Delta Elektronika SM 120-25 D Manual Download Page 9

DELTA ELEKTRONIKA BV

SM3000

Page 3 - 6

DESCRIPTIONS

1991, rev. May 2008

26)

SERIES OP ER A TION

Series op eration is al lowed up to 600 V total voltage. The power sup plies
can be con nected in se ries without spe cial pre cautions.
For eas ier con trol, Mas ter / Slave op eration is recommended (see fig. 3 -
20). By us ing the Mas ter / Slave Se ries fea ture a 

dual tracking

 power sup -

ply can be made with one unit as master and one as slave.
For se ries op eration in combination with Power Sink op tion, all units must
have a Power Sink built in side oth erwise no power can be ab sorbed.

27)

PAR AL LEL OP ER A TION

Paralleling of the units has no limitations. The power supplies can be con -
nected in par allel with out spe cial pre cautions. For eas ier con trol, Mas ter /
Slave op eration is recommended  (see fig. 3 - 20 and fig. 3 - 21).
Nor mal par al lel op er a tion of

Fast Pro gram ming

 units can give prob lems,

each com bination has to be tested first, in com bination with the load ! 
For par al lel op er a tion in com bi na tion with

Power Sink

 op tion, only one unit

can have a Power Sink. Re fer to Power Sink man ual for de tails and restric-
tions.

28)

MASTER / SLAVE OP ERATION

The Mas ter / Slave fea ture makes it pos sible to use the power sup plies as
building blocks to form one large unit (see fig. 3 - 21).
The re sulting com bination of units be haves like one power sup ply and can
be pro grammed on the mas ter. Fig ure 3 - 23 shows a computer con trolled
M/S par al lel com bi na tion.
Mixed par allel - se ries op eration is also pos sible (see fig. 3 - 22), to a max i-
mum of 600 V. Here the

MASTER / SLAVE SE RIES ADAPTER

(

δ

-prod uct)

must be used. For par allel op eration con nections can easily be made on
the an a log pro gram ming con nec tor.
In se ries mode the mas ter con trols one slave, which in turn con trols the
second slave and so on. In par allel mode the master con trols all the slaves.
The re sult is true 

current or voltage sharing

 in the par allel or se ries mode

re spec tively.

Note: Master / Slave parallel op eration is not recommended for more
than 3 units or in combination with Fast Pro gramming op tion.
Consult factory for a so lution.

29)

RE MOTE SENSING

The voltage at the load can be kept con stant by re mote sensing. This fea -
ture is not rec ommended for normal use but only when the load voltage is
not al lowed to vary a few millivolts. Al ways use a 

shielded ca ble

 for sens-

ing.
In or der to compensate for the voltage drop across the load leads, the unit
will have to supply a higher voltage: U

out

= (voltage drop across each lead)

+ (voltage across the load) (see fig. 3 - 24). The

OVP

 reads the voltage di -

rectly at the output and the setting must be in creased by the to tal voltage
drop across the load leads.
The voltmeter is connected to the sense leads and there fore reads the volt-
age across the load and 

not

 the voltage on the out put terminals.

The sense leads are pro tected for 

ac ci den tal in ter rup tion

, in which case

the out put voltage will go to a max. of 115% of the set value.

Warn ing:

 Do not in terrupt the mi nus lead while the S– lead is still con -

nected to the load, during op eration.
For sensing on a 

pul sat ing load

, see pre vious paragraph 17).

30)

OVP

The Over Volt age Pro tector will protect your circuit from un wanted high
volt ages.
A high out put voltage could be caused by accidental in terruption of leads,
ac ci den tally turn ing up the volt age potmeter or a de fect in the power sup-
ply. The OVP cir cuit uses a sep arate voltage di vider con nected di rectly to
the out put ter mi nals.
The OVP lim its the out put voltage to a value which can be set by the OVP
potmeter on the front panel. While do ing this, press the DIS PLAY OVP
SETTING button to read the limit value in the left dis play. The led on the
front panel will in dicate whether the OVP has reached the limit. The OVP
status output will give a logic 1 (+5 V).

Note: The Ther mal ShutDown and Re mote ShutDown will also cause the
OVP-led to burn and the OVP-status will be high.

fig. 3 - 20

Master / Slave ser ies operation

fig. 3 - 21

Master / Slave parallel operation

fig. 3 - 22

Master / Slave mixed series-parallel

fig. 3 - 23

The Master / Slave combination can also

be pro grammed with the interfaces

PSC-488 or the PSC-232

Summary of Contents for SM 120-25 D

Page 1: ...5 200D SM 30 100D SM 45 70D SM 70 45D SM 120 25D SM 300 10D SM 3000 series Elso Philips Service Jilemnick ho 2 911 01 Tren n tel 421 32 6582410 7431690 fax 421 32 6582592 email elso elso sk web www el...

Page 2: ...he protective earth terminal must be connected to the safety electrical ground before another connection is made Any interruption of the protective ground conductor or disconnection of the protective...

Page 3: ...l Shock Instruction manual symbol The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual Protective ground conductor terminal o Off supply...

Page 4: ...r cuit 2 INPUT VOLTAGE The power supplies have a wide input volt age range The units need a 3 phase input voltage but no neutral connection is required The units can also operate on one phase but at 9...

Page 5: ...lways use a shielded ca ble for programming The inputs have a protection circuit formed by a series resistor and a parallel zener see fig 3 7 The capacitor limits the speed to a safe value Note that t...

Page 6: ...h 13 PROGRAMMING SPEED The response time is measured with a step waveform at the CV prog input Programming from a low to a high output voltage is nearly load independent but programming down to a low...

Page 7: ...gh energy pulse of about 300 V If there is an electrical connection between the output and the input through the oscilloscope you will get a false reading The suppression for the SM120 25D is lower bu...

Page 8: ...tch shuts down the output in case of insufficient cooling After cooling down the unit will start working again The thermal protection circuit protects 2 parts separately in the unit the switching tran...

Page 9: ...ecommended for more than 3 units or in combination with Fast Programming option Consult factory for a solution 29 REMOTE SENSING The voltage at the load can be kept constant by remote sensing This fea...

Page 10: ...re and full load the fan will run at a very low speed The fan does not operate on no load Normally at 50 C ambient and full load the fan will not work at full speed Since the fan is over rated it will...

Page 11: ...TER circuit so no large inrush cur rent will flow As soon as the voltage is sufficiently high the power supply starts working and the series resistor is bypassed by a relay contact The operating switc...

Page 12: ...recom mended to set the OVP on 24 3 27 V Check that the cooling of the unit is not obstructed 2 ANALOG PROGRAMMING Put the appropriate switch es in the position PROGRAM Connect the programming voltage...

Page 13: ...put terminals so the OVP setting should be increased by the total voltage drop in the load leads 7 BATTERY CHARGER The CV CC regulated power supplies are ideal battery charg ers Once the output is set...

Page 14: ...ecommended for more than 4 units consult factory for using more than 4 power supplies in parallel First connect output terminals and test system in normal paral lel operation Ensure that all power con...

Page 15: ...PERATION For complex combinations as mixed series parallel always use the MASTER SLAVE SERIES ADAPTER product See fig 4 14 for an example of how to connect 2 units in se ries in parallel with 2 units...

Page 16: ...supply to dry before switching it on again 3 GALVANIC INDUSTRY For using the power supplies in the galvanic industry it is strongly recommended to take precautions against an aggressive environ ment...

Page 17: ...current is flowing through pin 1 of the prog connector Please check why current is flowing through pin 1 see also next paragraph 4 and fig 4 17 4 PROGRAMMING OFFSETS Unwanted offsets in the programmi...

Page 18: ...not try to re pair P430 except for D400 D401 F400 and F401 but send P430 for repair or ask for replacement 10 CHECK POINTS IN CASE OF A SERIOUS FAILURE Check output diodes Defective diodes give a sho...

Page 19: ...put with exactly 5 00 V Set output voltage to a low value en suring the power supply is in CC mode Measure the output current with an ac curate shunt Calibrate the current with R686 exactly on the rat...

Page 20: ...l Journal of the European Communities EN 61204 3 EMC low voltage power supplies EN 61000 6 3 Generic Emissions residential light industrial EN 55022 Radiated and conducted Class B EN 61000 3 3 Voltage...

Reviews: