Delta LYTE II DRL-24V480W1EN Manual Download Page 5

LYTE II DIN Rail Power Supply 

DRL-480W series / DRL-

V480W1EN

 

PRELIMINARY DATASHEET- For product review purpose only. The specs are subjected to change.

 

 

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (August 2021, Rev. X00) 

 

5

 

Model Number 

DRL-24V480W1EN

 

DRL-48V480W1EN 

 

EMC 

 

Emissions (CE & RE)

 

 

  CISPR 32, EN/BS 55032, EN/BS 61000-6-4, AS/NZS CISPR32, EN/BS EN/BS 61204-3, KN32 

Compliance to FCC Title 47, EN/BS 61000-6-3: Class B 

Component Power 

Supply for General Use 

 

EN/BS EN 61204-3 

Immunity 

  EN 55035, KN35, EN/BS 61000-6-2  

Compliance to EN/BS 61000-6-1 

Electrostatic 

Discharge 

IEC 61000-4-2  Level 4 Criteria A

1)

   

Air Discharge: 15k V 

Contact Discharge: 8 kV 

Radiated Field 

IEC 61000-4-3  Criteria A

1)  

 

80 MHz – 1 GHz, 10 V/M, 80% Modulation (1 kHz)  

1.4 GHz – 6 GHz, 3 V/M, 80% Modulation (1 kHz)  

2 GHz – 2.7 GHz, 1 V/M, 80% Modulation (1 kHz) 

Electrical Fast 

Transient / Burst 

IEC 61000-4-4  Level 3 Criteria A

1)

   

2 kV 

Surge 

IEC 61000-4-5  Level 4 Criteria A

1)

  

Common Mode

4)

: 4 kV 

Differential Mode

5)

: 2 kV  

Conducted 

IEC 61000-4-6  Level 3 Criteria A

1)

   

150 kHz – 80 MHz, 10 Vrms 

Power Frequency 

Magnetic Fields 

IEC 61000-4-8  Level 4 Criteria A

1)

   

30 A/m 

Voltage Dips and 

Interruptions 

IEC 61000-4-11  0% residual; 1 cycle, Criteria B

2)

 

40% residual; 10 cycle, Criteria C

3)

  

70% residual; 25 cycle, Criteria C

3)

 

Harmonic Current 

Emission 

 

IEC/EN/BS 61000-3-2, Class A 

Voltage Fluctuation and 

Flicker 

 

IEC/EN/BS 61000-3-3 

Voltage Sag Immunity 

SEMI F47 – 0706 

  80% of 200 Vac 

70% of 200 Vac 

50% of 200 Vac 

160 Vac, 1000 ms 

140 Vac, 500 ms 

100 Vac, 200 ms 

Criteria A

1)

 

Criteria A

1)

 

Criteria A

1)

 

1) Criteria A: Normal performance within the specification limits 

2) Criteria B: Temporary degradation or loss of function which is self-recoverable 

3)

 

Criteria C: Output out of regulation, shuts down during test (Need to recycle AC power cord to normal operation after test) 

4) Asymmetrical: Common mode (Line to earth) 

5) Symmetrical: Differential mode (Line to line)

 

 

Summary of Contents for LYTE II DRL-24V480W1EN

Page 1: ...applications without compromising on quality and reliability The convection cooled LYTE II series will operate between 30 C to 70 C with full rated power available from 30 C to 50 C at 230 Vac The ov...

Page 2: ...Vac Output Ratings Characteristics 2 Nominal Output Voltage 24 Vdc 48 Vdc Factory Set Point Tolerance 24 Vdc 1 48 Vdc 1 Output Voltage Adjustment Range 24 28 Vdc 48 55 Vdc Output Current 0 20 0 A 0 10...

Page 3: ...er De rating Temperature 40 C de rate power by 1 67 C 115 Vac 50 C de rate power by 2 5 C 230 Vac Input Voltage 100Vac de rate power by 1 Vac Operating Humidity 20 to 90 RH Non Condensing Operating Al...

Page 4: ...O P 100 load Ta 25 C Expected Cap Life Time 10 years 230 Vac 50 load 40 C Safety Standards Directives Electrical Safety CB scheme TUV Bauart UL cUL BSMI EAC IEC 62368 1 IEC 60950 1 IEC 61010 1 2 201 E...

Page 5: ...ectrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2 kV Surge IEC 61000 4 5 Level 4 Criteria A1 Common Mode4 4 kV Differential Mode5 2 kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150 k...

Page 6: ...iagram DRL V480W1EN EMI Filter PFC Converter Inrush current limit Filter DC DC Converter Output Rectifier Filter Over Temperature Protection PWM Control Over Power Protection Photo Coupler Feedback Co...

Page 7: ...ons L x W x D 123 6 x 56 x 116 8 mm 4 87 x 1 57 x 4 60 inch Unless otherwise specified tolerance of dimension are 0 5 mm AWG Wire Table Current Rating for PVC Wire 6 AWG 52 5 A 8 AWG 37 5 A 10 AWG 29...

Page 8: ...e output capacity is not reduced when the surrounding air temperature 50 C the device will run into Over Temperature Protection When activated power supply will latch off until the surrounding air tem...

Page 9: ...l out the power supply unit PSU from the rail Safety Instructions Vertical Mounting ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit If mains ar...

Page 10: ...d for the output voltage to change from 10 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set...

Page 11: ...lso provides protection against short circuits When a short circuit is applied the output current will operate in Hiccup mode The power supply will return to normal operation after the short circuit i...

Page 12: ...no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets Customer shall take its responsibility for evaluation of using the produc...

Reviews: