Layout Considerations

For any Delta

’s indoor air quality monitors, we recommend an area coverage of 

160 m

2

with the area of enclosed space calculated individually. 

For example:

One open space of 

160 m

2

requires one monitor.

Three conference rooms of 

80 m

2

each requires three monitors, one in each room.

Space over 160 m

2

should consider installing multiple monitors throughout the room to 

achieve optimal coverage. It is also recommended to align the sensor deployment area 
with the HVAC thermal zoning plan. 

Located at least ~5 meters (16 feet) away from operable windows, doors and diffusers.

Installation steps

1. Use the wall mount included in the box to install it on the wall, or install in a power 

box. The wall mount has screw hole spacing (60mm and 84mm) 

2. suitable for power boxes in multiple countries, but the power box must be installed 

horizontally as shown in Fig.1. 

3. Verify that the power supply and data lines are laid out according to specifications 
before installation.

4. As shown in Fig.2, installation the wall mount and verify that all four buckles are 
installed and fixed. 

5. As shown in Fig.3, use a hexagonal screw driver to fasten the M4 hex socket screws to 
complete the installation.

Note

Power source notice

This product uses a 

9-24V DC power supply

. AC power must be 

converted to the required power source or use the specified power 
adapter . 