Delta LYTE DRL-24V480W1A Series Technical Data Sheet Download Page 2

TECHINCAL DATASHEET

 

LYTE DIN Rail Power Supply 

24V 480W 1 Phase / DRL-24V480W1A

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (December 2020, Rev. 05) 

 

2

 

Specifications 

Input Ratings / Characteristics 

 

Nominal Input Voltage 

100-240Vac 

Input Voltage Range 

85-264Vac  

Nominal Input Frequency 

50-60Hz 

Input Frequency  Range 

47-63Hz 

DC Input Voltage Range* 

120-375Vdc 

Input Current 

5.4A typ. @ 115Vac, 2.7A typ. @ 230Vac 

Efficiency at 100% Load 

85% typ. @ 115Vac, 88% typ. @ 230Vac 

Max Power Dissipation 

0% load 

 
 

5W @ 115Vac 

4W @ 230Vac 

  

 

100% load  50W @ 115Vac 

40W @ 230Vac 

Max Inrush Current (Cold Start) 

40A typ. @ 115Vac,  80A typ. @ 230Vac 

Power Factor at 100% Load 

> 0.95 @ 115Vac & 230Vac 

Leakage Current 

< 1mA @ 264Vac 

*Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.

 

 

 

Output Ratings / Characteristics** 

 

Nominal Output Voltage 

 

24Vdc 

Factory Set Point Tolerance 

 

24Vdc ± 2% 

Output Voltage Adjustment Range 

 

22-28Vdc 

Output Current 

 

20.0A (480W max.) 

Output Power 

 

480W 

Line Regulation 

 

< 0.5% (@ 85-264Vac, 100% load) 

Load Regulation 

 

< 1.5% (0-100% load) @ > -10°C to +70°C 

< 2.0% ( 0-100% load) @ 

≤ 

-10°C to -20°C 

PARD*** (20MHz) 

 

< 120mVpp @ 0°C to +70°C 

< 240mVpp @ < 0°C to -10°C 

< 360mVpp @ < -10°C to -20°C 

Rise Time 

 

100ms typ. @ nominal input (100% load) 

Start-up Time 

 

1,000ms typ. @ 115Vac & 230Vac (100% load

)

 

Hold-up Time 

 

10ms typ. @ 115Vac (100% load

)

 

16ms typ. @ 230Vac (100% load

)

 

Dynamic Response  

(Overshoot & Undershoot O/P Voltage) 

 

± 10% (2400mVpp) @ 85-264Vac input, 0-50% load, 50-100% 

load 

(Slew Rate: 0.1A/μ

s) 

Start-up with Capacitive Loads 

 

8,000µF Max 

Functional 

DC OK Relay Contact  30V / 1A 

The relay contact are normally “ON” (closed) when the output 

(Vout) is greater than 90% of its rated value. 

**For power de-rating from 40°C to 70°C @ 115Vac & 50°C to 70°C @ 230Vac, and Vin < 100Vac, see power de-rating on page 3. 

***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1μF ceramic capacitor & 47μF electrolytic cap

acitor. 

 

 

 

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Summary of Contents for LYTE DRL-24V480W1A Series

Page 1: ...strial applications without compromising on quality and reliability The convection cooled LYTE series will operate between 20 C to 70 C with full rated power available from 10 C to 50 C at 230Vac The...

Page 2: ...ltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage Adjustment Range 22 28Vdc Output Current 20 0A 480W max Output Power 480W Line Regulation 0 5 85 264Vac 100 load Load Regulation 1 5 0 10...

Page 3: ...ate power by 2 5 C 230Vac Input Voltage 100Vac de rate power by 1 Vac Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock Test Non Operating IEC 60068 2 2...

Page 4: ...EN 60950 1 Electrical Safety TUV Bauart EN 60950 1 EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E131881 UL 62368 1 and CSA C22 2 No 62368 1 File No E131881 CCC GB4943 1 CB...

Page 5: ...1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Level 4 Criteria A1 30A m Voltage Dips and Interruptions IEC 61000 4 11 0 of 100Vac 20ms 40 of 100Vac 200ms 70 of 100Vac 500ms 0 of...

Page 6: ...ified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com December 2020 Rev 05 6 Block Diagram DRL 24V480W1AA DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Do...

Page 7: ...connector 2 Output terminal block connector 3 DC OK relay contact for DRL 24V480W1AS only 4 DC voltage adjustment potentiometer 5 DC OK LED Green 6 Universal mounting rail system Dimensions L x W x D...

Page 8: ...otherwise indicated www DeltaPSU com December 2020 Rev 05 8 L x W x D 123 6 x 85 5 x 128 5 mm 4 87 x 3 37 x 5 06 inch DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Downloaded fro...

Page 9: ...to keep the device in working condition and require removal re application of input AC voltage in order to restart 3 In order for the device to function in the manner intended it is also necessary to...

Page 10: ...st the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then sli...

Page 11: ...ecome very hot depending on the surrounding air temperature and load of the power supply Risk of burns The main power must be turned off before connecting or disconnecting wires to the terminals DO NO...

Page 12: ...lue Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current wil...

Page 13: ...atch Mode The power supply s overvoltage circuit will be activated when its internal feedback circuit fails The output voltage shall not exceed its specifications as described in Protections section P...

Page 14: ...ote that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the load current and surroundi...

Page 15: ...aspects such as higher purchasing costs Frequently the user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specifi...

Reviews: