2. CR#1: Used to set the working mode of four channels (CH1~CH4). There are 2 modes (J-type 

and K-type) for each channel and can be set individually. For example, If you want to set 
CH1~CH4 as following: CH1: mode 0 (b2~b0=000), CH2: mode 1(b5~b3=001), CH3: mode 
0(b8~b6=000) and CH4: mode 1(b11~b9=001), you should set CR#1 to H0208. The higher 
bits (b12~b15) will be reserved and the factory setting is H0000. 

3. CR#2 ~ CR#5: Used to set the times of input readings for the average temperature calculation. 

The available range is K1~K4096 and factory setting is K10. (Note: When PLC sets average 
times via TO/DTO instructions, please use rising-edge/falling-edge detection instruction (such 
as LDP and LDF) to get correct average times.) 

4. CR#6 ~ CR#9: The average temperature (

°

C).    The average temperature is calculated from 

multiple temperature readings.    Example: If CR#2 is 10, the temperature in CR#6 will be the 
average of the last 10 readings in CH1. 

5. CR#10 ~ CR#13: The average temperature (

°

F).    The average temperature is calculated from 

multiple temperature readings.    Example: If CR#2 is 10, the temperature in CR#12 will be the 
average of the last 10 readings in CH1. 

6. CR#14 ~ CR#17: display present temperature (

°

C) of CH1~CH4 input signal. 

7. CR#18, CR#23, CR#28, CR#29 are reserved. 

8. CR#19 ~ CR#22: display present temperature (

°

F) of CH1~CH4 input signal. 

9. CR#24 ~ CR#27: display offset value of channels CH1~CH4. The range is -1000~+1000 and 

unit is 0.1 degrees C. The definition of OFFSET is Actual temperature = temperature 
measured by DVP04TC-S – OFFSET value. 

10. CR#30 is a fault code register. Refer to the following chart. 

Fault 

description 

Content b15~b8 b7 b6 b5 b4 b3 b2 b1

b0 

Power 

source 

abnormal K1(H1) 

0 0 0 0 0 0 0 1 

Analog 

input 

value 

error K2(H2) 

0 0 0 0 0 0 1 0 

Setting 

mode 

error 

K4(H4) 

0 0 0 0 0 1 0 0 

Offset/Gain 

error 

K8(H8) 

0 0 0 0 1 0 0 0 

Hardware 

malfunction  K16(H10) 

0 0 0 1 0 0 0 0 

Digital 

range 

error 

K32(H20) 

0 0 1 0 0 0 0 0 

Average 

times 

setting 

error 

K64(H40) 

0 1 0 0 0 0 0 0 

Instruction error 

K128(H80) 

Reserved 

1 0 0 0 0 0 0 0 

Note: Each fault code will have corresponding bit (b0~b7). Two or more faults may happen at the same time. 0 

means normal and 1 means fault occurs. 

11. CR#31: RS-485 communication address. Setting range is 01~255 and factory setting is K1. 

12. CR#32: RS-485 communication baud rate: 4800, 9600, 19200, 38400, 57600 and 115200. 

b0:4800bps, b1:9600bps (factory setting), b2:19200bps,  b3:38400 bps, b4:57600 bps, 
b5:115200 bps, b6~b13: Reserved, b14: switch between low bit and high bit of CRC code 
(only for RTU mode), b15: ASCII / RTU mode. For ASCII mode, date format is 7Bits, even, 1 
stop bit (7 E 1). For RTU mode, date format is 8Bits, even, 1 stop bit (8 E 1). 

13. CR#33: Used to reset the settings of CR registers to factory settings.   

14. CR#34: software version. 

15. CR#35~ CR#48: Reserved for internal system use. 

16. The corresponding parameters address H 4096~H 40C7 of CR#0~CR#48 may provide users 

to read/write data via RS-485 communication. 

a.  Communication baud rate: 4800, 9600, 19200, 38400, 57600, 115200 bps. 
b.  Communication format: ASCII mode is 7Bit, even bit, 1 stop bit (7 E 1). Communication 

format of RTU mode is 8Bit, even bit, 1 stop bit (8 E 1).   

c.  Function code: 03H—read data from register. 06H—write a WORD into register. 

10H—write many WORDs into register. 

 

5  

Temperature/Digital 

Characteristic 

Curve 

 

Temperature mode: (Centigrade) 

J-type thermocouple 

+7000

-1000

+700

-100 C

C

Digital output

Temperature
 input

 

K-type thermocouple 

Digital output

Temperature
 input

+10000

-1000

+1000

-100 C

C

 

Temperature mode: (Fahrenheit)

 

J-type thermocouple

 

Digital output

Temperature
 input

+12920

-1480

+1292

-148 F

F

K-type thermocouple

 

Digital output

Temperature
 input

+18320

-1480

+1832

-148 F

F

 

6   

Initial PLC Start-up 

 

LED display: 

1.  Upon power-up, the ERROR LED will light for 0.5 seconds the POWER LED will light continuously. 
2.  No errors= POWER LED on and ERROR LED off.       

Low Voltage error (lower than 19.5V), ERROR LED will blink continuously till the power supply 
rises above 19.5V. 

3.  DVP04TC-S connected to PLC MPU in series = RUN LED on MPU will be lit and A/D LED or D/A 

LED should blink. 

4.  After receiving the first RS-485 instruction the A/D LED or D/A LED will blink. 
5.  If the input or output exceeds the upper or lower bounds, then the ERROR LED will blink. 

 

Example: 

M1000

FROM

K0

= H8B  D0

TO

K0

FROM

K0

FROM

K0

FROM

K0

FROM

K0

END

M1002

 

Explanation: 

 

Reading the model type of extension module K0 (should be H8B for DVP04TC-S model type). 

 

The averaging number for CH1~CH4 will be D10~D13. 

 

If the model type is DVP04TC-S. Reading the average temperature (

°

C) of CH1~CH4 (4 data) 

from CR#6~CR#9 and save them into D20~D23. 

 

Reading the average temperature (

°

F) of CH1~CH4 (4 data) from CR#10~CR#13 and save them 

into D24~D27. 

 

Reading the present temperature (

°

C) of CH1~CH4 (4 data) from CR#14~CR#17 and save them 

into D30~D33. 

 

Reading the present temperature 

(

°

F)

 of CH1~CH4 (4 data) from CR#19~CR#22 and save them 

into D34~D37. 

 

7   

Related Instructions Explanation 

 

API 

 

 

 

Applicable model 

SS SA/SX/SC EH

78

 

 

FROM 

P

 

 

 

 

Special module CR 
data read out 

 

 

 

Bit device 

Word device 

 

X Y M S K H KnX KnY KnM KnS T C D E F

m

1

 

 

 

 

 

¼

 

¼

 

 

 

 

 

m

2

 

 

 

 

   

¼

 

¼

 

 

 

 

 

 

 

 

 

 

 

 

 

¼

¼

¼

¼ ¼ ¼ ¼

¼

 

 

 

 

¼

 

¼

 

 

 

 

 

 

Note: The usage range of operand m

1

 is 0~7. 

The usage range of operand m

2

: SS/SA: 0-48, EH: 

0-254.   

The usage range of operand n: SS/SA: n= 1~(49-m2), 

EH: 1~(255-m2). 

SS series model doesn’t support pulse execution 

instruction (FROMP, DFROMP).

 

 

16-bit instruction (9 STEPS)

 

FROM

Continuous 
execution 

FROMP

Pulse 
execution 

 

32-bit instruction (17 STEPS)

 

DFROM

Continuous 
execution

DFROMP

Pulse 
execution

 

Flag: When M1083=On, it allows to 

insert interrupt during FROM/TO.

Refer to following for detail.

 

Command

Explanation

 

m1

: the number for special module. 

m2

: the number of CR (Control Register) of special 

module that will be read. 

D

: the location to save reading data. 

n

: the data number of 

reading one time. 

DVP-series PLC uses this instruction to read CR data of special module.

 

D

: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be used 

for 32-bit.

 

Please refer the following footnote for calculationof special module number.

 

 

API

 

Applicable model 

SS SA/SX/SC EH

79

D

TO 

 

 

 

 

Special module CR 
data write in 

 

 

 

Bit device 

Word device 

 

X

Y

M  S  K  H  KnX KnY KnM KnS  T  C  D

E

F

m

1

 

 

¼

 

¼

 

 

 

 

 

 

 

m

2

 

     

¼

 

¼

 

 

 

 

 

 

   

 

 

¼

 

¼

 

¼

 

¼

 

¼

 

¼

 

¼

 

¼

 

¼

¼

¼

 

 

¼

 

¼

 

 

 

 

 

 

 

 

Note: The usage range of operand m

1

 is 0~7. 

The usage range of operand m

2

: SS/SA: 0-48, EH: 

0-254. 

The usage range of operand n: SS/SA n= 1~(49-m2), 

EH: 1~(255-m2). 

For SS series, it doesn’t support pulse execution 

instruction (TOP, DTOP)

 

 

16-bit instruction (9 STEPS) 

TO

Continuous 
execution 

TOP

Pulse 
execution

 

32-bit instruction (17 STEPS) 

DTO

Continuous 
execution 

DTOP

Pulse 
execution

 

Flag: When M1083=On, it allows         

to insert interrupt during 
FROM/TO. 
Refer to following for detail.

 

 

Command

Explanation

 

m1

: the number of special module. 

m2

: the number of CR (Control Register) of special 

module that will be wrote in. 

S

: the data to write in CR. 

n

: the data number to write in 

one time.   

DVP-series PLC uses this instruction to write data into CR of special module.   

S

: When assigning bit operand, K1~K4 can be used for 16-bit and K5~K8 can be used 

for 32-bit.

 

Footnote

 

The rule of instruction operand: 

m1: arrangement number of special module. The number of special module that 
connects to PLC MPU. The numbering order of special module from the near to 
the distant of MPU is from 0 to 7. The maximum is 8 special modules and won’t 
occupy I/O point. 
m2: the number of CR. Built in 16-bit of 49 groups memory of special module is 
called CR (Control Register). The number of CR uses decimal digital (#0~#48). All 
running status and setting values of special module has included. 
If using FROM/TO instruction, the unit of read/write of CR is one number for one 
time. If using DFROM/DTO instruction, the unit of read/write of CR is two numbers 
in one time. 

CR #10

CR #9

Upper 16-bit Lower 16-bit

Specified CR number

 

The number of transmission groups n. The meaning of n=2 of 16-bit instruction 
and n=1 of 32-bit are the same.

 

 

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

Specified device

Specified CR

Specified device Specified CR

16-bit command when n=6

32-bit command when n=3

 

In SS series models, flag M1083 is not provided. When FROM/TO instruction is 
executed, all interrupts (including external or internal interrupt subroutines) will be 
disabled. All interrupts will be executed after FROM/TO instruction is completed. 
Besides, FROM/TO instruction also can be executed in the interrupt subroutine. 
The function of the flag M1083 (FROM/TO mode exchange) provided in SA/EH series 
models: 

1.  When M1083=Off, FROM/TO instruction is executed, all interrupts (including 

external or internal interrupt subroutines) will be disabled. All interrupts will be 
executed after FROM/TO instruction is completed. Besides, FROM/TO 
instruction also can be executed in the interrupt subroutine. 

2.  When M1083=On, if an interrupt occurs while FROM/TO instruction has been 

programmed, FROM/TO instruction will be interruptted to execute the 
interrupt. However, FROM/TO instruction cannot be executed in the interrupt 
subroutine. 

 

 