Quick installation guide for RPI H3 inverters

General Safety Instructions

1

DANGER

Risk of death by electrocution

Potentially fatal voltage is applied to the solar 
inverter during operation. This potentially fatal 
voltage is still present for 15 seconds after all 
power sources have been disconnected.

 

Ź

Never open the solar inverter. 

 

Ź

Always disconnect the solar inverter from 
power before installation, open the DC 
disconnection switch and make sure neither 
can be accidentally reconnected.

 

Ź

Wait at least 60 seconds until the capacitors 
have discharged.

DANGER

Risk of death or serious injury from elec-
trocution

Potentially fatal voltage may be applied to the 
DC connections of the solar inverter. When light 
is falling on solar modules, they immediately start 
producing energy. They do so, even when the 
sun is not shining.

 

Ź

Never disconnect the solar modules when the 
solar inverter is powered. 

 

Ź

First switch off the grid connection so that 
the solar inverter cannot feed energy into the 
grid. 

 

Ź

Turn the DC disconnection switch to position 

OFF

.

 

Ź

Make sure the DC connections cannot be 
accidentally touched.

 

Ɣ

Read this quick installation guide 

before

 you start installing 

the inverter.

 

Ɣ

The solar inverter can be safely and normally operated if 
installed and used in accordance with this manual (see 
IEC 62109-5.3.3). Delta Energy Systems is not responsible 
for damage incurred by failure to observe the installation and 
commissioning instructions in this manual. For this reason, 
be sure to observe and follow all instructions!

 

Ɣ

Installation and commissioning may only be performed by 

TXDOL¿HGHOHFWULFLDQVXVLQJWKHLQVWDOODWLRQDQGFRPPLVVLRQ

-

ing instructions found in this manual.

 

Ɣ

The solar inverter must be disconnected from power and the 
solar modules before any work on it can be performed.

 

Ɣ

The solar inverter has a high leakage current value. The 
ground wire 

must

 be connected before commissioning.

 

Ɣ

Do not remove any warning signs that the manufacturer has 
installed on the solar inverter.

 

Ɣ

Improper handling of the solar inverter may result in physical 
injury and damage to property. For this reason, observe and 
follow all general safety instructions and warnings.

 

Ɣ

The solar inverter contains no components that must be 
maintained or repaired by the operator or installer. All repairs 
must be performed by Delta Energy Systems. Opening the 
cover will void the warranty.

 

Ɣ

Do not disconnect any cables when the solar inverter is pow-
ered due to risk of a fault arc.

 

Ɣ

To prevent lightning strikes, follow the relevant regulations 
applicable in your country.

 

Ɣ

The surface of the solar inverter can become very hot dur-
ing operation. Use safety gloves when working on the solar 
inverter.

 

Ɣ

Only devices in compliance with SELV (EN 69050) may be 
connected to the RS485 interfaces.

 

Ɣ

$OOFRQQHFWLRQVPXVWEHVXI¿FLHQWO\LQVXODWHGLQRUGHUWRFRP

-

ply with the IP65 protection rating. Unused connections must 
be closed by placing cover caps on the solar inverter.

RPI_H3_QIG_V1.0_EU_EN_2015-05-11.indd   3

15.05.15   11:31

Summary of Contents for RPI H3_110

Page 1: ...Quick Installation Guide RPI H3_110 United Kingdom Europe RPI_H3_QIG_V1 0_EU_EN_2015 05 11 indd 1 15 05 15 11 31 ...

Page 2: ...f you experience deviations between the descriptions in this quick installation guide and the information on the inverter dis play please check www solar inverter com for a quick installation JXLGH WKDW PDWFKHV WKH UPZDUH YHUVLRQ RQ WKH LQYHUWHU 7KH standard manual can also be downloaded from www solar inverter com Delta Energy Systems Germany GmbH Tscheulinstrasse 21 79331 Teningen Germany Table ...

Page 3: ...installation and commissioning instructions in this manual For this reason be sure to observe and follow all instructions Ɣ Installation and commissioning may only be performed by TXDOL HG HOHFWULFLDQV XVLQJ WKH LQVWDOODWLRQ DQG FRPPLVVLRQ ing instructions found in this manual Ɣ The solar inverter must be disconnected from power and the solar modules before any work on it can be performed Ɣ The so...

Page 4: ... Indicates an error fault or warning Buttons SEL Select Move to the next menu entry Change a value Cancel value setting ENT Enter 6HOHFW PHQX LWHP 2SHQ FRQ JXUDEOH YDOXH IRU HGLWLQJ Finish editing adopt set value Display buttons LEDs Type label Electrical connectors DC switch DC Inputs AC Connector RS485 Digital inputs and dry contacts RPI_H3_QIG_V1 0_EU_EN_2015 05 11 indd 4 15 05 15 11 31 ...

Page 5: ...rter before working with the solar inverter and follow the instructions contained in the manual The housing of the inverter must be grounded if this is required by local regulations Regulatory Compliance Mark RCM mark The inverter is compliant with the Australian Electrical Safety and EMC standards Applies only to Australia and New Zealand Information on the type label 3 Scope of delivery 4 AC Plu...

Page 6: ...of against direct sun rain or snow Ź Mount the solar inverter vertically Where to mount the inverter ᅛ ᅟ ᅟ Ź Mount the solar inverter so that the LEDs and display can be easily seen and that the buttons can be operated Make sure the reading angle and instal ODWLRQ KHLJKW DUH VXI FLHQW Ź Always use the mounting plate supplied with the inverter Ź Check that the wall is capable of bearing the heavy w...

Page 7: ...ng plate Ź Check that the rail of the inverter hangs correctly in the mounting plate and screw the inverter to the mounting plate Ź Fasten the mounting plate with 6 M5 screws to the wall 1 2 3 4 Ź Ground the inverter housing Washer spring Washer M4 Screw Grounding cable Toothed ring RPI_H3_QIG_V1 0_EU_EN_2015 05 11 indd 7 15 05 15 11 31 ...

Page 8: ...cu tion Ź Set the DC disconnection switch to position OFF before connecting or disconnecting the AC plug AC connector The AC plug is included in the delivery box 2 N 1 L PE Wiring the AC connector 1 phase L N PE Use wire end sleeves on each wire 12 mm 52 5 mm 12 mm 55 mm PE RPI_H3_QIG_V1 0_EU_EN_2015 05 11 indd 8 15 05 15 11 31 ...

Page 9: ... the tripping current mainly depends on the installation of the PV generator the size of the PV array and environmental conditions e g humidity Important information regarding safety AC cable requirements Use properly sized wires see table AC plug Wieland RST25i3S S1AZR2V BG03 96 032 4154 3 Current rating Min max cable diameter 10 14 mm Min Max wire diameter 0 75 4 mm2 Recommended torque for termi...

Page 10: ... 4 6 3 6 32 0015P0001 UR 5 5 9 32 0017P0001 UR a b DANGER Risk of death or serious injury from electrocution Potentially fatal voltage may be applied to the DC connections of the solar inverter When light is falling on solar modules they immediately start pro ducing energy They do so even when the sun is not shining directly onto the solar modules Ź Turn the DC disconnection switch to position OFF...

Page 11: ...om the connection ports Water could leak into the inverter Ź The terminal blocks inside are not easily accessible Connector for digital inputs and dry contacts 2 1 Pos Designation 1 Dry contacts 2 Digital inputs and outputs Digital inputs 6 5 4 3 2 1 Pin Designation 1 Digital input 1 DI1 2 Digital input 2 DI2 3 Digital input 3 DI3 4 Digital input 4 DI4 5 Output 1 O1 6 Output 1 O2 Dry contacts When...

Page 12: ...or RS485 termination resistor RS485 is used to connect the inverters of the PV plant via a data logger to a monitoring system VCC can be used for an external relais For connecting RS485 Pins 3 to 6 are used If you want to use SOLIVIA Monitor the Internet based monitor ing from Delta you will also need a SOLIVIA M1 G2 Gateway Default baud rate is 19200 which can be changed on the inverter see chapt...

Page 13: ...n the inverter you connect single wires on the gateway you have to use a RJ45 plug Connect inverter and gateway according to following table Inverter SOLIVIA Gateway M1 G2 Data Terminal 3 or 5 TX_A Pin 7 Data Terminal 4 or 6 RX_B Pin 6 or 8 Connecting the inverter to a SOLIVIA Gateway M1 G2 Pin Assignment 1 8 1 Reserved 2 Reserved 3 Reserved 4 GND 5 Reserved 6 RX_B 7 TX_A 8 RX_B Pin assignment of ...

Page 14: ... LV VKRZQ 3 0 kVA Inverter Setting the inverter ID If your PV plant contains multiple inverters for each of the inverters a different inverter ID has to be set The inverter ID is needed to identify each inverter via RS485 For a description of the RS485 connection see Connecting to a datalogger via RS485 optional p 12 ID 1 Inverter 1 In the main menu use the button SEL to select Inverter ID 2 Press...

Page 15: ...Shut down Inverter 19200 Baud rate 3 Use the button SEL to select Baud rate and press the button ENT Next Enter 9600 4 Use the button SEL to select another baud rate To accept the selection press the button ENT N Y 9600 5 7R FRQ UP RXU VHOHFWLRQ SUHVV WKH EXWWRQ ENT ĺ The new baud rate is shown 9600 Baud rate N Y Exit 6 Use the button SEL to select Exit and press the button ENT WR QLVK Commissioni...

Page 16: ...to select the entry with time and date To change the setting press the button ENT ĺ 7KH GD LV ÀDVKLQJ 14 05 26 11 2014 11 2014 14 05 4 Use the button SEL to change the value 7R FRQ UP RXU VHWWLQJ SUHVV WKH EXWWRQ ENT ĺ 7KH PRQWK LV ÀDVKLQJ 14 05 26 11 2014 26 2014 14 05 5 Repeat step 3 and 4 for each value ĺ IWHU FKDQJLQJ WKH YDOXH IRU WKH PLQXWHV WKH ÀDVKLQJ VWRSV N Y Exit 6 Use the button SEL to...

Page 17: ...displayed Shut down Inverter English Language 3 Use the button SEL to select Language and press the button ENT Next Enter Deutsch 4 Use the button SEL to select another language To accept the selection press the button ENT N Y Deutsch 5 7R QDOO FRQ UP RXU VHOHFWLRQ SUHVV WKH EXWWRQ ENT ĺ The new language is used Deutsch Die Sprache Nein Ja Beenden 6 Use the button SEL to select Beenden and press t...

Page 18: ...ic isolation No Overvoltage category 2 II Output AC RPI H3 Maximum apparent power 3000 VA Nominal apparent power 3000 VA Voltage range 3 230 V 20 22 1 phase L N PE or L L PE Nominal current 13 A Maximum current 14 3 A Inrush current 30 A 1 ms Maximum output fault current 16 A Nominal frequency 50 60 Hz Frequency range 3 50 5 Hz 60 5 Hz Power factor adjustable 0 8 cap 0 8 ind Total harmonic distort...

Page 19: ...FLHQF 96 2 Operating temperature range 25 60 C Operating temperature range without derating 25 40 C Storage temperature range 25 60 C Relative humidity 0 95 non condensing Maximum operating altitude 2000 m above sea level Standards and Directives RPI H3 Protection degree IP65 Safety class I Pollution degree II Overload behavior Current limitation power limitation Safety IEC 62109 1 2 CE compliance...

Page 20: ...rter com 49 7641 455 549 Israel supporto israel solar inverter com 800 787 920 free call Italy supporto italia solar inverter com 800 787 920 free call Netherlands ondersteuning nederland solar inverter com 0800 022 1104 free call Poland support poland solar inverter com 48 22 335 26 00 Portugal suporte portugal solar inverter com 49 7641 455 549 Slovakia podpora slovensko solar inverter com 0800 ...

Reviews: