You can choose the setup items such as
Output, Input
,
ECO Mode
,
On/ Off
Settings
,
Battery
,
General
,
Outlet Control
,
Dry Contact Setting
and
Component
Life Prediction
to set up relevant settings. For more information about the
Setting
Menu
, please refer to the tables below for each setup item’s relevant default value
and selectable value.
z
Output
Setup Items
Selectable Value
Default
Output Phase
1-phase
1-phase
Output Voltage
999
99
9IRUVXႈ[%PRGHO
9IRUVXႈ[PRGHO
Output Frequency
Auto* / Converter-50Hz** /
Converter-60Hz**
Auto
Output Sync.
Freq. Range
+]
+]
Output Freq.
Slew Rate
0.5/ 1/ 2/ 3/ 4 Hz/ sec.
1 Hz/sec.
Output Mode
Industrial/ IT
IT
Standby Mode
No output/ Bypass output
Bypass output
Overload Alarm
30-105% (one step: 5%)
105%
NOTE :
1. * When the
Output Frequency
is set as
Auto
, the output frequency
will vary according to the bypass frequency. If the bypass frequency
LV+]WKH
Free_Run_Frequency
/
Cold_Start_Frequency
will be
set as 60Hz.
If the bypass frequency is < 55Hz, the
Free_Run_Frequency
/
Cold_
Start_Frequency
will be set as 50Hz.
2. When the
Output Frequency
is set as
Auto
and the
Bypass Output
under the
Standby Mode
item is set as
Enable
, the bypass output
range will be the same as the
Output Sync. Freq. Range
.
3. ** When the
Output Frequency
is set as
Converter-50Hz
/
Converter-60Hz
, the UPS will enter into
Frequency Conversion
mode and the bypass output will become
Disable
.