1-5. Configuration & Maintenance
Make sure the HEX surface sealed with mounting flange to avoid water
penetrates into shelter through mounting interface. It is suggested to use gaskets
sticking on the mounting flange and seal the gap between flange and cabinet with
silicone gel during installation. There should be
NO
any gap surround gaskets to
avoid water penetrates into enclosure.
In order to assure the HEX running at optimal condition, the condenser should
be cleaned once annually at least; user can clean the condenser with flow water
directly. The external side fan blade can also be cleaned with normal pressure water
if there is dust accumulation.
Please do not use strong water jet to impact the
center of fan and the surface of condenser.
The bottom hole of the heat exchangers is used for drainage, please clear
drain holes when the maintenance. Please also notice that following:
1.
Check wires are connected correctly, and the insulation is not cracking or
broken.
2. Do not wipe the product with organic solvent, volatile substances like toluene or
gasoline, it will destroy the powder-coated surface.
3. Turn off the power before maintaining.
4. Please turn off power and remove dry contact connector while non-operating for
a long time.
5. If any abnormal acoustic noise from HEX happened, please turn off the product
and contact with customer services.
NO. Q'TY
DESCRIPTION
1
1
Case Chassis
2
1
Internal Case Cover
3
2
Internal Fans
4
1
Heat Exchanger
(Evap/Cond)
5
1
External Case Cover
6
2
External Fans
7
1
Controller