FAULT
Message
Possible cause
Action
DC
Injection
(F01, F02,
F03)
1. Utility waveform is
abnormal
2. Detection circuit
malfunction
1. Check the utility waveform.
Grid connection of inverter need to be
far away from non-linear load if necessary
2. Check the detection circuit inside the
inverter
Temperature
(F05)
1. The ambient is over 60
℃
(The installation is abnormal)
2. Detection circuit malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
Temperature
(F07)
1. Ambient temperature is
<-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC1
Fail
(F06)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC2
Fail
(F08)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC3
Fail
(F09)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
HW NTC4
Fail
(F10)
1. Ambient temperature
>90
℃
or <-30
℃
2. Detection circuit
malfunction
1. Check the installation ambient and
environment
2. Check the detection circuit inside the
inverter
DC RLY
Fail
(F13)
1. Driver circuit for relay is
defective
2. Relay(s) is defective
3. Detection circuit malfunction
(Inverter voltage)
1. Check the input voltage, must >150Vdc
2. Replace the defective relay
3. Check the detection circuit inside the
inverter
HW DSP
ADC1
(F15)
1. Insufficient input power
2. Auxiliary power circuitry
malfunction
3. Detection circuit
malfunction
1. Check the input voltage, must >150Vdc
2. Check the auxiliary circuitry inside the
inverter
3. Check the detection circuit inside the
inverter
63
Error message and Trouble Shooting
Summary of Contents for RPI M30A
Page 2: ......
Page 57: ...Figure 6 3 Pull out the SPD unit Figure 6 2 Recognize the damaged SPD unit 57 Maintenance...
Page 77: ...RPI M30A M50A The power behind competitiveness www deltaww com English 1 77 153...
Page 79: ...79...
Page 81: ...2 1 RPI M30A M50A 2 1 2 2 1 2 2 RPI M30A 2 2 2 1 RPI M50A 2 3 2 2 81...
Page 87: ...3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 87...
Page 89: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 89...
Page 90: ...3 5 25 60 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 90...
Page 93: ...bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 RPI M50A 4 2 93...
Page 100: ...4 10 32A 4 10 M30A 32A 32A 100...
Page 101: ...4 11 30A 4 11 30A Note 30A M30A 101...
Page 103: ...2 2 103...
Page 104: ...String Fuse 15A String Fuse Y String Fuse 25A 6 2 String Fuse Max 25A 4 String Fuse 104...
Page 107: ...AC AC AC plug 55mm L1 L2 L3 N 52 5mm RPI M30A 12mm 0 5 inch RPI M50A 18mm 0 7 inch 4 12 AC 107...
Page 114: ...4 5 3 RPI M30A M50A 2 5 2 7 5 Dry Contact 4 19 Dry Contact 1 Dry Contact 2 114...
Page 131: ...SPD Fail 1 AC DC 2 6 1 3 DC SPD AC SPD 6 2 4 6 3 5 6 1 RPI M50A 131...
Page 132: ...6 3 SPD 6 2 SPD 132...
Page 134: ...6 5 6 6 6 3 6 6 134...
Page 135: ...6 7 6 8 6 4 6 5 6 8 4 135...
Page 142: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 142...
Page 148: ...148 9 3 M30A cos 0 9...
Page 152: ......
Page 153: ...RPI M30A M50A The power behind competitiveness www deltaww com English 1 77 153...
Page 155: ...155...
Page 157: ...RPI M30A M50A 2 1 2 2 1 2 1 2 2 RPI M30A 2 2 2 1 RPI M50A 2 3 2 2 157...
Page 163: ...3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 163...
Page 165: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 165...
Page 166: ...3 5 25 60 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 166...
Page 169: ...bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 RPI M50A 4 2 169...
Page 176: ...4 10 32A 4 10 M30A 32A 32A 176...
Page 177: ...4 11 30A 4 11 30A Note 30A M30A 177...
Page 179: ...2 2 179...
Page 180: ...String Fuse 15A String Fuse Y String Fuse 25A 6 2 String Fuse Max 25A 4 String Fuse 180...
Page 183: ...AC AC AC plug 55mm L1 L2 L3 N 52 5mm RPI M30A 12mm 0 5 inch RPI M50A 18mm 0 7 inch 4 12 AC 183...
Page 190: ...4 5 3 RPI M30A M50A 2 5 2 7 5 Dry Contact 4 19 Dry Contact 1 Dry Contact 2 190...
Page 207: ...SPD Fail 1 AC DC 2 6 1 3 DC SPD AC SPD 6 2 4 6 3 5 6 1 RPI M50A 207...
Page 208: ...6 3 SPD 6 2 SPD 208...
Page 210: ...6 5 6 6 6 3 6 6 210...
Page 211: ...6 7 6 8 6 4 6 5 6 8 4 211...
Page 218: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 218...
Page 222: ...222 9 1 M30A cos 1 0...
Page 224: ...224 9 3 M30A cos 0 9...
Page 228: ...Version 1 03 2015 May...