2-1 FUNCTIONS AND FEATURES
A True ON LINE design. The UPS insures the critical power protection for your
mission-critical equipment at all times.
Wide input range of power supply that reduces discharge rate of battery.
A smart charger design for auto equalizing charge to shorten charging time.
Equipped with RS232 port and Dry-contact interface, using the power management
software “UPSentry Smart 2000” allows near-end and far-end UPS monitoring
management.
Automatic detection
of 50/60Hz field input frequency
With excellent performance. Input current using active input power factor correction
and a high-frequency inverter with pulse width modulation.
Optional isolated output transformer: Provides isolation and multiple output voltage.
Start-on-battery capability for powering up the UPS even if utility power is not
available.
Optional SNMP interface card is an optional accessory for network communication.
Implementing diagnostic test and LCD message display by using microprocessor
technology can provide detailed information on operation status.
Manual and static bypass switch forms. Allowance for switching to the main power
supply.
Static bypass supply circuit incorporates functions such as surge suppression and
EMI filter.
Remote emergency power off (REPO): Emergency shutdown control through the
remote emergency power-off (REPO) port.
Auto recovery function of inverter:
When the AC power is restored after a low battery shutdown, the UPS inverter will
automatically restart.
Automatic transfer to inverter output from static bypass after overload condition is
cleared.
Alarm cancel facility to switch off the audible alarm and indicative lights still lit in the
event of long BACK-UP periods.
External battery cabinet can be used for extending operation time of battery mode.
Operation of “ECONOMIC Mode” (Optional): When input voltage is within the range of
rating voltage (±10%), the UPS is working in the bypass mode for higher efficiency.
Otherwise the UPS will be switched to inverter mode.
Auto detection for voltage in bypass mode: The protection range is +15%~ -
20%.
When the bypass voltage is beyond protection range, the UPS will not supply output
power to the load.
Auto detection and display for normal operation of fan.