background image

Connection with PV Combiner Box

M50A:

Note for Field Wiring

Due to the limitation of physical wire also the DC connector used in the

inverter, the absolute maximum current of each DC connector should be

always observed as following table to keep fire risk away. 

Note that, the following value is provided to identified and checked the

justification for field wiring instead of the DC current rating of inverter.

-Normally, the output current of combiner box is larger than 16A.

Thus it can’t be used as the following diagram (Shown as 

Figure 4-7

).

M50A is not suitable to connected with PV combiner box.

RPI M30A_121

32A

RPI M50A_120

16A

RPI M50A_122

16A

Table 4-1 Maximun current rating of each DC connector

Figure 4-7

>16A

>16A

>16A

>16A

23

Wiring

Summary of Contents for RPI M30A

Page 1: ...RPI M30A M50A Operation and Installation Manual Grid tie Transfomerless Solar Inverter The power behind competitiveness www deltaww com English 1 77 153...

Page 2: ......

Page 3: ...2 1 Home Page 5 2 2 Power Meter 5 2 3 Energy Log 5 2 4 Event Log 5 2 5 Inverter Information 5 2 6 General Settings 5 2 7 Install Settings 5 2 7 1 Inverter ID 5 2 7 2 Insulation 5 2 7 3 Country 5 2 7...

Page 4: ...hould ONLY be carried out by the manufacturer No user serviceable parts inside In Australia installation and maintenance work shall be conducted by qualified electrician and shall comply with Australi...

Page 5: ...t support off grid functionality The operation of solar inverter is shown as the Figure 1 1 Inverters convert the DC input power supplied from the PV Array into 3 phase AC output power to Grid Figure...

Page 6: ...on the packaging Check if all the accessories are in the package The standard accessories are shown in following tables and figures For RPI M30A Please refer to Figure 2 2 and Table 2 1 For RPI M50A P...

Page 7: ...formation of safety Installation specification etc 3 AC Plug Mounting Bracket Connector for AC connection Wall mounting bracket to mount the solar inverter on the wall 4 5 DC Plug 6 sets Connector for...

Page 8: ...2 User Manual The Instruction to provide the information of safety Installation specification etc 3 AC Plug Mounting Bracket Connector for AC connection Wall mounting bracket to mount the solar inver...

Page 9: ...30A and M50A series have 3 models The differences between them are having surge protection devices SPD and internal strings fuse or not For more detail information please see the table 2 3 Figure 2 4...

Page 10: ...t Output Interfaces Input Output Interfaces The Inverter s exterior objects are shown in Figure 2 5 The detailed input output interfaces illustration is shown in Figure 2 6 Different models have diffe...

Page 11: ...tion RS 485 2 EPO 1 Dry Contact 2 Digital Input 6 DC1 DC2 String8 String9 String10 String4 String5 String6 String7 RPI M50A DC1 DC2 String1 String2 String3 String4 String5 String6 AC Connector 380 400...

Page 12: ...e ensure the installation is perpendicular to the floor and the AC plug at the bottom Do not install the device on a slanting wall To mount the inverter on the wall please follow the procedure below 1...

Page 13: ...Figure 3 1 Mounting bracket dimension Figure 3 2 Recommended installation 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 13 Installation...

Page 14: ...M6 Screw 6 Wall M6 Screw 6 Figure 3 3 Screw the mounting bracket Figure 3 4 Attach to the bracket and fasten with screws 14 Installation...

Page 15: ...ess in turn ensuring easy access for service and maintenance Please leave an appropriate gap in between units when installing several solar inverter systems as shown in Figure 3 5 Please install solar...

Page 16: ...e detail wiring illustrations If you want inverter working at parallel input mode only 1 MPPT please install 2 bus bar kits in the inverter as shown in Figure 4 2 The outer wiring at DC side is same a...

Page 17: ...PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M30A can support 3P3W system 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV...

Page 18: ...bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 RPI M50A Figure 4 2 Force M50A operate in parallel mode 18 Wiring...

Page 19: ...iring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 1A Grounding fuse bus bar kit Figure 4 3 Mi...

Page 20: ...ring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac 1A Grounding fuse bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 Figure 4 4 P...

Page 21: ...ts must be parallel connection due to the RPI series not having galvanic isolation between the DC input and AC output When solar array is grounded the PID function can not be enable and the insulation...

Page 22: ...C Wiring Must be Parallel Connection Do not enable the PID function and set the insulation with Plus Grounded or Minus Grounded DC Distribution box Plus GND or Minus GND Z Z or Isolated transformer Ut...

Page 23: ...t the following value is provided to identified and checked the justification for field wiring instead of the DC current rating of inverter Normally the output current of combiner box is larger than 1...

Page 24: ...o each dc connector of inverter Shown as Figure 4 8 Because the current might not be symmetric among the branch the current of one branch might larger than the limitation still Figure 4 8 16A 16A 16A...

Page 25: ...wn risky connection with M30A and PV combiner box As Figure 4 10 shown the left pair of dc connector will suffer DC input current more than the limitation 32A Thus it is not suitable for use Figure 4...

Page 26: ...the branch plug might suffer the DC current lager than its limitation Thus it is not suitable for use Note that the max current rating of MC4 brauch commercially available is 30A Figure 4 11 30A Note...

Page 27: ...nt cover The Specific DC input connectors The inverter equips with 10 pair DC connector When 12 string applied branch plug are required See following illustrate RPI M50A String 1 String 2 String 3 Str...

Page 28: ...2 pairs of DC input connectors to connect with branch plugs Both 2 pairs of DC input connectors indicated by symbols shown as following picture Note that for Dc input connectors other than the specifi...

Page 29: ...specific DC connector the current passed through specific connector will be higher than that with only one PV string The rating of string fuse for the specific Dc connector should be enlarged 25A is...

Page 30: ...cs required per inverter Female Cable Coupler For polarity 2 Pcs required per inverter Male Cable Coupler Female cable coupler Vendor Model No Multi Contact PV AZS4 Vendor Model No Multi Contact PV AZ...

Page 31: ...he electrical code RPI M30A and M50A support both 3P3W 3phase and PE and 3P4W 3phase N and PE connections For M30A model End sleeve is not able to be installed if 25mm2 or 4AWG is applied For M50A mod...

Page 32: ...ct between installation instruction and electrical code please follow the electrical code Follow the steps below to strip the wires before assembling the AC plug Remove 55 mm 2 2 inch of AC cable oute...

Page 33: ...E must be connected correctly 1 Fixed this part 2 Rotate to loosen the AC plug 3 Depart the AC plug L1 L2 L3 N PE L1 L2 L3 N PE 4 Insert the wires 5 Tighten the screws to fixed the wires 5 Reassemble...

Page 34: ...AC plug L1 L2 N PE L3 Cable L1 L2 L3 N PE Cable Rotate to tighten the inserter Rotate gland to fix cable Fix it Inverter Rotate to tighten the plug AC plug Socket AC plug Cable Figure 4 14 AC plug ill...

Page 35: ...N The connection number of PV Array open circuit voltage and power of all strings in DC1 must be coherent The connection number of PV Array open circuit voltage and power of all strings in DC2 must be...

Page 36: ...sitive and negative which is shown in Figure 4 15 The connection shall be coherent with the indication marked on inverter PV KBT4 6 PV KST4 6 4 5 Communication Module Connections Please refer to Figur...

Page 37: ...Figure 4 17 only the first and last inverter s terminal resistor must be switched ON Please refer to table 4 7 for the terminal resister setting Pin Function 1 VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DAT...

Page 38: ...unction in Install Settings page Please refer to section 5 2 7 6 EPO RPI M30A M50A also provides 6 sets of digital input function K1 K6 Please refer to Table 4 8 for the digital input setting It have...

Page 39: ...sets of Dry Contact These 2 Dry Contacts are linked together and have the same function The function can be customized by users please refer to section 5 2 7 5 Dry Contact Figure 4 19 Dry contact por...

Page 40: ...rs through the LCD panel When you are adjusting settings LCD panel will change the display cursor from to 5 1 LCD Flow Chart Power Meter Energy Log Event Log Inverter Information General Settings Inst...

Page 41: ...d wait for inverter initially self test about 2 minutes If there is enough power generated from PV array inverter will start to feen in power to grid First Startup M30A M50A ENT Are you sure to set co...

Page 42: ...energy and life runtime via Energy Log page V 230 230 230 I 11 5 11 5 11 5 P 2645 2645 2645 L1 L2 L3 AC Power Frequency E Today AC 7935 50 00 24 W Hz kWh ENT or V 544 472 I 8 0 8 3 P 4350 3915 DC1 DC2...

Page 43: ...rred at grid side and it can show 5 records at a time 1 20 02 2013 15 30 AC Freq High 2 19 02 2013 09 30 AC Volt Low 29 20 02 2013 15 30 AC Freq High 30 19 02 2013 09 30 AC Volt Low ENT EXIT ENT or EN...

Page 44: ...ugh 5 2 6 General Settings Users can set Language Date and Time and RS 485 communication baud rate in this page Figure 5 7 Inverter information page Figure 5 8 General settings page Language Date and...

Page 45: ...nsulation Country Grid Settings DC Injection Dry Contact RCMU EPO ON Normal Close AC Connection Anti islanding Max Power Return to Factory 3P4W ON 52500W User Level Inverter ID Insulation Country Dry...

Page 46: ...pedance limits Installer must select the appropriate method based on PV array s wiring 5 2 7 3 Country Each country has its own electricity regulations Installer must select the country correctly ENT...

Page 47: ...Hi Off Slow Hi On Slow 219 0V 0 3s 276 0V 259 0V Hi Off Sl T Lo Off Slow Lo On Slow Lo Off Sl T 600 0s 184 0V 219 0V 1 0s Voltage Protection Freq Protection Reconnect T P Ramp Up ENT EXIT High Off Hig...

Page 48: ...iming No action Inverter is connecting to grid Fan Fail occurs Insulation test fail Any error fault or warning occurs Any Error occurs Any Fault occurs Setting Disable On Grid Fan Fail Insulation Alar...

Page 49: ...ls can support 3P3W and 3P4W system Please select the correct AC wiring type 5 2 7 8 Max Power Electricity regulation in some area requests that inverter must have power limit function In these areas...

Page 50: ...d in next section 5 2 8 1 Power Limit This control mode can reduce the output power to a percentage of inverter s rated power Users can limit the output power by set the Set Point in Power Limit page...

Page 51: ...in voltage V lock in and inverter s present output power is greater than lock in power P lock in inverter will reduce the output power and keep it at a certain value P lock out until grid voltage dro...

Page 52: ...operation interval When grid voltage reach the lock in voltage V lock in inverter will enable cosphi P function automatically and disabled it when grid voltage reach lock out voltage V lock out Consta...

Page 53: ...ive power accroding to grid voltage For country Italy MV and Italy LV users can set lock in power and lock out power to assign Q V function operation interval Constant cosphi Cosphi P Constant Q Q V E...

Page 54: ...ted to grid when grid voltage drops suddenly in few seconds In these areas users can enable FRT function and adjust the parameters to meet the requirement 100 U1 0 t1 Fault occurence t3 time Ugrid Uno...

Page 55: ...6 Maintenance WARNING Before any maintenance please switch AC and DC power off to avoid risk of electronic shock SPD DC SPD AC Temperature 400C 850C Item fail Green light will turn off Manufacturers...

Page 56: ...nd wait until LCD display turn off 2 Loosen the 6 screws on the front cover Figure 6 1 3 Recognize which SPD unit was damaged For DC SPD find the one that green light was turned off For AC SPD find th...

Page 57: ...Figure 6 3 Pull out the SPD unit Figure 6 2 Recognize the damaged SPD unit 57 Maintenance...

Page 58: ...splay turn off 2 Loosen the 6 screws on the front cover Figure 6 1 3 Pull out the fuse holder and check the fuse Figure 6 4 4 Replace the fuse if necessary 5 Reassemble the inverter Please be careful...

Page 59: ...fuse Figure 6 6 Diassembling fan panel 6 3 Clean Fan Loosen the 4 screws shown in Figure 6 1 Once the screws are loose pulling the fan bracket out will expose the connectors Each fan has one wire con...

Page 60: ...hat a fan needs to be replaced user should disassemble the 4 pcs screws around the fans and disconnect the connector right behind the fan bracket Then replace new fan and reassemble the 4pcs screws 6...

Page 61: ...AC breaker is OFF 2 Disconnect in AC plug 1 Switch on AC breaker 2 Check the connection in AC plug and make sure it connects to inverter AC Volt Low E10 E15 E20 1 Actual utility voltage is under the...

Page 62: ...itching devices in boost1 3 Check the detection circuit inside the inverter Solar2 Low W02 1 Actual Solar2 voltage is under the limit 2 Some devices were damaged inside the inverter if the actual Sola...

Page 63: ...Ambient temperature 90 or 30 2 Detection circuit malfunction 1 Check the installation ambient and environment 2 Check the detection circuit inside the inverter HW NTC3 Fail F09 1 Ambient temperature...

Page 64: ...iary circuitry inside the inverter 3 Check the detection circuit inside the inverter HW Red ADC1 F18 HW Red ADC2 F19 HW Eff F20 1 The calibration is incorrect 2 Current feedback circuit is defective 1...

Page 65: ...round 3 Driver for boost is defective or disconnected 4 Detection circuit malfunction 1 Check the inputs connections 2 Check the PV Array insulation 3 Check the driver circuit for boost inside the inv...

Page 66: ...ion circuit malfunction 1 Check the utility waveform Grid connection of inverter need to be far away from non linear load if necessary 2 Check all switching devices in inverter stage 3 Check the detec...

Page 67: ...Switch off AC circuit breaker to disconnect with electricity grid Switch off the PV array switch to disconnect from the PV array Use proper voltmeter to confirm that the AC and DC power are disconnec...

Page 68: ...vanic isolation NO Safety class Class I metal enclosure with protective earth Weight 74kg Dimensions W H D 612 740 278mm 48 5kg 612 625 278mm Connectors Weather resistant connectors DC INPUT Solar sid...

Page 69: ...y Rated 50 60Hz Programmable 45Hz 65Hz Total harmonic distortion 3 Power factor 0 99 full power Adjustable 0 80 leading 0 80 lagging Tare loss DC current injection Maximum efficiency EU efficiency AC...

Page 70: ...AR N 4105 BDEW UK G59 3 UTE C15 712 NB T 32004 Emission EN 61000 6 3 Harmonics EN 61000 3 12 Variations and flicker EN 61000 3 11 Immunity EN 61000 6 2 Immunity ESD IEC 61000 4 2 RS IEC 61000 4 3 EFT...

Page 71: ...5 0 7 0 75 0 8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 520V 600V 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of RPI M30A cos 1 0 Figure 9 1 M30A Thermal Derating Curve cos...

Page 72: ...ng Curve cos 0 95 0 5 0 55 0 6 0 65 0 7 0 75 0 8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 S 520V S 600V S 800V P 520V P 600V P 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of...

Page 73: ...8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 S 520V S 600V S 800V P 520V P 600V P 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of RPI M30A cos 0 9 Figure 9 3 M30A Thermal Derat...

Page 74: ...l Derating Curve cos 1 0 Ambient Temperature 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A 520Vdc 600Vdc 800Vdc P Pn Cos 1 0 Pn 50kW Ambient Te...

Page 75: ...ing Curve cos 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn Pn 50kW Cos 0 95 Am...

Page 76: ...ing Curve cos 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn 99 Pn 50kW Cos 0 9 A...

Page 77: ...RPI M30A M50A The power behind competitiveness www deltaww com English 1 77 153...

Page 78: ...ettings 5 2 7 5 Dry Contact 5 2 7 6 EPO 5 2 7 7 AC connection 5 2 7 8 Max Power 5 2 8 Active Reactive power 5 2 8 1 Power Limit 5 2 8 2 Power vs Frequency 5 2 8 3 P V 5 2 8 4 Constant cosphi 5 2 8 5 C...

Page 79: ...79...

Page 80: ...M30A RPI M50A 1 2 solar inverter PV array stand alone 1 1 1 1 1 3 RPI M30A RPI M50A http www deltaww com PV Array Electrical Grid Solar Inverter 3PH AC Distribution box Surge arrestor AC breaker 3 pha...

Page 81: ...2 1 RPI M30A M50A 2 1 2 2 1 2 2 RPI M30A 2 2 2 1 RPI M50A 2 3 2 2 81...

Page 82: ...2 2 M30A RPI M30A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 6 DC 2 1 M30A 1000V 1A Midget 82...

Page 83: ...2 3 M50A 1000V 1A Midget RPI M50A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 6 1 pcs 7 2 pcs DC DC 2 3 AC AC 4 5 DC 10 DC 2 2 M50A 83...

Page 84: ...2 3 2 4 RPI M30A M50A DC 2 3 RPI303FA0E1100 RPI503FA0E0000 RPI503FA0E0200 X V X DC X V V RPI M30A_121 RPI M50A_120 RPI M50A_122 2 3 2 4 RPI M50A RPI M30A 84...

Page 85: ...2 4 2 5 2 6 DC 2 5 Display Air inlet Label RPI M50A Display Air inlet Label RPI M30A Input Output Interfaces Input Output Interfaces 85...

Page 86: ...S 485 2 EPO 1 Dry Contact 2 Digital Input 6 DC1 DC2 String8 String9 String10 String4 String5 String6 String7 RPI M50A DC1 DC2 String1 String2 String3 String4 String5 String6 AC Connector 380 400Vac 3P...

Page 87: ...3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 87...

Page 88: ...3 1 3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 88...

Page 89: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 89...

Page 90: ...3 5 25 60 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 90...

Page 91: ...4 1 DC 4 OFF M50A DC 15A DC 10A DC 4 1 MPPT 2 4 2 DC 4 1 RPI AC 1000V 1A midget 4 3 4 4 PID Plus Grounded Minus Grounded DC AC DC insulation 5 2 7 Install Settings 91...

Page 92: ...Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M30A can support 3P3W system 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M50A...

Page 93: ...bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 RPI M50A 4 2 93...

Page 94: ...1 2 3 AC Wiring DC Wiring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 1A Grounding fuse bus b...

Page 95: ...2 3 AC Wiring DC Wiring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac 1A Grounding fuse bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 Stri...

Page 96: ...ID Plus Grounded Minus Grounded DC Insulation 5 2 7 Install Settings 4 5 M30A_121 DC 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 PV Array AC Wiring DC Wiring Parallel or Separate RPI M30A can sup...

Page 97: ...1 3 PV Array AC Wiring Must be Parallel Connection DC Distribution box Plus GND or Minus GND Z Z or Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac Must install a transformer 2 DC Wirin...

Page 98: ...M50A Note for Field Wiring M50A 16A 4 7 M50A RPI M30A_121 32A RPI M50A_120 16A RPI M50A_122 16A 4 1 4 7 16A 16A 16A 16A 98...

Page 99: ...4 8 16A 4 8 16A 16A 16A 16A Strictly forbiden Risk of fire on internal entrance cabling M50A 99...

Page 100: ...4 10 32A 4 10 M30A 32A 32A 100...

Page 101: ...4 11 30A 4 11 30A Note 30A M30A 101...

Page 102: ...25A Y 10 10 12 Y RPI M50A String 1 String 2 String 3 String 5 String 4 String 6 String 7 String 8 String 9 String10 String 1 String 2 String 3 String 5 String 6 String 8 String 9 String11 String12 Str...

Page 103: ...2 2 103...

Page 104: ...String Fuse 15A String Fuse Y String Fuse 25A 6 2 String Fuse Max 25A 4 String Fuse 104...

Page 105: ...For polarity 2 Female Cable Coupler For polarity 2 Male Cable Coupler Female cable coupler Vendor Model No Multi Contact PV AZS4 Vendor Model No Multi Contact PV AZB4 Little Fuse 0SPF025 T 1000V 25A 4...

Page 106: ...d PE Model Upstream circuit breaker RPI M30A RPI M50A 100A 60A 4 2 AC 4 3 4 3 M30A 25mm2 4AWG M50A 1AWG M50A 25mm2 3AWG 65A 100 A RPI M30A RPI M50A 3 N m 2 5 N m G N L1 L3 L2 N L1 L2 L3 PE To solar in...

Page 107: ...AC AC AC plug 55mm L1 L2 L3 N 52 5mm RPI M30A 12mm 0 5 inch RPI M50A 18mm 0 7 inch 4 12 AC 107...

Page 108: ...oosen the AC plug 3 Depart the AC plug L1 L2 L3 N PE L1 L2 L3 N PE 4 Insert the wires 5 Tighten the screws to fixed the wires 5 Reassemble the AC plug Inverter 7 Rotate to tighten the plug 8 Rotatethe...

Page 109: ...e to loose the AC plug L1 L2 N PE L3 Cable L1 L2 L3 N PE Cable Rotate to tighten the inserter Rotate gland to fix cable Fix it Inverter Rotate to tighten the plug AC plug Socket AC plug Cable 4 14 RPI...

Page 110: ...tings AC L1 L2 400 Vac 10 L1 N 230 Vac 10 L1 L3 400 Vac 10 L2 N 230 Vac 10 L2 L3 400 Vac 10 L3 N 230 Vac 10 4 4 PV Array DC1 string TDC2 string Voc 1000Vdc 4 4 RPI M30A RPI M50A 35 kW 52 5 kW DC1 DC2...

Page 111: ...M50A_120 DC 15A 4 6mm 12 10 AWG 2 RPI M50A_122 DC 15A 4 6mm 12 10 AWG 2 4 5 4 15 DC 4 16 DC 4 15 PV KBT4 6 PV KST4 6 4 5 RPI M30A M50A 4 16 VCC RS 485 3 5 4 9 EPO 1 Digital Inputs 6 Dry Contact 2 VCC...

Page 112: ...VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA 4 6 RS 485 4 17 1 2 3 4 5 6 Data Format Baud rate 9600 19200 default or 38400 Data bits 8 Stop bit 1 Parity N A RS485 USB or RS485 RS232 Terminal Resistor 12...

Page 113: ...F Terminal Resistor OFF OFF ON 4 7 4 18 EPO 4 8 EPO 4 5 2 RRPI M30A M50A EPO Install Settings 5 2 7 6 EPO 6 K1 K6 4 8 digital input Active Reactive power PF and P U EPO Digital Input 30 60 100 V1 K0 V...

Page 114: ...4 5 3 RPI M30A M50A 2 5 2 7 5 Dry Contact 4 19 Dry Contact 1 Dry Contact 2 114...

Page 115: ...30A M50A 4x20 LED 5 1 5 1 LCD Power Meter Energy Log Event Log Inverter Information General Settings Install Settings Active Reactive Power FRT 5 2 2 5 2 3 5 2 4 5 2 5 5 2 6 5 2 7 5 2 8 5 2 9 5 70 5 1...

Page 116: ...tus DC 2 First Startup M30A M50A ENT Are you sure to set country XXX Yes No EXIT ENT EXIT Select Country AU NZ Austria Belgium Select Language English Deutsch Fran ais 5 2 1 5 3 Power ESC 5 21 Jun 201...

Page 117: ...230 230 I 11 5 11 5 11 5 P 2645 2645 2645 L1 L2 L3 AC Power Frequency E Today AC 7935 50 00 24 W Hz kWh ENT or V 544 472 I 8 0 8 3 P 4350 3915 DC1 DC2 DC ENT or 5 4 Power meter 5 5 Energy log Energy...

Page 118: ...15 30 AC Freq High 2 19 02 2013 09 30 AC Volt Low 29 20 02 2013 15 30 AC Freq High 30 19 02 2013 09 30 AC Volt Low ENT EXIT ENT or ENT or EXIT Error Events Grid Report Error Events Grid Report 1 20 02...

Page 119: ...General settings Language Date and Time Baud Rate ENT or S N RN11179CB0 Install 30 04 2014 DSP 1 80 Red 1 65 Comm 1 65 ID 002 ENT or AC connection Max Power Dry Cont EPO 3P4W 52500W Insulation Normal...

Page 120: ...4W ON 52500W User Level Inverter ID Insulation Country Dry Contact EPO AC Connection Max Power Manufacturer Level All Settings Installer Level Inverter ID Insulation Country Grid Settings Dry Contact...

Page 121: ...ded OFF 5 2 7 3 Country ENT EXIT Inverter ID 002 Insulation Country Grid Settings AU NZ Austria Belgium China ENT EXIT ENT EXIT EXIT Inverter ID 002 Insulation Country Grid Settings Mode ON Resistance...

Page 122: ...600 0s 184 0V 219 0V 1 0s Voltage Protection Freq Protection Reconnect T P Ramp Up ENT EXIT High Off High On High Off T Low Off 51 50Hz 50 05Hz 0 1s 47 50Hz Low On Low Off T Hi Off Slow Hi On Slow 47...

Page 123: ...Fault Warning Error Fault Disable On Grid Fan Fail Insulation Alarm Error Fault Warning Warning 5 2 5 14 Dry Contact DC Injection Dry Contact RCMU EPO On Grid ON Normal Close ENT EXIT Alarm Error Faul...

Page 124: ...onnection RPI M30A M50A 3P3W 3P4W 5 2 7 8 Max Power DC Injection Dry Contact RCMU EPO ON Normal Close 5 15 EPO 5 16 EPO 5 17 Max Power AC Connection Anti islanding Max Power Return to Factory 3P4W ON...

Page 125: ...stant Q and Q V 5 2 8 1 Power Limit Set Point 5 2 8 2 Power vs Frequency 5 13 Power Limit Power vs Frequency P V ENT EXIT Mode Set Point ON 100 Power Limit Power vs Frequency P V Mode F start F recove...

Page 126: ...Others f recovery fprotection fprotection 5 21 Power vs Frequency 5 22 P V 5 2 8 3 P V V lock in P lock in P lock out V lock out T recovery Power Limit Power vs Frequency P V ENT EXIT EXIT Mode P loc...

Page 127: ...sphi P Constant Q Q V ENT EXIT Mode cosphi OFF Ind 1 00 5 23 Constant cosphi 5 24 Cosphi P Constant cosphi Cosphi P Constant Q Q V ENT EXIT EXIT Mode Q upper P lower Q lower OFF Ind 1 00 45 Ind 0 90 P...

Page 128: ...ock in P lock out Constant cosphi Cosphi P Constant Q Q V ENT EXIT Mode Fix Q OFF Ind 90 Constant cosphi Cosphi P Constant Q Q V ENT EXIT EXIT EXIT Mode V1s V2s Qs limit OFF 248 4V 253 0V Ind 44 V1i V...

Page 129: ...30 FRT 5 2 9 FRT Fault ride through FRT 100 U1 0 t1 Fault occurence t3 time Ugrid Unom Umin Udrop Disconnect from grid Stay connected General Settings Install Settings Active Reactive Pwr FRT ENT EXIT...

Page 130: ...ers ShangHai GEHE Lighti Temperature 400C 850C Item fail Red upright bulb Manufacturers ShangHai GEHE Lighti Table 6 1 SPD Specifications Part number GPU1 ZS1000 Y Part number GPU1 C4 690 1P Y Work vo...

Page 131: ...SPD Fail 1 AC DC 2 6 1 3 DC SPD AC SPD 6 2 4 6 3 5 6 1 RPI M50A 131...

Page 132: ...6 3 SPD 6 2 SPD 132...

Page 133: ...AC DC 2 6 1 3 6 4 4 5 Item String Fuse source 1 Part number 10GPV15U0 Rate amp 15 A Rate voltage 1000 V Manufacturers Hollyland Item String Fuse source 2 Part number 0SPF015 T Rate amp 15 A Rate volt...

Page 134: ...6 5 6 6 6 3 6 6 134...

Page 135: ...6 7 6 8 6 4 6 5 6 8 4 135...

Page 136: ...1 2 3 Grid Quality E07 HW Con Fail E08 1 AC 2 1 AC 2 No Grid E09 1 AC 2 AC 1 AC 2 AC AC Volt Low E10 E15 E20 1 2 3 AC 4 1 2 3 AC 4 AC Volt High E11 E13 E16 E18 E21 E23 1 2 3 4 1 2 3 4 Solar1 High E30...

Page 137: ...ray Voc 1000Vdc 2 Insulation E34 1 2 3 1 2 3 7 1 Solar1 Low W01 1 Solar1 2 Solar1 0 3 1 Solar1 2 boost1 3 Solar2 Low W02 1 Solar2 2 Solar1 0 3 1 Solar2 voltage 2 boost2 3 HW FAN W11 1 2 3 4 1 2 3 4 SP...

Page 138: ...erature F07 1 30 2 1 2 RTM1 RTB1 RTG1 and RTH1 HW NTC1 Fail F06 1 90 30 2 1 2 RTM1 HW NTC2 Fail F08 1 90 30 2 1 2 RTB1 HW NTC3 Fail F09 1 90 30 2 1 2 RTG1 HW NTC4 Fail F10 1 90 30 2 1 2 RTH1 DC RLY Fa...

Page 139: ...1 150Vdc 2 3 1 2 3 1 150Vdc 2 3 HW Red ADC1 F18 HW Red ADC2 F19 HW Eff F20 1 2 1 2 HW COMM1 F23 1 DSP 2 3 1 DSP reset crystal 2 DSP COMM 3 HW COMM2 F22 1 Red CPU 2 1 Red CPU reset crystal 2 Red CPU D...

Page 140: ...RLY Short F28 RLY Open F13 F29 Bus Unbal F30 1 2 3 Boost 4 1 2 3 boost 4 HW Bus OVR F31 F33 F35 1 Boost 2 Voc 1000Vdc 3 4 1 boost 2 Voc 1000Vdc 3 N A 4 AC Cur High F36 F37 F38 F39 F40 F41 1 2 Inverter...

Page 141: ...F43 1 2 CSC2 3 1 WC3 CNC16 2 CSC2 3 HW CT C Fail F44 1 2 CSC3 3 1 WC3 CNC16 2 CSC3 3 1 2 3 1 2 inverter stage 3 HW AC OCR F45 HW ZC Fail F50 DC Cur High F60 F61 F70 F71 1 Boost 2 Boost 3 1 boost 2 boo...

Page 142: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 142...

Page 143: ...put III DC Input II 0 NO Class I metal enclosure with protective earth 74kg W H D 612 740 278mm 48 5kg 612 625 278mm Weather resistant connectors Solar side 35kW 58kW 31 5kW 52 5kW PV 38kW 63kW 1000V...

Page 144: ...leading 0 80 lagging DC AC 0 5 rated current 3 Ph N PE 3 phase AC plug that meets IP67 and specifications in table 4 2 6 pairs MC4 10 pairs MC4 30A 2 50 A 2 36A Each String 12A 60A Each String 12A 50k...

Page 145: ...EN 61000 6 3 Harmonics EN 61000 3 12 Variations and flicker EN 61000 3 11 Immunity EN 61000 6 2 Immunity ESD IEC 61000 4 2 RS IEC 61000 4 3 EFT IEC 61000 4 4 Surge IEC 61000 4 5 CS IEC 61000 4 6 PFMF...

Page 146: ...146 0 5 0 55 0 6 0 65 0 7 0 75 0 8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 520V 600V 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of RPI M30A cos 1 0 9 1 M30A cos 1 0...

Page 147: ...A cos 0 95 0 5 0 55 0 6 0 65 0 7 0 75 0 8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 S 520V S 600V S 800V P 520V P 600V P 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of RPI M3...

Page 148: ...148 9 3 M30A cos 0 9...

Page 149: ...9 4 M50A cos 1 0 Ambient Temperature 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A 520Vdc 600Vdc 800Vdc P Pn Cos 1 0 Pn 50kW Ambient Temperatu...

Page 150: ...0A cos 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn Pn 50kW Cos 0 95 Ambient T...

Page 151: ...0A cos 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn 99 Pn 50kW Cos 0 9 Ambien T...

Page 152: ......

Page 153: ...RPI M30A M50A The power behind competitiveness www deltaww com English 1 77 153...

Page 154: ...5 2 7 5 Dry Contact 5 2 7 6 EPO 5 2 7 7 AC connection 5 2 7 8 Max Power 5 2 8 Active Reactive power 5 2 8 1 Power Limit 5 2 8 2 Power vs Frequency 5 2 8 3 P V 5 2 8 4 Constant cosphi 5 2 8 5 Cosphi P...

Page 155: ...155...

Page 156: ...30A RPI M50A 1 2 solar inverter PV array stand alone 1 1 1 1 1 3 RPI M30A RPI M50A http www deltaww com PV Array Electrical Grid Solar Inverter 3PH AC Distribution box Surge arrestor AC breaker 3 phas...

Page 157: ...RPI M30A M50A 2 1 2 2 1 2 1 2 2 RPI M30A 2 2 2 1 RPI M50A 2 3 2 2 157...

Page 158: ...2 2 M30A RPI M30A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 2 3 AC AC 4 5 DC 6 DC 2 1 M30A 1000V 1A Midget 158...

Page 159: ...2 3 M50A 1000V 1A Midget 2 2 M50A RPI M50A 1 1 pcs 1 pcs 1 pcs 1 pcs RPI 6 1 pcs 7 2 pcs DC DC 2 3 AC AC 4 5 DC 10 DC 159...

Page 160: ...2 3 2 4 RPI M30A M50A DC 2 3 RPI303FA0E1100 RPI503FA0E0000 RPI503FA0E0200 X V X DC X V V RPI M30A_121 RPI M50A_120 RPI M50A_122 2 3 2 4 RPI M50A RPI M30A 160...

Page 161: ...2 4 2 5 2 6 DC 2 5 Display Air inlet Label RPI M50A Display Air inlet Label RPI M30A Input Output Interfaces Input Output Interfaces 161...

Page 162: ...485 2 EPO 1 Dry Contact 2 Digital Input 6 DC1 DC2 String8 String9 String10 String4 String5 String6 String7 RPI M50A DC1 DC2 String1 String2 String3 String4 String5 String6 AC Connector 380 400Vac 3Ph...

Page 163: ...3 AC DC 1 12 M6 3 3 2 3 2 M6 3 4 163...

Page 164: ...3 1 3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 164...

Page 165: ...M6 Screw 6 Wall M6 Screw 6 3 3 3 4 165...

Page 166: ...3 5 25 60 30 cm 20 cm 50 cm 30 cm 30 cm 3 5 166...

Page 167: ...4 1 DC 4 OFF M50A DC 15A DC 10A DC 4 1 MPPT 2 4 2 DC 4 1 RPI AC 1000V 1A midget 4 3 4 4 PID Plus Grounded Minus Grounded DC AC DC insulation 5 2 7 Install Settings 167...

Page 168: ...iring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M30A can support 3P3W system 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M50A c...

Page 169: ...bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 RPI M50A 4 2 169...

Page 170: ...2 3 AC Wiring DC Wiring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 String 6 10 1A Grounding fuse bus ba...

Page 171: ...2 3 AC Wiring DC Wiring Separated connection only Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac 1A Grounding fuse bus bar kit 2 DC1 DC2 DC1 DC2 String 1 5 String 6 10 String 1 5 Strin...

Page 172: ...D Plus Grounded Minus Grounded DC Insulation 5 2 7 Install Settings 4 5 M30A_121 DC 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 PV Array AC Wiring DC Wiring Parallel or Separate RPI M30A can supp...

Page 173: ...1 3 PV Array AC Wiring Must be Parallel Plus Grounded Minus Grounded PID Connection DC Distribution box Plus GND or Minus GND Z Z or Isolated transformer Utility To Inverter 3Ph 400Vac 3Ph 400Vac Must...

Page 174: ...M50A Note for Field Wiring M50A 16A 4 7 M50A RPI M30A_121 32A RPI M50A_120 16A RPI M50A_122 16A 4 1 4 7 16A 16A 16A 16A 174...

Page 175: ...4 8 16A 4 8 16A 16A 16A 16A Strictly forbiden Risk of fire on internal entrance cabling M50A 175...

Page 176: ...4 10 32A 4 10 M30A 32A 32A 176...

Page 177: ...4 11 30A 4 11 30A Note 30A M30A 177...

Page 178: ...25A Y 10 10 12 Y RPI M50A String 1 String 2 String 3 String 5 String 4 String 6 String 7 String 8 String 9 String10 String 1 String 2 String 3 String 5 String 6 String 8 String 9 String11 String12 Str...

Page 179: ...2 2 179...

Page 180: ...String Fuse 15A String Fuse Y String Fuse 25A 6 2 String Fuse Max 25A 4 String Fuse 180...

Page 181: ...For polarity 2 Female Cable Coupler For polarity 2 Male Cable Coupler Female cable coupler Vendor Model No Multi Contact PV AZS4 Vendor Model No Multi Contact PV AZB4 Little Fuse 0SPF025 T 1000V 25A 4...

Page 182: ...d PE Model Upstream circuit breaker RPI M30A RPI M50A 100A 60A 4 2 AC 4 3 4 3 M30A 25mm2 4AWG M50A 1AWG M50A 25mm2 3AWG 65 A 100 A RPI M30A RPI M50A 3 N m 2 5 N m G N L1 L3 L2 N L1 L2 L3 PE To solar i...

Page 183: ...AC AC AC plug 55mm L1 L2 L3 N 52 5mm RPI M30A 12mm 0 5 inch RPI M50A 18mm 0 7 inch 4 12 AC 183...

Page 184: ...oosen the AC plug 3 Depart the AC plug L1 L2 L3 N PE L1 L2 L3 N PE 4 Insert the wires 5 Tighten the screws to fixed the wires 5 Reassemble the AC plug Inverter 7 Rotate to tighten the plug 8 Rotatethe...

Page 185: ...e to loose the AC plug L1 L2 N PE L3 Cable L1 L2 L3 N PE Cable Rotate to tighten the inserter Rotate gland to fix cable Fix it Inverter Rotate to tighten the plug AC plug Socket AC plug Cable 4 14 RPI...

Page 186: ...L1 L2 400 Vac 10 L1 N 230 Vac 10 L1 L3 400 Vac 10 L2 N 230 Vac 10 L2 L3 400 Vac 10 L3 N 230 Vac 10 4 4 WARNING PV Array CAUTION DC1 string TDC2 string Voc 1000Vdc 4 4 RPI M30A RPI M50A 35 kW 52 5 kW...

Page 187: ...M50A_120 DC 15A 4 6mm 12 10 AWG 2 RPI M50A_122 DC 15A 4 6mm 12 10 AWG 2 4 5 4 15 DC 4 16 DC 4 15 PV KBT4 6 PV KST4 6 4 5 RPI M30A M50A 4 16 VCC RS 485 3 5 4 9 EPO 1 Digital Inputs 6 Dry Contact 2 VCC...

Page 188: ...VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA 4 6 RS 485 4 17 1 2 3 4 5 6 Data Format Baud rate 9600 19200 default or 38400 Data bits 8 Stop bit 1 Parity N A RS485 USB or RS485 RS232 Terminal Resistor 12...

Page 189: ...F OFF OFF ON 4 7 4 18 EPO 4 8 EPO 4 5 2 RPI M30A M50A EPO Install Settings 5 2 7 6 EPO 6 K1 K6 4 8 digital input Active Reactive power P F and P U EPO Digital Input 30 60 100 V1 K0 V1 K1 V1 K2 V1 K3 V...

Page 190: ...4 5 3 RPI M30A M50A 2 5 2 7 5 Dry Contact 4 19 Dry Contact 1 Dry Contact 2 190...

Page 191: ...30A M50A 4x20 LED 5 1 5 1 LCD Power Meter Energy Log Event Log Inverter Information General Settings Install Settings Active Reactive Power FRT 5 2 2 5 2 3 5 2 4 5 2 5 5 2 6 5 2 7 5 2 8 5 2 9 5 70 5 1...

Page 192: ...tus DC 2 First Startup M30A M50A ENT Are you sure to set country XXX Yes No EXIT ENT EXIT Select Country AU NZ Austria Belgium Select Language English Deutsch Fran ais 5 2 1 5 3 Power ESC 5 21 Jun 201...

Page 193: ...230 230 I 11 5 11 5 11 5 P 2645 2645 2645 L1 L2 L3 AC Power Frequency E Today AC 7935 50 00 24 W Hz kWh ENT or V 544 472 I 8 0 8 3 P 4350 3915 DC1 DC2 DC ENT or 5 4 Power meter 5 5 Energy log Energy...

Page 194: ...15 30 AC Freq High 2 19 02 2013 09 30 AC Volt Low 29 20 02 2013 15 30 AC Freq High 30 19 02 2013 09 30 AC Volt Low ENT EXIT ENT or ENT or EXIT Error Events Grid Report Error Events Grid Report 1 20 02...

Page 195: ...General settings Language Date and Time Baud Rate ENT or S N RN11179CB0 Install 30 04 2014 DSP 1 80 Red 1 65 Comm 1 65 ID 002 ENT or AC connection Max Power Dry Cont EPO 3P4W 52500W Insulation Normal...

Page 196: ...4W ON 52500W User Level Inverter ID Insulation Country Dry Contact EPO AC Connection Max Power Manufacturer Level All Settings Installer Level Inverter ID Insulation Country Grid Settings Dry Contact...

Page 197: ...ded OFF 5 2 7 3 Country ENT EXIT Inverter ID 002 Insulation Country Grid Settings AU NZ Austria Belgium China ENT EXIT ENT EXIT EXIT Inverter ID 002 Insulation Country Grid Settings Mode ON Resistance...

Page 198: ...600 0s 184 0V 219 0V 1 0s Voltage Protection Freq Protection Reconnect T P Ramp Up ENT EXIT High Off High On High Off T Low Off 51 50Hz 50 05Hz 0 1s 47 50Hz Low On Low Off T Hi Off Slow Hi On Slow 47...

Page 199: ...Fault Warning Error Fault Disable On Grid Fan Fail Insulation Alarm Error Fault Warning Warning 5 2 5 14 Dry Contact DC Injection Dry Contact RCMU EPO On Grid ON Normal Close ENT EXIT Alarm Error Faul...

Page 200: ...onnection RPI M30A M50A 3P3W 3P4W 5 2 7 8 Max Power DC Injection Dry Contact RCMU EPO ON Normal Close 5 15 EPO 5 16 EPO 5 17 Max Power AC Connection Anti islanding Max Power Return to Factory 3P4W ON...

Page 201: ...stant Q and Q V 5 2 8 1 Power Limit Set Point 5 2 8 2 Power vs Frequency 5 13 Power Limit Power vs Frequency P V ENT EXIT Mode Set Point ON 100 Power Limit Power vs Frequency P V Mode F start F recove...

Page 202: ...Others f recovery fprotection fprotection 5 21 Power vs Frequency 5 22 P V 5 2 8 3 P V V lock in P lock in P lock out V lock out T recovery Power Limit Power vs Frequency P V ENT EXIT EXIT Mode P loc...

Page 203: ...sphi P Constant Q Q V ENT EXIT Mode cosphi OFF Ind 1 00 5 23 Constant cosphi 5 24 Cosphi P Constant cosphi Cosphi P Constant Q Q V ENT EXIT EXIT Mode Q upper P lower Q lower OFF Ind 1 00 45 Ind 0 90 P...

Page 204: ...ock in P lock out Constant cosphi Cosphi P Constant Q Q V ENT EXIT Mode Fix Q OFF Ind 90 Constant cosphi Cosphi P Constant Q Q V ENT EXIT EXIT EXIT Mode V1s V2s Qs limit OFF 248 4V 253 0V Ind 44 V1i V...

Page 205: ...30 FRT 5 2 9 FRT Fault ride through FRT 100 U1 0 t1 Fault occurence t3 time Ugrid Unom Umin Udrop Disconnect from grid Stay connected General Settings Install Settings Active Reactive Pwr FRT ENT EXIT...

Page 206: ...1000 Vdc Work voltage 690 Vac Work Amp In 8 20 20kA Work Amp In 8 20 15kA Rate Amp I max 8 20 40kA Temperature 400C 850C Item fail Green light will turn off Manufacturers ShangHai GEHE Lighti Rate Amp...

Page 207: ...SPD Fail 1 AC DC 2 6 1 3 DC SPD AC SPD 6 2 4 6 3 5 6 1 RPI M50A 207...

Page 208: ...6 3 SPD 6 2 SPD 208...

Page 209: ...AC DC 2 6 1 3 6 4 4 5 Item String Fuse source 1 Part number 10GPV15U0 Rate amp 15 A Rate voltage 1000 V Manufacturers Hollyland Item String Fuse source 2 Part number 0SPF015 T Rate amp 15 A Rate volt...

Page 210: ...6 5 6 6 6 3 6 6 210...

Page 211: ...6 7 6 8 6 4 6 5 6 8 4 211...

Page 212: ...1 2 3 Grid Quality E07 HW Con Fail E08 1 AC 2 1 AC 2 No Grid E09 1 AC 2 AC 1 AC 2 AC AC Volt Low E10 E15 E20 1 2 3 AC 4 1 2 3 AC 4 AC Volt High E11 E13 E16 E18 E21 E23 1 2 3 4 1 2 3 4 Solar1 High E30...

Page 213: ...ray Voc 1000Vdc 2 Insulation E34 1 2 3 1 2 3 7 1 Solar1 Low W01 1 Solar1 2 Solar1 0 3 1 Solar1 2 boost1 3 Solar2 Low W02 1 Solar2 2 Solar1 0 3 1 Solar2 voltage 2 boost2 3 HW FAN W11 1 2 3 4 1 2 3 4 SP...

Page 214: ...erature F07 1 30 2 1 2 RTM1 RTB1 RTG1 and RTH1 HW NTC1 Fail F06 1 90 30 2 1 2 RTM1 HW NTC2 Fail F08 1 90 30 2 1 2 RTB1 HW NTC3 Fail F09 1 90 30 2 1 2 RTG1 HW NTC4 Fail F10 1 90 30 2 1 2 RTH1 DC RLY Fa...

Page 215: ...1 150Vdc 2 3 1 2 3 1 150Vdc 2 3 HW Red ADC1 F18 HW Red ADC2 F19 HW Eff F20 1 2 1 2 HW COMM1 F23 1 DSP 2 3 1 DSP reset crystal 2 DSP COMM 3 HW COMM2 F22 1 Red CPU 2 1 Red CPU reset crystal 2 Red CPU D...

Page 216: ...RLY Short F28 RLY Open F13 F29 Bus Unbal F30 1 2 3 Boost 4 1 2 3 boost 4 HW Bus OVR F31 F33 F35 1 Boost 2 Voc 1000Vdc 3 4 1 boost 2 Voc 1000Vdc 3 N A 4 AC Cur High F36 F37 F38 F39 F40 F41 1 2 Inverter...

Page 217: ...CSC2 3 1 WC3 CNC16 2 CSC2 3 HW CT C Fail F44 1 2 CSC3 3 1 WC3 CNC16 2 CSC3 3 1 WC3 CNC16 2 CSC3 3 1 2 inverter stage 3 HW AC OCR F45 HW ZC Fail F50 DC Cur High F60 F61 F70 F71 1 Boost 2 Boost 3 1 boo...

Page 218: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 218...

Page 219: ...put III DC Input II 0 NO Class I metal enclosure with protective earth 74kg W H D 612 740 278mm 48 5kg 612 625 278mm Weather resistant connectors Solar side 35kW 58kW 31 5kW 52 5kW PV 38kW 63kW 1000V...

Page 220: ...rrent 3 Ph N PE 3 phase AC plug that meets IP67 and specifications in table 4 2 6 pairs MC4 10 pairs MC4 30A 2 50 A 2 36A Each String 12A 50kW 50kVA 33kW 33kVA 9 1 9 3 55kW 55kVA 9 4 9 6 3Ph 230 400Va...

Page 221: ...EN 61000 6 3 Harmonics EN 61000 3 12 Variations and flicker EN 61000 3 11 Immunity EN 61000 6 2 Immunity ESD IEC 61000 4 2 RS IEC 61000 4 3 EFT IEC 61000 4 4 Surge IEC 61000 4 5 CS IEC 61000 4 6 PFMF...

Page 222: ...222 9 1 M30A cos 1 0...

Page 223: ...A cos 0 95 0 5 0 55 0 6 0 65 0 7 0 75 0 8 0 85 0 9 0 95 1 1 05 1 1 1 15 25 30 35 40 45 50 55 60 S 520V S 600V S 800V P 520V P 600V P 800V P Pn Pn 30kW AmbientTemperature Temperature Derating of RPI M3...

Page 224: ...224 9 3 M30A cos 0 9...

Page 225: ...9 4 M50A cos 1 0 Ambient Temperature 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A 520Vdc 600Vdc 800Vdc P Pn Cos 1 0 Pn 50kW Ambient Temperatu...

Page 226: ...0A cos 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn Pn 50kW Cos 0 95 Ambient T...

Page 227: ...0A cos 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P 520Vdc S 520Vdc P 600Vdc S 600Vdc P 800Vdc S 800Vdc P Pn 99 Pn 50kW Cos 0 9 Ambien T...

Page 228: ...Version 1 03 2015 May...

Reviews: