Wiring diagram 

– RS485

Connect A1 and B1 with the 

equipment’s A and B, the recommended wire to use is 

22AWG Shielded Foil Twisted-Pair (SFTP)

Power on verification

After the product has been installed, the power indicator lights up after the power is 

connected, and the air quality indicator turns blue, which means the device is 
turning on at this time. If green or yellow appears, it means that the device has 
completed booting and the current air quality status is displayed. If the power
indicator does not light up, please verify that the power cord is properly connected 
and that there is a supply of power.

Do not inject contaminants

Do not directly inject contaminants containing gases or particulate matter. 
Exposure to excessive contaminants can permanently damage the sensor.

Do not repair this product yourself

The product does not have components that users can repair themselves. Do not 
attempt to open it. Once the warranty sticker breaks, the warranty is void.

Note

Do not insert objects through the vents, which may be

dangerous and damaging.

Prohibit live line operation

When the installer configures DIP switches and terminal connector, be sure to 
power off before execution and then power on after.

In RS485 control mode, if the equipment is successfully connected, the 

equipment status indicator is static on/off or it will keep blinking.

The installer can verify ventilation volume by switching to manual mode with fixed

fan speed.

After a period, the health of the filter will return to zero. At this time, it is recommended 

to replace the filter. After the replacement, you can press and hold the factory reset 
button on the back of the product to reset.

DIP switches

1

2

3

4

5

6      7

8

Enable smart control function

Turn all the DIP switches up, press the multi-func. button then power on, release the 

button after the filter health LED blinks, and confirm that the screen has changed 
successfully after restarting, and then restore the DIP switches as previously stated.

Wiring diagram - DO(digital output)

Note

To connect multiple equipment, you must set different Modbus slave address. 
Please reference the user manual of 

that equipment

to config slave address.

Connect multiple equipment

The product can connect to the 4 same equipment via RS485 in series through 

daisy chain - linear topology. At this time, each device will follow the same 
control mode and fan speed level.

Wiring diagram

Fan speed levels

Control interface

12V GND B A

6

7

Unlimited

1 level

6

7

3 levels

6

7

2 levels

6

7

8

RS485

Delta ERV

“VEB250AT3”

Dip switches

11

10

12 13

B1

A1

Vin

14

Vout

6

5

7

8

9

2

1

3

4

B2

A2

NO2 NO1

NO3

NO4

AI2

AI1

GND

Low fan speed

Medium fan speed 

High fan speed

NO4

COM

12VDC
AC250V

+

-

ON/OFF

NO1

COM

APP and website links

The product is equipped with wireless technology and can use an APP and website 
to monitor the air quality status, which can be obtained using the following QR 
codes. (For the wireless model only). Please go to the official website to learn about 
how to use the product.

iOS APP

Android APP

UNOweb

Doc. & Resources

1 level output (ON/OFF)

3 level output (FAN speed)

12VDC
AC250V

or/and

Note

DIP switches pin8 should be turned ON

External relay requirement : AC250V resistive, and 12VDC SPDT, 15A

Factory reset

Click this button 3 times within 2 seconds will trigger factory reset. The values

below will be restored to default. “MQTT broker setting”, “Sensor calibration settings 
(Temperature/HCHO)”, “Software Setting”, not include “Modbus baud rate setting” 

Note

Not following instructions may result in damage to the product or other items.

Using right connectors and ports

Do not force the connector into the port. Check the port for foreign objects. If the 

connectors and ports do not fit easily, it may be because they do not match each other. 
Make sure that the connector matches the port, and that the connector is aligned to 
the correct location corresponding to the port.

Insert the wrong pin may result in damage to the product, it will not be responsible for 

the product warranty.

+

12VDC
AC250V

+

12VDC
AC250V

NO3

NO2

COM

COM

-

-

5

6

4

(depend on equipment)

Note

The product supports control of energy recovery ventilation and 

inline fan. Regarding the compatibility of equipment brands and models, please 
contact your dealer and local sales for technical evaluation before purchasing. No 
matter RS485 or digital output, control logic is fixed for smart ventilation control, 

PLEASE DON’T TO USE FOR OTHER APPLICATIONS

Pin

Name

Definition

1

GND

Ground

2

AI1

Analog input-1 External 
temperature sensor

3

AI2

Analog input 2

4

NO4

Digital output - HF

5

NO3

Digital output - MF

6

NO2

Digital output - LF

7

NO1

Digital output 

– ON/OFF

8

B2

Modbus slave B

9

A2

Modbus slave A

10

B1

Modbus master B

11

A1

Modbus master A

12

GND

Ground

13

Vin

9-24V DC input

14

Vout

9-24V DC output

Number

Switch Definition

ON

OFF*

1

Modbus  terminal resistor

2

Modbus  slave position [3]

3

Modbus  slave position [2]

4

Modbus  slave position [1]

5

Modbus  slave position [0]

6

Maximum  fan speed [1]

7

Maximum  fan speed [0]

8

Control mode selection

* The above are the default states of the DIP
switches

Terminal block pin function definition

DIP switch function definition

Hardware Interface 

Step for Equipment Control 

Cleaning the exterior of UNOnext

To clean the product, unplug the power cord and all wiring.

Wipe with a soft, cotton-free cloth. Avoid moisture at any openings on the device 
body. Please do not spray liquids directly onto it.

Specification

Sensor specification

Operating range

0

o

C to 50

o

C, 10-90 %RH, IP20

Storage temp.

-20

o

C to 70

o

C

Power requirements

Input 1 : 9-24VDC +/-10% or
Input 2 : Power adapter 12V/1A

Power consumption

Max 500mA@12VDC

Ventilation control

RS485 or DO(low active)

Dimensions

14.2 cm(L) x 6.8 cm(W) x 4.2 cm(D)

Weight

208 g

Display

1.3'' OLED

Accessories

Wall mount

Language

Chinese, English

Connectivity

RS485, Wi-Fi 2.4G, 802.11 b/g/n, BLE 5.1

Items

Measurement Range

Accuracy

Temperature

0 - 50 

o

C

± 1

o

C

Humidity

0 - 100 %RH

± 5%

CO

2

400 - 10000 ppm

±30 ppm ±

 3%

PM2.5

0 - 1000 ug/m

3

± (5 µg/m³ + 20%) 

 0-100 µg/m³

± 10% at 100-1000 µg/m3

PM10

0 - 1000 ug/m

3

± (5 µg/m³ + 20%) 

 0-100 µg/m³

± 25% at 100-1000 µg/m3

Luminance

0 - 10000 lux

For background ambient light reference

HCHO

0 - 5000 ppb

± 15% 

CO

0 - 500 ppm

± 20 ppm or ± 5% 

O

3

0.5 - 10 ppm

0.01 ppm

TVOC

0 - 30000 ppb

± 15% in lab test (Ethanol)