3. INSTALLATION
3-1 Unpacking
Please read this user manual before installing the UPS.
This UPS contains batteries which are potentially hazardous to
user, even when the UPS is not connected to the utility power.
Before unpacking the UPS, check the packing box. If there are
any visible damage, contact your dealer at once.
-This unit is to operate by any individuals with previous training.
-This unit should be installed by service personnel.
3-2 Before Installation
Avoid exposing the UPS to direct sunlight or other heat source.
The UPS should be facing away from direct sunlight glare.
Choose a well-ventilated area to position your UPS to allow
adequate dissipation of heat.
Ensure the UPS surrounding area is clean and free from
moisture.
Do not put heavy objects on the cable or power cord.
3-3 Installation
Notice:
-
AC output need a disconnect device such as a breaker which has to be
provided by others.
-
The wire length of output power cord connected to the output receptacle
or pressure terminal should be less then 10 meters.
-
The UPS provide with pressure terminal connector for field installed wiring,
the terminal connector should be applied a 13.8 lb-in (1.554 N-m) of
tightening torque.
-
The over current protection and short circuit protection for the AC output
is provided by internal circuits of UPS and breaker.
-
Concerning about the battery voltage, ambient temperature and other
specifications of the UPS, please refer to the specification section of this
manual.
-
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away batteries.
-
When replacing batteries, replace with the same type and number.