HD45 / HD46
- 33 -
V2.4
Relay outputs
P#
DESCRIPTION
VALUE
DEFAULT NOTE
050
Hysteresis relay in HD45 and CO
2
relay in HD46
In HD45… models it is the hysteresis
when the rotary selector is in position 0
Value is in ppm if associated with CO
2
.
Value is x10 if associated with humidity
or temperature in HD45.
Over the whole range
100
( HD45 B,
HD46)
50
( HD45 17,
HD45 7B)
(3),(4)
051
Hysteresis (x10) temperature relay
in HD46
Over the whole range
50
(3),(4)
052
Hysteresis (x10) humidity relay in
HD46
Over the whole range
50
(3),(4)
053
Relay assignment in HD45…R
0
:
not assigned
1
:
CO
2
2
:
Temperature
3
:
Humidity
1
(HD45 B)
2
( HD45 17,
HD45 7B)
(5)
054
Lower threshold in ppm for LED
indicators in HD45
BVR and
HD45
BAR model
MIN:
400
MAX:
800
600
(5)
055
Medium threshold in ppm for LED
indicators in HD45
BVR and
HD45
BAR model
MIN:
500
MAX:
2000
800
(5)
056
Upper threshold in ppm for LED
indicators in HD45
BVR and
HD45
BAR model
MIN:
1000
MAX:
4000
1400
(5)
057
Threshold hysteresis in ppm for
LED indicators in HD45
BVR and
HD45
BAR model
MIN:
0
MAX:
100
20
(5)
062
Relay operating mode in HD45
models when rotary selector is in
position other than 0.
0
:
Active below threshold
1
:
Active over threshold
1
(5)
063
Relay simplified mode activation in
HD46 models
0
: Dis
able simplified mode
1
:
Enable simplified mode
0
064
CO
2
relay operating mode in HD46
with simplified mode enabled.
0
:
Active below threshold
1
:
Active over threshold
1
065
Temperature relay operating mode in
HD46 with simplified mode enabled.
0
:
Active below threshold
1
:
Active over threshold
1
066
Humidity relay operating mode in
HD46 with simplified mode
enabled.
0
:
Active below threshold
1
:
Active over threshold
1
082
Rotary selector threshold in
position 1 when the relay is
associated with humidity or
temperature measure (x10)
Over the whole range
180
(4),(5)
083
Rotary selector increment for
positions 2…9 when the relay is
associated with humidity or
temperature measure (x10)
Over the whole range
50
(4),(5)
084
Relay hysteresis when rotary
selector is in position other than 0
(x10 if related to humidity or
temperature)
Over the whole range
100
(HD45 B)
50
( HD45 17,
HD45 7B)
(4),(5)