Delta LYTE II DRL-24V480W1EN Manual Download Page 9

LYTE II DIN Rail Power Supply 

DRL-480W series / DRL-

V480W1EN

 

PRELIMINARY DATASHEET- For product review purpose only. The specs are subjected to change.

 

 

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (August 2021, Rev. X00) 

 

9

 

Assembly & Installation 

 

The power supply unit (PSU) can be mounted on 35 mm DIN rails in accordance with EN 60715. The device should be installed with 

input terminal block at the bottom.  

 

Each device is delivered ready to install. 

 

Mounting 

Dismounting 

 

 

 

       

                    

Fig. 3.1   Mounting 

 

Snap on the DIN rail as shown in Fig. 3.1: 

1.  Tilt the unit upwards and insert it onto the DIN rail.  

2.  Push downwards until stopped. 

3.  Press against the bottom front side for locking. 

4.  Shake the unit slightly to ensure that it is secured 

Fig. 3.2   Dismounting 

 

To uninstall, Delta provides an easy way to pull or slide down the 

latch with screw driver as shown in Fig. 3.2. Then slide the power 

supply unit (PSU) in the opposite direction, release the latch and 

pull out the power supply unit (PSU) from the rail. 

 

 

 

 

Safety Instructions 

  Vertical Mounting 

    

 

 

 

  ALWAYS switch mains of input power OFF before connecting and 

disconnecting the input voltage to the unit. If mains are not turned OFF, 

there is risk of explosion / severe damage. 

 

To guarantee sufficient convection cooling, keep a distance of 40 mm 

(1.57 inch) above and 20 mm (0.79 inch) below the device as well as a 

lateral distance of 5 mm (0.2 inch) to other units and if load less than 

50%, lateral distance can be 0 mm. In case the adjacent device is a 

heat source, the lateral distance will be 15 mm (0.6 inch). 

  Note that the enclosure of the device can become very hot depending on 

the surrounding air temperature and load of the power supply. Risk of burns! 

  The main power must be turned off before connecting or disconnecting 

wires to the terminals. 

  DO NOT insert any objects into the unit. 

  Hazardous voltages may be present for up to 5 minutes after the input 

mains voltage is disconnected. Do not touch the unit during this time. 

  The power supplies are built in units and must be installed in a cabinet or 

room (condensation free environment and indoor location) that is relatively 

free of conductive contaminants. 

Summary of Contents for LYTE II DRL-24V480W1EN

Page 1: ...applications without compromising on quality and reliability The convection cooled LYTE II series will operate between 30 C to 70 C with full rated power available from 30 C to 50 C at 230 Vac The ov...

Page 2: ...Vac Output Ratings Characteristics 2 Nominal Output Voltage 24 Vdc 48 Vdc Factory Set Point Tolerance 24 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 24 28 Vdc 48 55 Vdc Output Current 0 20 0 A 0 10...

Page 3: ...er De rating Temperature 40 C de rate power by 1 67 C 115 Vac 50 C de rate power by 2 5 C 230 Vac Input Voltage 100Vac de rate power by 1 Vac Operating Humidity 20 to 90 RH Non Condensing Operating Al...

Page 4: ...O P 100 load Ta 25 C Expected Cap Life Time 10 years 230 Vac 50 load 40 C Safety Standards Directives Electrical Safety CB scheme TUV Bauart UL cUL BSMI EAC IEC 62368 1 IEC 60950 1 IEC 61010 1 2 201 E...

Page 5: ...ectrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 4 Criteria A1 Common Mode4 4 kV Differential Mode5 2 kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150 k...

Page 6: ...iagram DRL V480W1EN EMI Filter PFC Converter Inrush current limit Filter DC DC Converter Output Rectifier Filter Over Temperature Protection PWM Control Over Power Protection Photo Coupler Feedback Co...

Page 7: ...ons L x W x D 123 6 x 56 x 116 8 mm 4 87 x 1 57 x 4 60 inch Unless otherwise specified tolerance of dimension are 0 5 mm AWG Wire Table Current Rating for PVC Wire 6 AWG 52 5 A 8 AWG 37 5 A 10 AWG 29...

Page 8: ...e output capacity is not reduced when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air tem...

Page 9: ...l out the power supply unit PSU from the rail Safety Instructions Vertical Mounting ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit If mains ar...

Page 10: ...d for the output voltage to change from 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set...

Page 11: ...lso provides protection against short circuits When a short circuit is applied the output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit i...

Page 12: ...no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the produc...

Reviews: