Infrasuite Power Management

7.5 Upgrade

 

z

Upgrade via Web 

You can upgrade the SNMP IPv6’s firmware or the rSTS’s firmware through 

the  

InsightPower SNMP IPv6 for rSTS Web

 (please see the following figure). The 

SNMP IPv6 will restart after finishing self-upgrade. If you upload the rSTS’s 
firmware to the Web, you can see the rSTS’s firmware upgrade progress from 

the Web.

 

z

Upgrade via FTP/ SFTP

You can also upgrade the SNMP IPv6’s firmware or the rSTS’s firmware by 

using FTP or SFTP program. Make sure you upload correct images to 

upgrade_

snmp

 when upgrading SNMP IPv6’s firmware, and upload correct images to 

upgrade_device

 when upgrading the rSTS’s firmware.

Summary of Contents for STS 16A

Page 1: ...frasuite Power Management User Manual The power behind competitiveness Rack Static Transfer Switch TEST O P S1 S1 ON S2 S2 ON RESET NETWO RK TEST O P S1 S1 ON S2 S2 ON NETWO RK RESET LOCAL TEST O P S1...

Page 2: ...f this product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission...

Page 3: ...res 4 2 4 Model Type 5 Chapter 3 Installation 7 3 1 Installation_ Model STS30002SR00035 7 3 2 Installation_ Model STS30002SR10035 8 3 3 Installation_ Model STS30002SR10135 9 Chapter 4 Wiring 10 4 1 Wi...

Page 4: ...Pv6 Features 18 7 3 Top View and Front View of SNMP IPv6 19 7 4 Console Management 20 7 5 Upgrade 24 7 6 rSTS Command Settings 26 7 7 Key Generation for SSH 30 Chapter 8 Troubleshooting 32 Appendix 1...

Page 5: ...bjects from getting inside the unit 7 Do not operate the unit close to gas or fire z Upstream circuit breaker must be added for each input The recommended break er is D curve 30A for STS30002SR00035 a...

Page 6: ...2 Class A and FCC Class A z EMS IEC 61000 4 2 IEC 61000 4 6 IEC 61000 4 3 IEC 61000 4 8 IEC 61000 4 4 IEC 61000 4 11 IEC 61000 4 5 z IPv6 Certification IPv6 Ready Logo Phase 2 Core for Host Logo ID 02...

Page 7: ...r can know the power flow and rSTS s status from the front panel s LED indica tors and monitor the rSTS via the built in InsightPower SNMP IPv6 The unit has a network interface for users to read and w...

Page 8: ...hom you purchased the unit 2 If the rSTS needs to be returned carefully repack the rSTS and all of the accessories using the original packing material that came with the unit 2 3 Features z Flexible i...

Page 9: ...s Model No Input Output Type Length Type Length STS30002SR00035 L6 30P 3600 mm 141 73 L6 30R 450 mm 17 72 STS30002SR10035 IEC309 32A 4000 mm 157 48 IEC309 32A 1000 mm 39 37 STS30002SR10135 HP T4049S 3...

Page 10: ...6 Infrasuite Power Management z Model STS30002SR10035 TEST O P S1 S1 O N S2 S2 O N NETW ORK RESE T LOCA L z Model STS30002SR10135 TEST O P S1 S1 O N S2 S2 O N NETW ORK RESE T LOCA L...

Page 11: ..._ Model STS30002SR00035 z Front installation TEST O P S1 S1 ON S2 S2 ON NETWORK RESET LOCAL z Rear installation TEST O P S1 S1 ON S2 S2 ON NETWORK RESET LOCAL NOTE After installation the surplus four...

Page 12: ...TS30002SR10035 z Front installation TEST O P S1 S1 ON S2 S2 ON NETWORK RESET LOCAL z Rear installation TEST O P S1 S1 ON S2 S2 ON NETWORK RESET LOCAL NOTE After installation the surplus four bracket s...

Page 13: ...0002SR10135 z Front installation TEST O P S1 S1 ON S2 S2 ON NETWOR K RESET LOCAL z Rear installation TEST O P S1 S1 ON S2 S2 ON NETWORK RESET LOCAL NOTE After installation the surplus four bracket scr...

Page 14: ...3 Connect the Ethernet cable not provided to the front panel s NETWORK port To Source 1 T o S o u r c e 2 T o L o a d TEST O P S1 S1 O N S2 S2 O N RES ET NET WOR K LOC AL 4 2 Wiring_ Model STS30002SR...

Page 15: ...rce 1 T o S o u r c e 2 T o L o a d TEST O P S1 S1 O N S2 S2 O N NETW ORK RES ET LOC AL 4 3 Wiring_ Model STS30002SR10135 1 Remove the two screws shown in the figure below TE ST O P S1 S1 ON S2 S2 ON...

Page 16: ...ect the wiring terminals and the source 1 S1 source 2 S2 and your load For wiring please refer the figure below Please note that source 1 S1 is the preferred source Wiring Terminal Location L N G Wire...

Page 17: ...ght up as green If the input source 2 is out of the acceptable range the LED will be off 3 S1_ON LED Green If the rSTS uses input source 1 to supply power to the output the LED will light up as green...

Page 18: ...ronmental Fault Error Code Meaning E01 Output overload E02 Over temperature due to detection of ambient temperature E03 Over temperature warning due to detection of S1 heat sink temperature E04 Over t...

Page 19: ...rk communication status rSTS LED amber indicates the rSTS s communication status NETWORK NET LED rSTS LED LED Condition Meaning ALL Blinking Rapidly Firmware is upgrading NET LED OFF Ethernet is unlin...

Page 20: ...he built in SNMP IPv6 provides the rSTS s status information and parameters through a network system OFF ON Pass Through Mode The built in SNMP IPv6 stops polling the rSTS but transfers the communicat...

Page 21: ...sitive equipment L N G 2 poles circuit breaker rSTS L N G S1 S2 L1 N1 G L2 N2 G After power connection the rSTS will automatically perform power on self test After the test the rSTS will start supplyi...

Page 22: ...on about the SNMP IPv6 s user manual please visit the website below https datacenter softwarecenter deltaww com Download DataCenter Manual SNMP_IPv6_for_rSTS EN pdf 7 2 SNMP IPv6 Features z Network rS...

Page 23: ...Remote event log management through syslog IPv6 Ready Logo certified ID 02 C 000624 DEFAULT SETTING User Name admin Password password DHCP Client Enable IPv4 Address 192 168 1 100 7 3 Top View and Fro...

Page 24: ...1f MAC Address 00 30 ab 26 b1 b4 1 User Manager 2 TCP IP Setting 3 Network Parameter 4 Time Server 5 Soft Restart 6 Reset All To Default d Device Communication z Exit Without Save 0 Save And Exit Plea...

Page 25: ...tion e Auto Negotiation Enable f Speed 100M g Duplex Full h Status Stable 3 i Telnet Idle Time 60 Seconds 0 Back To Previous Menu Please Enter Your Choice TCP IP Setting z Network Parameter 1 HTTP Ser...

Page 26: ...Back To Previous Menu Please Enter Your Choice Time Server z Soft Restart Web Card Version 01 12 11f MAC Address 00 30 ab 26 b1 b4 1 User Manager 2 TCP IP Setting 3 Network Parameter 4 Time Server 5...

Page 27: ...bs2p 180 0 STS Tdp2s 12 0 STS Tds2p 12 0 STS TempF 96 STS TempC 36 STS Age 1075878 STS Time 13 3 24 07 18 2011 STS XCount 4402 STS Prefer S1 STS DevID 12345678901234567890 STS Serial STS Tprevl 13 35...

Page 28: ...art after finishing self upgrade If you upload the rSTS s firmware to the Web you can see the rSTS s firmware upgrade progress from the Web z Upgrade via FTP SFTP You can also upgrade the SNMP IPv6 s...

Page 29: ...ade via EzSetting You can also upgrade the SNMP IPv6 s firmware or the rSTS s firmware by using EzSetting 1 Click Discover A list of SNMP devices is shown Select a device from the Device List and clic...

Page 30: ...rSTS Fahrenheit temperature N A TempC Report internal rSTS Celsius temperature N A Age Report internal rSTS age N A days hh mm ss Time Report present time N A hh mm ss MM DD YYYY XCount Report number...

Page 31: ...arameters Vout Report the output voltage N A Iout Report the output current N A Vs1 Report the primary voltage N A Vs2 Report the secondary voltage N A Fs1 Report the primary frequency N A Fs2 Report...

Page 32: ...g Report the event code and time of prior transfers Index to show 1 20 STS Log 10 STS Log 1 15 33 59 03 20 2016 0x29 STS Log 3 5 Index Time Date Event 3 13 07 42 07 12 2011 0x29 4 13 07 54 07 12 2011...

Page 33: ...ssage SetVbp2s Set the primary to secondary brownout voltage 180 0 264 0 Message SetVbs2p Set the secondary to primary brownout voltage 180 0 264 0 Message SetTdp2s Set the recovery time of transfer f...

Page 34: ...ex to show 1 20 STS UpDate 3 STS UpDate 1 13 43 15 04 10 2013 STS UpDate 1 20 Index Time Date 1 13 43 15 04 10 2013 2 13 28 26 04 10 2013 3 13 27 37 04 10 2013 AgentVer Report SNMP IPv6 version N A AA...

Page 35: ...ey Generate key pair to generate an RSA key 4 Select Conversions Export OpenSSH Key and assign a file name to the RSA key Please ignore it when prompted to provide key passphrase 5 Select SSH 2 DSA fr...

Page 36: ...rs S1 or S2 LED is off The corresponding power source is absent or out of range 1 Check the corresponding power source 2 Reset the corresponding upstream circuit breaker Fault LED flashes Output overl...

Page 37: ...mm 1 69 17 32 15 35 Weight STS30002SR00035 7 7 kg 16 98 lb STS30002SR10035 7 6 kg 16 76 lb STS30002SR10135 6 2 kg 13 67 lb Environment Operating temperature 0 40 C 32 104 F Storage temperature 15 50...

Page 38: ...esistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for any damage out of the...

Page 39: ...3168 Australia T 61 3 9543 3720 E ups australia deltaww com Delta Electronics Korea Inc 1511 Byucksan Digital Valley 6 cha Gasan dong Geumcheon gu Seoul Korea 153 704 T 82 2 515 5303 E ups south kore...

Page 40: ...5013212303...