4.  This function will consume 3 ~ 5 seconds more when you switch on DTE. 

 

 RS-485 Communication

 

1.  DTE supports baud rates 2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps and does not support communication 

format 7, N, 1/8, E, 2/8, O, 2. Communication protocol = Modbus ASCII or RTU. 

2.  Function codes: H03 = read maximum 8 words in the register; H06 = write 1 word into the register. 
3.  Address and contents: Every parameter has 2 communication addresses. One is numbered by the function of the 

parameter, and the other is by the order of channel (as shown in the table below). 

 

 

INA 

INB 

Content 

Explanation 

CH1 

CH2 

CH3 

CH4 

CH5 

CH6 

CH7 

CH8 

Present 
temperature 
value/input error 
code 

Unit; 0.1 
See Table 5 

H1000 

(H1100) 

H1001 

(H1200) 

H1002 

(H1300) 

H1003 

(H1400) 

H1004 

(H1500) 

H1005 

(H1600) 

H1006 

(H1700) 

H1007 

(H1800) 

Set temperature 
value 

Unit: 0.1 

H1008 

(H1101) 

H1009 

(H1201) 

H100A 

(H1301) 

H100B 

(H1401) 

H100C 

(H1501) 

H100D 

(H1601) 

H100E 

(H1701) 

H100F 

(H1801) 

Max. temperature 
value 

Disabled when higher 
than default value 

H1010 

(H1102) 

H1011 

(H1202) 

H1012 

(H1302) 

H1013 

(H1402) 

H1014 

(H1502) 

H1015 

(H1602) 

H1016 

(H1702) 

H1017 

(H1802) 

Min. temperature 
value 

Disabled when lower 
than default value 

H1018 

(H1103) 

H1019 

(H1203) 

H101A 

(H1303) 

H101B 

(H1403) 

H101C 

(H1503) 

H101D 

(H1603) 

H101E 

(H1703) 

H101F 

(H1803) 

Error temperature 
value 

-999 ~ +999 
Unit: 0.1°C 

H1020 

(H1104) 

H1021 

(H1204) 

H1022 

(H1304) 

H1023 

(H1404) 

H1024 

(H1504) 

H1025 

(H1604) 

H1026 

(H1704) 

H1027 

(H1804) 

Proportional band 
value (Pb) 

0 ~ 9,999   
Unit: 0.1 

H1028 

(H1105) 

H1029 

(H1205) 

H102A 

(H1305) 

H102B 

(H1405) 

H102C 

(H1505) 

H102D 

(H1605) 

H102E 

(H1705) 

H102F 

(H1805) 

Ti value 

0 ~ 9,999 

H1030 

(H1106) 

H1031 

(H1206) 

H1032 

(H1306) 

H1033 

(H1406) 

H1034 

(H1506) 

H1035 

(H1606) 

H1036 

(H1706) 

H1037 

(H1806) 

Td value 

0 ~ 9,999 

H1038 

(H1107) 

H1039 

(H1207) 

H103A 

(H1307) 

H103B 

(H1407) 

H103C 

(H1507) 

H103D 

(H1607) 

H103E 

(H1707) 

H103F 

(H1807) 

Integration default 

0.0 ~ 100.0% 
Unit: 0.1% 

H1040 

(H1108) 

H1041 

(H1208) 

H1042 

(H1308) 

H1043 

(H1408) 

H1044 

(H1508) 

H1045 

(H1608) 

H1046 

(H1708) 

H1010 

(H1808) 

Proportional control 
offset error value, 
when Ti = 0 

0.0 ~ 100.0% 
Unit: 0.1% 

H1048 

(H1109) 

H1049 

(H1209) 

H104A 

(H1309) 

H104B 

(H1409) 

H104C 

(H1509) 

H104D 

(H1609) 

H104E 

(H1709) 

H104F 

(H1809) 

Proportional band 
coefficient of output 
1 and output 2 

0.01 ~ 99.99 
Unit: 0.01 

H1050 

(H110A) 

H1051 

(H120A) 

H1052 

(H130A) 

H1053 

(H140A) 

H1054 

(H150A) 

H1055 

(H160A) 

H1056 

(H170A) 

H1057 

(H180A) 

Dead band of 
control output 1 & 
output 2. 

-99.9 ~ 999.9 

H1058 

(H110B) 

H1059 

(H120B) 

H105A 

(H130B) 

H105B 

(H140B) 

H105C 

(H150B) 

H105D 

(H160B) 

H105E 

(H170B) 

H105F 

(H180B) 

Hysteresis for 
output 1 

0 ~ 9,999 
Unit: 0.1% 

H1060 

(H110C) 

H1061 

(H120C) 

H1062 

(H130C) 

H1063 

(H140C) 

H1064 

(H150C) 

H1065 

(H160C) 

H1066 

(H170C) 

H1067 

(H180C) 

Hysteresis for 
output 2 

0 ~ 9,999 
Unit: 0.1% 

H1068 

(H110D) 

H1069 

(H120D) 

H106A 

(H130D) 

H106B 

(H140D) 

H106C 

(H150D) 

H106D 

(H160D) 

H106E 

(H170D) 

H106F 

(H180D) 

Read/write output 
1 value 

Unit: 0.1 % 

H1070 

(H110E) 

H1071 

(H120E) 

H1072 

(H130E) 

H1073 

(H140E) 

H1074 

(H150E) 

H1075 

(H160E) 

H1076 

(H170E) 

H1077 

(H180E) 

Read/write output 
2 value 

Unit: 0.1 % 

H1078 

(H110F) 

H1079 

(H120F) 

H107A 

(H130F) 

H107B 

(H140F) 

H107C 

(H150F) 

H107D 

(H160F) 

H107E 

(H170F) 

H107F 

(H180F) 

Upper limit for 
alarm output 

Alarm enabled 
when temperature 
exceeds upper limit 

H1080 

(H1110) 

H1081 
(1210) 

H1082 

(H1310) 

H1083 

(H1410) 

H1084 

(H1510) 

H1085 

(H1610) 

H1086 

(H1710) 

H1087 

(H1810) 

Lower limit for 
alarm output 

Alarm enabled 
when temperature 
falls below lower 
limit 

H1088 

(H1111) 

H1089 

(H1211) 

H108A 

(H1311) 

H108B 

(H1411) 

H108C 

(H1511) 

H108D 

(H1611) 

H108E 

(H1711) 

H108F 

(H1811) 

Tuning for upper 
limit of analog 
output 

Current (4 ~ 20mA) 
or voltage output 
tuning 

H1090 

(H1112) 

H1091 

(H1212) 

H1092 

(H1312) 

H1093 

(H1412) 

H1094 

(H1512) 

H1095 

(H1612) 

H1096 

(H1712) 

H1097 

(H1812) 

Tuning for lower 
limit of analog 
output 

Current (4 ~ 20mA) 
or voltage output 
tuning 

H1098 

(H1113) 

H1099 

(H1213) 

H109A 

(H1313) 

H109B 

(H1413) 

H109C 

(H1513) 

H109D 

(H1613) 

H109E 

(H1713) 

H109F 

(H1813) 

Input sensor type 

See “Input” section 

H10A0 

(H1114) 

H10A1 

(H1214) 

H10A2 

(H1314) 

H10A3 

(H1414) 

H10A4 

(H1514) 

H10A5 

(H1614) 

H10A6 

(H1714) 

H10A7 

(H1814) 

Output function 
for output 1 

0: heating 
1: cooling 
2: proportional 

output 

H10A8 

(H1115) 

H10A9 

(H1215) 

H10AA 

(H1315) 

H10AB 

(H1415) 

H10AC 

(H1515) 

H10AD 

(H1615) 

H10AE 

(H1715) 

H10AF 

(H1815) 

Output function 
for output 2 

0: heating (default) 
1: cooling 
2: alarm 

H10B0 

(H1116) 

H10B1 

(H1216) 

H10B2 

(H1316) 

H10B3 

(H1416) 

H10B4 

(H1516) 

H10B5 

(H1616) 

H10B6 

(H1716) 

H10B7 

(H1816) 

Control method 

0: PID   
1: ON-OFF 
2: manual   
3: PID 

programmable 

H10B8 

(H1117) 

H10B9 

(H1217) 

H10BA 

(H1317) 

H10BB 

(H1417) 

H10BC 

(H1517) 

H10BD 

(H1617) 

H10BE 

(H1717) 

H10BF 

(H1817) 

Alarm 1 output 
mode 

See “Alarm Output” 

section 

H10C0 

(H1118) 

H10C1 

(H1218) 

H10C2 

(H1318) 

H10C3 

(H1418) 

H10C4 

(H1518) 

H10C5 

(H1618) 

H10C6 

(H1718) 

H10C7 

(H1818) 

Alarm 2 output 
mode 

See “Alarm Output” 
section 

H10C4 

(H1518) 

H10C5 

(H1618) 

H10C6 

(H1718) 

H10C7 

(H1818) 

 

 

 

 

Heating/cooling 
cycle for output 1 

1 ~ 99 seconds 
0 = 0.5 second 

H10C8 

(H1119) 

H10C9 

(H1219) 

H10CA 

(H1319) 

H10CB 

(H1419) 

H10CC 

(H1519) 

H10CD 

(H1619) 

H10CE 

(H1719) 

H10CF 

(H1819) 

Heating/cooling 
cycle for output 2 

1 ~ 99 seconds 
0 = 0.5 second 

H10D0 

(H111A) 

H10D1 

(H121A) 

H10D2 

(H131A) 

H10D3 

(H141A) 

H10D4 

(H151A) 

H10D5 

(H161A) 

H10D6 

(H171A) 

H10D7 

(H181A) 

 

 

INA 

INB 

Content 

Explanation 

CH1 

CH2 

CH3 

CH4 

CH5 

CH6 

CH7 

CH8 

Run/Stop the 
control 

0: stop 
1: executing 
2: program stops   
3: program pauses 

H10D8

(H111B)

H10D9

(H121B)

H10DA

(H131B)

H10DB

(H141B)

H10DC

(H151B)

H10DD 

(H161B) 

H10DE 

(H171B) 

H10DF 

(H181B) 

Status of PID 
auto-tuning 

0: stop 
1: executing 

H10E0

(H111C)

H10E1

(H121C)

H10E2

(H131C)

H10E3

(H141C)

H10E4

(H151C)

H10E5 

(H161C) 

H10E6 

(H171C) 

H10E7 

(H181C) 

Positive/negative 
proportional 
output 

0: positive 
1: negative (slope) 

H10E8

(H111D)

H10E9

(H121D)

H10EA

(H131D)

H10EB

(H141D)

H10EC

(H151D)

H10ED 

(H161D) 

H10EE 

(H171D) 

H10EF 

(H181D) 

Other statuses 

Other statuses 

H10F0

Temperature 

unit 

H10F1

Open special 

function

(H1234)

H10F2

Return to 

default

 

(H1357)

H10F3  

Reserved

H10F4  

Reserved

H10F5  

Reserved

 

H10F6  

Reserved

 

H10F7  

Reserved

 

Communication 
specifications 

See Table 4 

H10F8

Auto ID 

setup 

H10F9

Reserved

H10FA

Baud rate

H10FB

ASCII = 0 

RTU = 1 

H10FC

8 bits=0 
7 bits=1

H10FD 

2 stop=0 
1 stop=1

 

H10FE 

Parity 

H10FF 

Address 

1 ~ 247

 

Communication Parameter Setting: 

Content 

Baud rate 

2,400bps 

4,800bps 

9,600bps 

19,200bps

38,400bps

57,600bps 

115,200bps 

Parity bit 

None (N) 

Even (E) 

Odd (O) 

 

 

 

 

Table 4

 

Error Codes: 

The error codes can be read from address H1000 ~ H1007. When the input operation is in normal status, H1000 ~ H1007 are 
for input values. When input error occurs (except for stable status and input exceeding the range), DTE will read error codes 
in H8001 ~ H8002. 

 

H1000 Error 

description 

H8001 

EEPROM cannot be written in. 

H8002 

Input sensor is not connected. 

H8003 

Group INB is not connected. 

Table 5

 

Analog output current tuning scale: 

1

μ

A/scale 

Analog output voltage tuning scale:

 1mV/scale

 

Returning to Default Value: 

Write H1234 into address H10F1 and H1357 into address H10F2. Restart DTE. 

Programmable Communication Parameter Setting: 

 

 

INA 

INB 

Content 

Explanation

CH1

CH2

CH3

CH4

CH5

CH6 

CH7 

CH8 

Read remaining time of the step

Unit: sec 

H111E H121E H131E H141E H151E H161E  H171E  H181E 

Read remaining time of the step

Unit: min 

H111F

H121F H131F H141F H151F H161F  H171F  H181F 

Read the NO. of the current 
pattern 

0 ~ 7 

H1120

H1220

H1320

H1420

H1520

H1620  H1720  H1820 

Read the NO. of the current step

0 ~ 7 

H1121

H1221

H1321

H1421

H1521

H1621  H1721  H1821 

NO. of start pattern 

0 ~ 7 

H1122

H1222

H1322

H1422

H1522

H1622  H1722  H1822 

NO. of start step 

0 ~ 7 

H1123

H1223

H1323

H1423

H1523

H1623  H1723  H1823 

Programmable Parameter Setting: 

Content 

Explanation 

Pattern 

Pattern 

Pattern 

Pattern 

Pattern 

Pattern 

Pattern 

Pattern 

Max. number of 
steps in the pattern 

0 ~ 7 = N: The pattern 
executes from step 0 to 
N. 

H2068

H2069 H206A H206B H206C H206D H206E H206F 

Number of cycles of 
pattern 0 ~ 7 
execution 

0 ~ 199: The pattern 

has been executed for 1 
~ 200 times 

H2070

H2071

H2072

H2073

H2074

H2075 H2076 H2077 

NO. of current link 
pattern 

0 ~ 8: 8 refers to end of 

program; 0 ~ 7 refer to 
the NO. of next pattern 

H2078

H2079 H207A H207B H207C H207D H207E H207F 

 

Address 

Default 

Content 

Explanation 

2000H ~ 203FH 

Target temperatures for pattern 0 ~ 7 
Pattern 0: 2000H ~ 2007H 

Unit: 0.1°C 

2080H ~ 20BFH 

Execution time for pattern 0 ~ 7 
Pattern 0: 2080H ~ 2087H 

Time: 0 ~ 900 (Unit: 1 min) 

4.  Communication format: H03 = read bit data; H06 = write bit data 

ASCII Mode:

 

Read Command 

Read Response Message 

Write Command 

Write Response Message 

Start word 

’:’

Start word 

’:’

Start word 

’:’

Start word 

’:’ 

Machine address 1 

‘0’

Machine address 1 

‘0’

Machine address 1 

‘0’

Machine address 1 

‘0’ 

Machine address 0 

‘1’

Machine address 0 

‘1’

Machine address 0 

‘1’

Machine address 0 

‘1’ 

Command 1 

‘0’

Command 1 

‘0’

Command 1 

‘0’

Command 1 

‘0’ 

Command 0 

‘3’

Command 0 

‘3’

Command 0 

‘6’

Command 0 

‘6’ 

Read Command 

Read Response Message 

Write Command 

Write Response Message

‘1’

‘0’

‘1’

‘1’

‘0’

Length of response data 

(byte) 

‘4’

‘0’

‘0’

‘0’

‘0’

‘0’

‘0’

Read start address of 

data/bit 

‘0’

‘1’

Data address 

‘1’

Data address 

‘1’

‘0’

‘F’

‘0’

‘0’

‘0’

Data content in H1000

‘4’

‘3’

‘3’

‘0’

‘0’

‘E’

‘E’

Read length of data/bit 

(word/bit) 

‘2’

‘0’

Write data content 

‘8’

Write data content 

‘8’

LRC1 check   

‘E’

‘0’

LRC1 check 

‘F’

LRC1 check 

‘F’

LRC0 check 

‘A’

Data content in H1001

‘0’

LRC0 check 

‘D’

LRC0 check 

‘D’

End word 1 

CR

LRC1 check   

‘0’

End word 1 

CR

End word 1 

CR

End word 0 

LF

LRC0 check 

‘3’

End word 0 

LF

End word 0 

LF

  

End 

word 

CR

    

  

End 

word 

LF

    

LRC Check:

 

Sum up the contents from “machine address” to “data content”, e.g. H01 + H03 + H10 + H00 + H00 + H02 = H16. Obtain 
2’scomplement H EA.

 

RTU Mode: 

Read Command 

Read Response Message

Write Command 

Write Response Message 

Machine address 

H01

Machine address 

H01

Machine address 

H01

Machine address

H01

Command H03

Command H03

Command H06

Command H06

H10

H10

H10

Read start address of 

data 

H00

Length of response 

data (byte) 

H04

Write data address

H01

Write data address

H01

H00

H01

H03

H03

Read length of data 

(bit/word) 

H02

Data content 1 

HF4

Write data content

H20

Write data content

H20

CRC low byte 

HC0

H03

CRC low byte 

HDD

CRC low byte 

HDD

CRC high byte 

HCB

Data content 2 

H20

CRC high byte 

HE2

CRC high byte 

HE2

 

CRC low byte 

HBB

 

 

CRC high byte 

H15

 

CRC (Cyclical Redundancy Check) is obtained by the following steps:

 

                           

unsigned int reg_crc = 0xffff; 

i = 0; 
while (length--) 
{  reg_crc ^= RTUData[i]; 

      i ++; 
      for (j = 0; j < 8; j++) 
   {  if (reg_crc & 0x01)        reg_crc = (reg_crc >> 1) ^ 0xA001; 

            else                                          reg_crc = reg_crc >> 1; 

       

}   

}  
return(reg_crc); 

Software for Setting up Communication on PC: 

Download the free software on Delta

s website.

 

 

 How to Mount & DIN Rail Size

 

 

 

 

Connect maximum 7 DTC2000 or DTC2001 controllers to DTE by using DIN rail. 

 

 

 

 

 

 

 

The content of this instruction sheet may be revised without prior notice. Please consult our distributor or 

download the most updated version at http://www.delta.com.tw/industrialautomation.