13. Technical data
Installation and Operation Manual for RPI M50A
106
Mechanical Design
RPI M50A_120
RPI M50A_122
Dimensions (W x H x D)
612 x 740 x 278 mm
Weight
74 kg
Cooling
5 Fans
AC Connector type
China Aviation Optical-Electrical Technology Co.
PVE5T125KE36
DC Connector type
Multi-Contact MC4
Communication interfaces
2 x RS485, 2 x Dry contacts, 1 x EPO, 6 x Digital inputs
General Specification
RPI M50A_120
RPI M50A_122
Delta model name
RPI M50A_120
RPI M50A_122
Delta part number
RPI503FA0E0000
RPI503FA0E0200
Maximum efficiency
98.6%
EU efficiency
98.4%
Operating temperature range
-25 ... +60 °C
Operating temperature range without derating
-25 ... +40 °C
Storage temperature range
-25 ... +60 °C
Relative humidity
0 ... 100%, non-condensing
Maximum operating altitude
2000 m above sea level
Standards and Directives
RPI M50A_120
RPI M50A_122
Protection degree
IP65
Safety class
I
Pollution degree
II
Overload behavior
Current limitation; power limitation
Safety
IEC 62109-1 / -2, CE compliance
EMC
EN 61000-6-2, EN 61000-6-3
Immunity
IEC 61000-4-2 / -3 / -4 / -5 / -6 / -8
Harmonics
EN 61000-3-2
Variations and flicker
EN 61000-3-3
Grid interfaces
You can find the up-to-date list on www.solar-inverter.
com.
1)
When operated with asymmetrical load (67/33 %)
2)
Maximum 34.8 kW per DC input with asymmetrical load (67/33 %)
3)
For some firmware versions limited to 1000 V
4)
IEC 60664-1, IEC 62109-1
5)
The value when the internal temperature of the inverter is 25 °C. At higher internal temperature the value may drop to 10 A.
6)
For cos phi = 1 (VA = W)
7)
55 kVA is possible with: DC input voltage is 600 V; symmetrical load; ambient temperature < 34 °C.
8)
AC voltage and frequency range will be programmed according to the individual country requirements.