![Delta DVPDT02-H2 Operation Manual Download Page 15](http://html1.mh-extra.com/html/delta/dvpdt02-h2/dvpdt02-h2_operation-manual_2471702015.webp)
DeviceNet Slave Communication Module DVPDT02-H2
DVP-PLC Operation Manual
13
9. Confirm the I/O data of DVPDT02-H2 node.
Item
Explanation
Default
Address
Node address of DVPDT02-H2 on DeviceNet network
N/A
Name
Name of the node
N/A
Vendor ID
799 is the vendor ID of Delta Electronics, Inc.
799
Device Type
Device type of DVPDT02-H2. 12 refers to communication adapter
12
Product Code Product code of DVPDT02-H2
83
Major Rev.
Major version of DVPDT02-H2's firmware
1
Nod
e
information
Min Rev.
Minor version of DVPDT02-H2’s firmware
1
Polled Setting
One of standard DeviceNet I/O transmission methods
Supported
Bit-Strobe Setting
One of standard DeviceNet I/O transmission methods.
DVPDT02-H2 does not support this.
N/A
COS/CC Setting
One of standard DeviceNet I/O transmission methods.
DVPDT02-H2 does not support this.
N/A
Input Size
Length of data transmitted from DVPDT02-H2 to DeviceNet master
32 bytes
Output Size
Length of data transmitted from DeviceNet master to DVPDT02-H2
32 bytes
10. Confirm all the settings are correct and click on “OK”.
Configuration of DVPDNET-SL
1. Double click on DNET Scanner (node 01), and the "Scan Module Configuration…” dialog box will appear.
You can find the currently available node, DVPDT02-H2, in the list. On the right hand side, there is an
empty “Scan List”.