1-5. Configuration & Maintenance 

Make  sure  the  HEX  surface  sealed  with  mounting  flange  to  avoid  water 

penetrates  into  shelter  through  mounting  interface.  It  is  suggested  to  use  gaskets 

sticking on the mounting flange and seal the gap between flange and cabinet with 

silicone  gel  during  installation.  There  should  be 

NO

  any  gap  surround  gaskets  to 

avoid water penetrates into enclosure. 

 

 

 

 

       

 

In order to assure the HEX running at optimal condition, the condenser should 

be  cleaned  once  annually  at  least;  user  can  clean  the  condenser  with  flow  water 

directly. The external side fan blade can also be cleaned with normal pressure water 

if  there  is  dust  accumulation. 

Please  do  not  use  strong  water  jet  to  impact  the 

center of fan and the surface of condenser. 

 

The  bottom  hole  of  the  heat  exchangers  is  used  for  drainage,  please  clear 

drain holes when the maintenance. Please also notice that following: 

 

1. 

Check  wires  are  connected  correctly,  and  the  insulation  is  not  cracking  or 

broken. 

2.  Do not wipe the product with organic solvent, volatile substances like toluene or 

gasoline, it will destroy the powder-coated surface. 

3.  Turn off the power before maintaining. 

4.  Please turn off power and remove dry contact connector while non-operating for 

a long time. 

5.  If any abnormal acoustic noise from HEX happened, please turn off the product 

and contact with customer services. 

NO.  Q'TY 

DESCRIPTION 

Case Chassis 

Internal Case Cover 

Internal Fans 

Heat Exchanger 
(Evap/Cond) 

External Case Cover 

External Fans 

Controller 

Summary of Contents for HEX180PB

Page 1: ...PB Rev 00 Sample Date Code Sample Issue Date Mar 21 2018 Delta Electronics Inc 252 Shang Ying Road Kuei San District TEL 886 0 3 3591968 Taoyuan City 33341 Taiwan R O C FAX 886 0 3 3591991 Please send...

Page 2: ...ermal and Airflow 4 2 Electrical Specification 4 2 1 Indicator Connector 4 2 1 1 Power Supply Alarm Connector 4 2 1 2 Panel Operation 5 2 2 Fan Control Curve 5 3 Environmental Condition 6 3 1 Operatin...

Page 3: ...HEX unit and be sure to install it correctly After completing the installation make sure that the unit operates properly during the start up operation Meaning of WARNING and CAUTION notices Warning Fa...

Page 4: ...rained users in shops in light industry and on farms or for commercial use by lay persons Caution 1 Install the HEX on a wall door strong enough to withstand the weight of the unit 2 Do not allow a ch...

Page 5: ...Specification for Approval Customer Description Heat Exchanger Customer P N Rev Delta model no HEX180PB Rev 00 Sample revision Date Code Sample issue date Quantity INTERNAL EXTERNAL...

Page 6: ...ght Kg 25 0 Mounting Method N A Door Side Color optional N A RAL7035 Environmental Protection Performance Operating Temperature Range C 20 to 65 Refrigerant type and quantity N A R134a 350 10g Protect...

Page 7: ...Page 2 1 3 Dimension 1 Material steel sheet SGCC t 1 0mm 2 Finish Powder coating 75 m MIN Color RAL 7035 3 Dimensional Tolerance 1 0mm 0 04 1 4 Mounting Panel Cutout...

Page 8: ...ease do not use strong water jet to impact the center of fan and the surface of condenser The bottom hole of the heat exchangers is used for drainage please clear drain holes when the maintenance Plea...

Page 9: ...eparated mechanism design internal and external air flow won t be mixed since the waste heat can be dissipated from the cabinet to the ambience Internal temperature sensor is placed at return air stre...

Page 10: ...3 Pin 4 Pin 5 Pin 4 Control board NTC and fan are in normal status OPEN CLOSE Power off or control board is disabled CLOSE OPEN NTC resistance is over range such as open circuit or short circuit or O...

Page 11: ...expected to be at least 100 000 hours continuous operation at 35 C with 15 65 RH label rated voltage 4 Reliability Table Test item Condition High temperature IEC 60068 2 2 Low temperature IEC 60068 2...

Page 12: ...Notice Check the surrounding obstacles to make sure the product get enough space for air circulate Pin Description Cable wire size 1 48V 16 AWG 2 0V 16 AWG 3 Normal open 24 AWG 4 Common 24 AWG 5 Norm...

Page 13: ...and humidity range as indicated in the Delta product Specification s and product Instruction User Manual s Filters if applicable must be cleaned regularly Products and any parts thereof must not be mo...

Page 14: ...utside of the carton Delta Electronics Inc is not responsible for material damaged in transit Shipping cost for all non warranty repairs is the responsibility of the sender and must be shipped prepaid...

Reviews: