 1 sec
05-32 Time
Unit
Settings
01: 0.1 sec
00
05-33
The Amplitude of
Wobble Vibration
0.00~400.00 Hz
0.00
05-34
Wobble Skip Frequency 0.00~400.00 Hz
0.00
Group 6 Protection Parameters
390.0V
780.0V
975.0V
06-00
Over-Voltage Stall
Prevention
230V series: 330.0V to 410.0V
460V series: 660.0V to 820.0V
575V series: 825.0V to1025.0V
00: Disable over-voltage stall prevention
06-01
Over-Current Stall
Prevention during Accel
20 to 250%
170
06-02
Over-Current Stall
Prevention during
Operation
20 to 250%
170