DVP04TC-S

 

Thermocouple Sensors 

Instruction Sheet

 

 

 

WARNING 

  Always read this instruction thoroughly before using the DVP04TC-S. 

  Make sure that power is OFF before wiring.   

  This is an OPEN TYPE PLC.    The PLC should be kept in an enclosure away from airborne dust, 

humidity, electric shock risk and vibration.    Also, it is equipped with protective methods such as 
some special tools or keys to open the enclosure, in order to prevent hazard to users or damage 
the PLC.   

  Do NOT connect the AC main circuit power supply to any of the input/output terminals, or it may 

damage the PLC.    Check all the wiring prior to power up. 

    Do NOT touch internal circuit within 1 minute after power is OFF. 

    Make sure that the DVP04TC-S is properly grounded 

, to avoid any electromagnetic noise. 

2  

INTRODUCTION 

2.1  Model Explanation and Peripherals 

 

Thank you for choosing DELTA’s DVP Series PLC.  The DVP04TC-S allows the connection of 
four thermocouple sensors (Type J/K).    The DVP04TC-S series can read/write the data by using 
instructions FROM / TO via DVP-PLC SS/SA/SX/SC MPU program.    There are 49 CR (Control 
Register) in each module and 16 bits for each register.   

 

DVP04TC-S thermocouple sensor can update software version by RS-485.    Power supply and 
main processing units are sold separately.   

 

The DVP04TC-S works with both Centigrade and Fahrenheit.  The input resolution for 
Centigrade is 0.1 degrees and for Fahrenheit is 0.18 degrees. 

 

Nameplate Explanation 

P L C  m o d e l

Input power Supply Spec.

Analog Input /Output Module Spec.

Barcode, series and version

MODEL  

POWER  INPUT 

THERMOCOUPLES

04 TC -S0 T50 200 01

VX.X

24Vdc  2W 

MADE  I N  XXXXX X

RESOLUTION

14 BITS

TYPE J , K

 

 

Model Explanation

 

Serial Number

Model

S: for SS/SA series MPU

XA: Analog input/output  mixed  module

Product Series
Input + Output points 

Model type

AD: Analog input module

DA: Analog output module

PT: Platinum temperature sensors (PT-100) 

TC: Thermocouple sensors (Type J/K)

Production series
Production week

Production year (2005)
Production place (Taoyuan)
Serial number of version

Production Model

RT: Resistor Thermocouple(NTC)

 

2.2  Product Profile and Outline 

90.00

4.00

3.00

25.20

1

2

3

4

60.00

5

6

7

8

9

3

10

L+
L-
SLD

C

H

1

C

H

2

C
H

3

C

H

4

11

12

13

3.4

90.00

60.00

3.00

14

L+
L-

L+
L-

L+
L-

SLD

SLD

SLD

 

Unit: mm

 

1. Status indicator (Power, RUN and ERROR) 

8. Extension port 

2. Model Number 

9. Extension Clip 

3. DIN rail clip 

10. DIN rail location (35mm) 

4. I/O terminals 

11. RS-485 Communication port 

5. I/O point indicator 

12. Extension Clip 

6. Extension hole of the extension unit mounting 

pins 

13. DC Power input 

7. Specification Label 14. 

Extension 

port 

 

2.3 External 

wiring 

CH1

CH4

DC/ DC

5V

AG

+15V

-15V

AG

24+
24-

SLD

L-

L+

SLD

L-

L+

Converter

System

Class 3 Grounding

(100    of less)

terminal of

power module

Shielded*1

*2

*3

Shielded*1

Grounding

Thermocouple

+

-

100

MUX

Cold-junction

Compensation

Thermocouple

+

-

Note 1: Use only the wires that are 

supplied with your 
thermocouple sensor.  Tighten 
PLC terminal screws to a 
torque of 1.95 kg-cm (1.7 
in-lbs). 

Note 2: Terminal SLD is a grounding 

location for noise suppression. 

Note 3: Please connect 

 terminal of 

power supply module and 

 

terminal of DVP04TC-S 
thermocouple sensors module 
to system earth ground. 

Warning: DO NOT connect wires to the 

No Connection ( ) terminals.
Use copper conductor only, 
60

 

2.4    Terminals of analog module 

DVP04AD-S 

DVP02DA-S

DVP04DA-S

DVP04PT-S

DVP04TC-S

DVP06XA-S

DVP08RT-S

V+

I+

COM

FG

V+

I+

COM

FG

I+

COM

FG

V+

I+

COM

FG

V+

 

V+

I+

COM

FG

V+

I+

COM

FG

 

V+

I+

COM

FG

V+

I+

COM

FG

I+

COM

FG

V+

I+

COM

FG

V+

 

L+

L-

FG

FG

I-

L+

L-

I-

L+

L-

FG

FG

I-

L+

L-

I-

 

L+

L-

SLG

L+

L-

SLG

L+

L-

SLG

L+

L-

SLG

 

V+

I+

COM

V+

I+

COM

I+

COM

V+

I+

COM

V+

V+

I+

COM

V+

I+

COM

 

L+

L-

L-

L-

L+

L+

L-

L+

L+

L-

L-

L-

L+

L+

L-

L+

 

 

3  

STANDARD 

SPECIFICATIONS 

3.1 Function 

Specifications 

Platinum Temperature Module (04TC)

Centigrade (

°

C) 

Fahrenheit

 (

°

F) 

Power Supply Voltage 

24 VDC(20.4VDC~28.8VDC) ( –15%~+20%) 

Analog Input Channel 

4 channels per module 

Sensors Type 

J-type or K-type thermocouple 

Temperature Input Range 

J-type: -100

°

C~700

°

K-type: -100

°

C~1000

°

J-type: -148

°

F~1292

°

K-type: -148

°

F~1832

°

Digital Conversion Range 

J-type: K-1000~K7000 
K-type: K-1000~K10000 

J-type: K-3280~K12920 
K-type: K-1480~K18320 

Resolution 

14 bits(0.1

°

C) 14 

bits(0.18

°

F) 

Overall Accuracy 

±

0.5% of full scale of 25

°

C(77

°

F), 

±

1% of full scale during 0~55

°

(32~131

°

F) 

Response Time 

250 ms 

×

 channels 

Isolation Method 

Isolation between digital and analog circuitry. There is no isolation between 
channels. 

Digital Data Format 

2’s complement of 16-bit, (13 Significant Bits) 

Average Function 

Yes (CR#2~CR#5 may be set and the range is K1~K4096) 

Self Diagnostic Function 

Yes 

Communication Mode (RS-485) 

MODBUS ASCII/RTU Mode. Communication baud rate of 4800 / 9600 / 
19200 / 38400 / 57600 / 115200. For ASCII mode, date format is 7Bits, 
even, 1 stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop 
bit (8 E 1). The RS-485 is disabled when the DVP04TC-S is connected in 
series to an MPU. 

Connection to a DVP-PLC MPU in 
Series 

When DVP04TC-S modules are connected to an MPU, the modules are 
numbered from 0 – 7. 0 is the closest to the MPU and 7 is the farthest. The 
Maximum number of modules is 8 modules and they do not occupy any 
digital I/O points of the MPU. 

3.2 Other 

Specification 

Power Specification 

Maximum Power Consumption 

2W at 24 VDC (20.4VDC~28.8VDC) ( -15 % ~ +20 %) 

 

Environment Condition 

Environment Condition 

Follow the DVP-PLC MPU. 

Static Electricity Prevention 

All places between terminals and ground comply with the spec. 

 

4

CR (Controlled Register) 

 

DVP04TC-S platinum temperature sensors 

Explanation 

CR
No.

RS-485 

Parameter 

address

Latched Register 

name b15 

b14 

b13 

b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

#0

H 4096

 

Model type 

System used, DVP04TC-S model code = H 8B 

Reserved CH4 CH3 CH2 CH1 

#1

H 4097

  R/W Thermocouple 

type 

Example: Setting of CH1 
1.  b0: set 0 to use J-type and set 1 to use K-type 
2. b1: Reserved. 
3. b2: Reserved. 

#2

H 4098

  R/W  CH1 average number 

#3

H 4099

  R/W  CH2 average number 

#4

H 409A

  R/W  CH3 average number 

#5

H 409B

  R/W  CH4 average number 

The number of readings used for “average” temperature on channels CH1~CH4.   
Setting range is K1~K4096 and factory setting is K10. 

#6

H 409C

 

CH1 average degrees(

°

C) 

#7

H 409D

 

CH2 average degrees(

°

C) 

#8

H 409E

 

CH3 average degrees(

°

C) 

#9

H 409F

 

CH4 average degrees(

°

C) 

Average degrees for channels CH1~CH4.    (unit: 0.1 degrees C) 

#10

H 40A2

 

CH1 average degrees(

°

F) 

#11

H 40A3

 

CH2 average degrees(

°

F) 

#12

H 40A4

 

CH3 average degrees(

°

F) 

#13

H 40A5

 

CH4 average degrees(

°

F) 

Average degrees for channels CH1~CH4.    (unit: 0.1 degrees F) 

#14

H 40A8

 

Present temperature of 
CH1 (

°

C) 

#15

H 40A9

 

Present temperature of 
CH2 (

°

C) 

#16

H 40AA

 

Present temperature of 
CH3 (

°

C) 

#17

H 40AB

 

Present temperature of 
CH4 (

°

C) 

Present temperature of channels CH1~CH4. (unit: 0.1 degrees C) 

#18 Reserved 

#19

H 40AE

 

Present temperature of 
CH1 (

°

F) 

#20

H 40AF

 

Present temperature of 
CH2 (

°

F) 

#21

H 40B0

 

Present temperature of 
CH3 (

°

F) 

#22

H 40B1

 

Present temperature of 
CH4 (

°

F) 

Present temperature of channels CH1~CH4. (unit: 0.1degrees F) 

#23 Reserved 
#24

H 40AE

 

CH1 OFFSET Value 

#25

H 40AF

 

CH2 OFFSET Value 

#26

H 40B0

 

CH3 OFFSET Value 

#27

H 40B1

 

CH4 OFFSET Value 

Adjust offset value of channels CH1~CH4. The range is -1000~+1000 and 
factory setting is K0. (unit: 0.1 degrees C) 

#28~#29 Reserved 
#30

H 40B4

 

Error status 

Data register stores the error status, refer to fault code chart for details. 

#31

H 40B5

  R/W Communication 

address 

setting 

RS-485 communication address.   
Setting range is 01~255 and factory setting is K1 

#32

H 40B6

  R/W  Communication baud rate 

setting 

Communication baud rate (4800, 9600, 19200, 38400, 57600 and 115200 bps). 
b0: 4800 bps (bit/sec). 
b1: 9600 bps (bit/sec).    (factory setting) 
b2: 19200 bps (bit/sec). 
b3: 38400 bps (bit/sec). 
b4: 57600 bps (bit/sec). 
b5: 115200 bps (bit/sec). 
b6~b13: Reserved. 
b14: switch between low bit and high bit of CRC code (only for RTU mode) 
b15: RTU mode.   

b15 b14  b13  b12 b11 b10 b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Definition of ERR 

LED 

CH4 CH3 CH2  CH1 

#33

H 40B7

  R/W  Reset to factory setting 

Example: Setting of CH1 
1. b0 Reserved 
2. b1 Reserved 
3. b2: Set to 1 and PLC will be reset to factory settings. 
Definition of ERR LED: b12~b15=1111(factory settings) 
1.  b12 corresponds to CH1:    when b12=1, scale exceeds the range or external 

contact has no connection, ERR LED flashes. 

2.  b13 corresponds to CH2: when b13=1, scale exceeds the range or external 

contact has no connection, ERR LED flashes. 

3.  b14 corresponds to CH3: when b14=1, scale exceeds the range or external 

contact has no connection, ERR LED flashes. 

4.  b15 corresponds to CH4: when b15=1, scale exceeds the range or external 

contact has no connection, ERR LED flashes. 

#34

H 40B4

 

Software version 

Display software version in hexadecimal.    Example: H 010A = version 1.0A. 

#35~#48 System 

used 

 means latched.  

 means not latched. 

R means can read data by using FROM instruction or RS-485.   
W means can write data by using TO instruction or RS-485. 

Explanation: 

1. CR#0: The PLC model type.   

 