Delta LYTE DRL-24V480W1A Series Technical Data Sheet Download Page 1

TECHINCAL DATASHEET

 

LYTE DIN Rail Power Supply 

24V 480W 1 Phase / DRL-24V480W1A

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (December 2020, Rev. 05) 

 

1

 

 

 

Highlights & Features 

  Universal AC input voltage 

  Built-in constant current circuit for reactive loads 

  Up to 88.0% efficiency 

  Full power from -20°C to +50°C operation at 230Vac 

@ 5,000 meters or 16,400 feet altitude 

  Built-in DC OK relay contact option available 

  Compliance to SEMI F47 @ 200Vac  

  Conformal coating on PCBAs to protect against common 

dust and chemical pollutants 

 

 

Safety Standards 

 

CB Certified for worldwide use 

 

 

Model Number:

   

DRL-24V480W1A

 

Unit Weight:

 

 

1.30 kg (2.86 lb) 

Dimensions (L x W x D):

  123.6 x 85.5 x 128.5

 

mm

 

(4.87 x 3.37 x 5.06 inch) 

 

 

General Description 

Delta’s LYTE DIN rail power supply series is designed for cost sensitive users who need to fulfill essential features needed for many 

general industrial applications, without compromising on quality and reliability. The convection-cooled LYTE series will operate 

between -20°C to +70°C, with full rated power available from -10°C to +50°C at 230Vac. The overcurrent protection is designed to 

operate in constant current mode, which makes the LYTE series suitable for inductive and capacitive load applications. The product is 

certified according to safety standards IEC/EN/UL 60950-1

 

& IEC/EN/UL 62368-1 for Information Technology Equipment (ITE) and UL 

508 for Industrial Control Equipment (ICE). Electromagnetic radiated and conducted emissions are compliant to EN 55032, Class B; 

and, the product is RoHS compliant for

 

environmental protection. 

 

 

Model Information 

LYTE DIN Rail Power Supply 

 

Model  Number

 

Input Voltage Range

 

Rated Output  Voltage

 

Rated Output  Current

 

DRL-24V480W1A

 

85-264Vac (120-375Vdc) 

24Vdc 

20.0A 

 

 

Model Numbering 

DR

 

L –

 

24V

 

480W

 

1

 

A

 

 

DIN Rail 

Product Type 
L – LYTE Series 

Output Voltage  Output Power 

Single Phase  Delta 

Standard 

A – Without DC OK Contact 

S – With DC OK Relay Contact 

 

 

 

*This picture is for reference to DRL-24V480W series only.

 

Downloaded from

Arrow.com.

Summary of Contents for LYTE DRL-24V480W1A Series

Page 1: ...strial applications without compromising on quality and reliability The convection cooled LYTE series will operate between 20 C to 70 C with full rated power available from 10 C to 50 C at 230Vac The...

Page 2: ...ltage 24Vdc Factory Set Point Tolerance 24Vdc 2 Output Voltage Adjustment Range 22 28Vdc Output Current 20 0A 480W max Output Power 480W Line Regulation 0 5 85 264Vac 100 load Load Regulation 1 5 0 10...

Page 3: ...ate power by 2 5 C 230Vac Input Voltage 100Vac de rate power by 1 Vac Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 5 000 Meters 16 400 ft Shock Test Non Operating IEC 60068 2 2...

Page 4: ...EN 60950 1 Electrical Safety TUV Bauart EN 60950 1 EN 62368 1 UL cUL recognized UL 60950 1 and CSA C22 2 No 60950 1 File No E131881 UL 62368 1 and CSA C22 2 No 62368 1 File No E131881 CCC GB4943 1 CB...

Page 5: ...1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Level 4 Criteria A1 30A m Voltage Dips and Interruptions IEC 61000 4 11 0 of 100Vac 20ms 40 of 100Vac 200ms 70 of 100Vac 500ms 0 of...

Page 6: ...ified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com December 2020 Rev 05 6 Block Diagram DRL 24V480W1AA DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Do...

Page 7: ...connector 2 Output terminal block connector 3 DC OK relay contact for DRL 24V480W1AS only 4 DC voltage adjustment potentiometer 5 DC OK LED Green 6 Universal mounting rail system Dimensions L x W x D...

Page 8: ...otherwise indicated www DeltaPSU com December 2020 Rev 05 8 L x W x D 123 6 x 85 5 x 128 5 mm 4 87 x 3 37 x 5 06 inch DRL 24V480W1AS Downloaded from Arrow com Downloaded from Arrow com Downloaded fro...

Page 9: ...to keep the device in working condition and require removal re application of input AC voltage in order to restart 3 In order for the device to function in the manner intended it is also necessary to...

Page 10: ...st the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2 Dismounting To uninstall pull or slide down the latch with screw driver as shown in Fig 2 2 Then sli...

Page 11: ...ecome very hot depending on the surrounding air temperature and load of the power supply Risk of burns The main power must be turned off before connecting or disconnecting wires to the terminals DO NO...

Page 12: ...lue Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current wil...

Page 13: ...atch Mode The power supply s overvoltage circuit will be activated when its internal feedback circuit fails The output voltage shall not exceed its specifications as described in Protections section P...

Page 14: ...ote that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the load current and surroundi...

Page 15: ...aspects such as higher purchasing costs Frequently the user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specifi...

Reviews: