5 4
Amplon RT Series
z
Battery
Setup Item
Selectable Value
Default Value
Automatic Battery Test
No test/ Daily/ Weekly/
Biweekly/ Monthly
No test
Deep Discharge Test
20-90% (one step: 10%)
90%
Low Battery
Warning Capacity
0-95%
(one step: 5%)
10%
Warning of
Remaining Time
0-60mins
(one step: 1min)
2mins
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240
(one step: 1min)
Disable
Charge Mode
2-stage/ 3-stage
2-stage
Float Charging
Voltage
Auto/ Customize
9FHOO
RQHVWHS9
Auto
Internal Charging
Current
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6
1A (5K/ 6K)
1.5A (8K/ 10K)
External Battery Type *
Standard battery pack/
Customer own batt. pack
External Battery
Capacity
Standard battery pack:
Part Number Quantity
Customer own batt. pack:
%DWWHU\9ROWDJH&DSDFLW\
Install date
YYYY/ MM/ DD
NOTE :
*
When the
External Battery Type
is set as
Standard battery pack
, you
need to configure the
Part Number
and the
Quantity
of the standard
battery pack(s).