TECHNICAL DATASHEET

 

CliQ DIN Rail Power Supply 

24V 480W 1 Phase / DRP024V480W1AA

 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (November 2020, Rev. 09) 

 

10

 

Functions 

 

Graph illustrating the Start-up Time, Rise Time, and Hold-up Time 

 

 

Start-up Time 

The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied. 

 

 

Rise Time 

The time required for the output voltage to change from 10% to 90% of its final steady state set value. 

 

 

Hold-up Time 

Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value. 

 

 

Inrush Current 

Inrush current is the peak, instantaneous, input current measured 

and, occurs when the input voltage is first applied. For AC input 

voltages, the maximum peak value of inrush current will occur 

during the first half cycle of the applied AC voltage. This peak value 

decreases exponentially during subsequent cycles of AC voltage. 

 

 

 

 

Dynamic Response 

The power supply output voltage will remains within ±5% of its 

steady state value, when subjected to a dynamic load from 0% to 

100% of its rated current. 

 

50% duty cycle / 5Hz to 1kHz 

 

 

 

 

 

 

Summary of Contents for DRP024V480W1AA

Page 1: ...lta Electronics Group The rugged metal is both shock and vibration resistant according to IEC 60068 2 standard The product operates within a wide temperature range from 20 C to 80 C The DRP024V480W1AA features universal AC input voltage range from 85Vac to 264Vac and the power will not de rate for the entire input voltage range The single phase power supply unit includes overvoltage overcurrent ov...

Page 2: ... 2 Output Voltage Adjustment Range 22 28Vdc Output Current 20 0A continuously operating at 24 30 0A Power Boost for 3 seconds at 24V refer to the details in the Functions section 40 0A Power Boost for 2 seconds at 24V refer to the details in the Functions section Output Power 480W continuously operating at 24V 720W Power Boost for 3 seconds at 24V refer to the details in the Functions section 960W...

Page 3: ...rtical Mounting 50 C de rate power by 2 5 C Operating Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 000 Meters 6 560 ft Shock Test Non Operating IEC 60068 2 27 30G 300m S for a duration of 18ms 3 times per direction 6 times in total Vibration Non Operating IEC 60068 2 6 10Hz to 150Hz 50m S 5G peak 90 min per axis for all X Y Z direction Over Voltage Category III According to IEC EN ...

Page 4: ... 60950 1 File No E191395 UL 62368 1 and CSA C22 2 No 62368 1 File No E191395 CB Scheme IEC 60950 1 IEC 62368 1 Industrial Control Equipment UL cUL listed UL 508 and CSA C22 2 No 107 1 01 File No E315355 CSA CSA C22 2 No 107 1 01 File No 181564 Hazardous Location ATEX cCSAus CSA C22 2 No 213 M1987 and ANSI ISA 12 12 01 2007 Class I Division 2 Group A B C D T4 Ta 20 C to 80 C 50 C derating ATEX EN 6...

Page 5: ...dulation 1kHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2kV Differential Mode3 1kV Conducted IEC 61000 4 6 Level 3 Criteria A1 150kHz 80MHz 10Vrms Power Frequency Magnetic Fields IEC 61000 4 8 Criteria A1 100A Meter Voltage Dips and Interruptions IEC 61000 4 11 100 dip 1 cycle 20ms Self Recoverable Low Energy Pulse Te...

Page 6: ...pecified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 09 6 Block Diagram Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiometer 4 DC OK control LED Green 5 Universal mounting rail system ...

Page 7: ...ication as defined on Page 3 under Environment the device may run into Over Temperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition 3 In order for the device to function in the manner intended it is also necessary to keep a ...

Page 8: ...ules Use appropriate copper cables designed to sustain operating temperature of at least 75 C or more to fulfill UL requirements For stranded wires it is recommended to use suitable lug to crimp wires Dismounting Fig 2 1 Mounting Snap on the DIN rail as shown in Fig 2 1 1 Tilt the unit upwards and insert it onto the DIN rail 2 Push downwards until stopped 3 Press against the bottom front side for ...

Page 9: ...ding air temperature and load of the power supply Risk of burns Only plug in and unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected Do not touch the unit during this time The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installati...

Page 10: ... 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is the peak instantaneous input current measured and occurs when the input voltage is first applied For AC input voltages the maximum peak value of inrush current will occur during the first half cycle of the...

Page 11: ...e unit is protected at the L pin with an internal fuse that cannot be replaced The power supply has been tested and approved on 20A UL and 16A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thus if an external protective device is necessary or utilized please refer a minimum value in...

Page 12: ...urrent will operate in Hiccup mode as shown in the illustration in the OLP OCP section on this page The power supply will return to normal operation after the short circuit is removed Overvoltage Protection Auto Recovery The power supply s overvoltage circuit will be activated when its internal feedback circuit fails The output voltage shall not exceed its specifications defined on Page 3 under Pr...

Page 13: ...tem load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the load current and surrounding air temperature The Signal GND in the DRR module is for the built in LED and DC OK signals The Output GND terminals from the two PSU s do not need to be connected to the ...

Page 14: ...earth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ can use on 2 of 3 phase system Please refer to the following step Step 1 The input voltage applied from Line to Neutral is below the maximum rated input The input voltage shall be below 240Vac 10 Step 2 The external protector is needed on N Neutral input...

Page 15: ... environment complying with EN 61000 3 2 is only necessary under special conditions Complying to this standard can have some technical drawbacks such as lower efficiency as well as some commercial aspects such as higher purchasing costs Frequently the user does not profit from fulfilling this standard therefore it is important to know whether it is mandatory to meet this standard for a specific ap...