Amplon MX Series
Step 2:
Press and hold the “Selection” button for 3 seconds
to enter Setting mode.
Step 3:
Press the “Up” button (ON/MUTE) to switch to “02”
of program list. Then press “Enter” button to enter
value setting of parameter 2. Press the “Up” button
to change the value to “ENA” to enable the pro-
grammable outlet function. Then press “Enter” but-
ton again to confirm the setting.
Step 4:
Press the “Up” button (ON/MUTE) again to switch
to “03” of program list. Then press “Enter” button for
setting programmable outlet time. Push “Up” button
to change the value of backup time according your
demand. Then press “Enter” to confirm the setting.
Step 5:
Press “Up” button (ON/MUTE) to switch to “00” of
program list. Then press “Enter” button to exit set-
ting menu.
Step 6:
Disconnect AC input and wait until the LCD display is off. The new setting will
be activated when turning on the UPS again.
3.6 Operating Mode Description
z
z
Normal mode
When the input voltage is within
voltage regulated range, UPS will
power the output directly from the
mains. In this mode, when battery
is fully charged, the fan will stop
working for energy saving.