background image

 

 

 

Warning 

 

Always read this instruction sheet thoroughly before using DVP EH digital I/O extension unit. 

 

This is an OPEN TYPE extension unit. The extension unit should be kept in an enclosure away from airborne, dust, 
high humidity, electric shock risk and vibration. Also, it is equipped with protective methods such as special tools or 
keys to open the enclosure, so as to avoid the hazard to users and damage the extension unit. 

 

DO NOT connect AC main circuit power supply to any of the input/output terminals, as it will damage the extension 
unit. Check all the wiring prior to power up. DO NOT touch terminals when power on. 

 Introduction

 

Thank you for choosing Delta DVP-EH series PLC. The main processing units offer 8 ~ 48 points and the 
maximum input/output can be extended up to 256 points. 

 Product Profile and Outline 

1

3

4

3

5

5

2

7

7

 

2

1

5

5

3

3

4

7

7

 

 

Dimension  (mm) 

Model   

Length 

Width 

Height 

DVP08HM11N 

90 

40 

82 

DVP16HM11N 

90 

55 

82 

DVP08HN11R/T 

90 

40 

82 

DVP16HP11R/T 

90 

55 

82 

 

3

4

2

6

6

6

7

7

3

3

8

 9

1

10

11

 

 

Dimension  (mm) 

Model 

Length 

Width 

Height 

DVP32HN00R/T 

90 

143.5 

82.2 

DVP32HP00R/T 

90 

143.5 

82.2 

DVP48HP00R/T 

90 

174 

82.2 

 

1. Power, low voltage indicators 

5.  Extension  wiring 

9. Cover 

2.  I/O  terminals 

6.  Extension port cover 

10. Input  indicators 

3. DIN rail clip 

7.  Direct  mounting  holes   

11.  Output  indicators 

4. DIN rail 

8. Model name 

 

 DVP EH Series Model 

 

Input unit 

Output unit 

Model 

Power 

Points 

Type 

Points 

Type 

DVP08HM11N 

DVP16HM11N 

16 

N/A 

DVP08HN11R 

DVP08HP11R 

DVP16HP11R 

Relay: 250V AC/30V DC 2A/1point 

DVP08HN11T 

DVP08HP11T 

DVP16HP11T 

24V DC 

DC Type 

Sink/Source 

Transistor: 5 ~ 30V DC 0.3A/1point at 40°C 

ENGLISH 

 Specifications 

 Electrical Specification 

 

Model   

  Item 

08HM11N 
16HM11N 

08HN11R/T  08HP11R/T  16HP11R/T  32HN00R/T 

32HP00R/T 

48HP00R/T 

Power supply voltage 

24V DC (20.4 ~ 28.8V DC) (-15% ~ 20%) 

100~240V AC (-15%~10%), 50/60Hz 

±

 5% 

Power consumption 

1W/1.5W 

1.5W 

1.5W 

2W 

30VA 

30VA 

30VA 

24V DC supply current 

NA 

NA 

NA 

NA 

NA 

500mA 

500mA 

Power protection 

24V DC output  with  short-circuit  protection

 

Voltage withstand 

1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 

Insulation  resistance 

> 5 M

 at 500V DC (Between all input/output and earth) 

Noise  immunity 

ESD: 8KV Air  Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & 
Communication  I/O:  250V,   
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 

Grounding 

The diameter of grounding wire cannot be smaller than the wire diameter of the terminals Land 
N (All DVP units should be grounded directly to the ground pole.) 

Environment 

Operation:  0

°

C ~ 55°C (temperature),  50 ~ 95% (humidity),  Pollution  degree 2;   

Storage: -25

°

C ~ 70

°

C (temperature),  5 ~ 95% (humidity) 

Vibration/shock 
resistance 

Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

Weight  (g) 

124/160 

130/120 

136/116 

225/210 

660/590 

438/398 

616/576 

Approvals 

 

 

 

 

 I/O Terminal Specification 

Input point 

Input  point type 

DC 

Input  type 

DC (SINK or SOURCE) 

Input  current 

24V DC 5mA 
Off

On, above 16.5V DC     

Active  level 

On

Off, below 8V DC 

Reaction time 

About 20ms 

Circuit isolation 
/operation  indicator 

Photocoupler/LED On 

 

Output  point 

  Output point type 

  Relay-R 

  Transistor-T 

Current specification 

1.5A/1point (5A/COM) 

55°C 0.1A/1point, 50°C 0.15A/1point, 
45°C 0.2A/1point, 40°C 0.3A/1point (2A/COM) 

Voltage specification 

Below 250V AC, 30V DC 

30V DC 

75VA (inductive) 

Maximum  load 

90W (resistive) 

9W 

Reaction  time 

About 10ms 

Off

On 15us    On

Off 25us 

Input unit 

Output unit 

Model 

Power 

Points 

Type 

Points 

Type 

DVP32HN00R 

32 

DVP32HP00R 

16 

16 

DVP48HP00R 

24 

24 

Relay: 250V AC/30V DC 2A/1point 

DVP32HN00T 

32 

DVP32HP00T 

16 

16 

DVP48HP00T 

100 ~ 240V   

AC 

24 

DC Type 

Sink/Source 

24 

Transistor:  5 ~ 30V DC 0.3A/1 point at 40°C 

 Installation and Wiring 

 Digital I/O Terminal Wiring 

08HM 

DVP-08HM (8in)

X0 X

2

X

4

X

6

X

1

X

3

X

5

X

7

S/S

 

08HN 

DVP-08HN (8out)

Y0 Y1

Y3

Y4 Y5

Y7

C0 Y2

C1 Y6

 

08HP 

DVP-08HP (4in/4out)

X 0

Y1

Y 3

C0 Y2

Y0

X 2

S /S X 1 X3

 

16HM 

DVP-16HM (16in)

X10 X 11

S /S

X1

X 3

S/S

X12 X13 X 14 X15 X16 X 17

X 0

X2

X4 X5

X7

X6

 

16HP 

DVP-16HP (8in/8out)

X4 X5

X 1

X3

S /S

X6 X7

Y3

Y4 Y5 Y 6

X0

X 2

C 0 Y 0

Y2

Y 1

Y 7

 

32HN 

X15

X14

C3

Y12

Y11

Y10

Y7

Y6

C2

Y5

Y4

Y3

C1

Y2

Y1

Y16

Y20

Y21 Y22 Y23

Y24

C7

C6

C5

C4

Y25

Y30

Y31

Y35

Y36

Y34

Y32

Y27

Y26

C0

DVP-32HN(32out)
(AC Power IN)

Y33

Y37

 

32HP 

X1 7

X16

X15

X14

X13

X12

X11

X1 0

X7

X6

X5

X4

X3

X2

X1

X0

Y0

Y1

Y2

Y3

Y4

Y5

Y6

C3

C2

C1

C0

Y7

Y1 2

Y13

Y16

Y17

Y1 5

Y1 4

Y11

Y1 0

S/S

DVP-32HP(16in/16out)
(AC Power IN,DC Signal IN)

 

48HP 

X17

X16

X15

X14

X13

X12

X11

X10

X7

X6

X5

X4

X3

X2

X1

X0

Y0

Y1

Y2

Y3

Y4

Y5

Y6

C3

C2

C1

C0

Y7

Y12

Y13

Y16

Y17

Y15

Y14

Y11

Y10

S/S

X27

X26

X25

X24

X23

X22

X21

X20

C4 Y21

Y22

Y27

Y23

Y26

Y24

Y20

Y25

DVP-48HP(24in/24out)
(AC Power IN,DC Signal IN)

 

 Mounting Arrangements and Wiring Notes 

DIN Rail Installation: 

The DVP-PLC can be secured to a cabinet by using the DIN 
rail that is 35mm high with a depth of 7.5mm. When 
mounting the PLC on the DIN rail, be sure to use the end 
bracket to stop any side-to-side motion of the PLC, thus to 
reduce the chance of the wires being pulled loose. On the 
bottom of the PLC is a small retaining clip. To secure the 
PLC to the DIN rail, place it onto the rail and gently push up 
on the clip. To remove it, pull down on the retaining clip and 
gently pull the PLC away from the DIN rail. Please see the 
figure on the right: 

 

Direct Mounting:

 Use the specified dimensions and install with M4 screws. 

For heat dissipation. Make 
sure to provide a minimum 
clearance of 50mm between 
the unit and all sides of the 
cabinet. (shown as below) 

D V P MP U

  >  5 0 mm

  >  5 0mm

> 5 0 mm

> 5 0 mm

 

Wiring:

 

Below 6.2

To suit M3.5 screw terminal

Below 6.2

 

1. Please use O-type or Y-type terminals for I/O wiring terminals. The 

specification for the terminals is as shown on the left. PLC terminal screws 
should be tightened to between 5 ~ 8 kg-cm (4.3 ~ 6.9 in-lbs). Use copper 
conductor only, 60°C/75°C. 

2.  DO NOT wire to the No Function terminals   

  . I/O signal wires or power 

supply should not run through the same multi-wire cable or conduit. 

3. When tightening the screws and performing wiring, please avoid that 

metallic particles fall into PLC. After completing wiring, please remove the 
label which is used to obstruct the metallic particles on the ventilation hole 
for well heat dissipation. 

4.  There should be a 50mm or more distance between the PLC and other 

control component. Also, keep the PLC away from high voltage line and 
power equipment.

 

Environment: 

1.

 DO NOT store the PLC in an airborne dust, smoky, metallic particles, corrosive or flammable gases. 

2. DO NOT store the PLC in a location where temperatures and humidity will exceed specification. 
3. DO NOT mount the PLC in a location where vibration and shock will exceed specification. 

 I/O Point Serial Sequence 

When connecting MPU with less than 32 points to extension unit, the input number of 1

st

 extension unit is 

started from X20 in sequence and the output number is started from Y20 in sequence. If connecting MPU with 
more than 32 points to extension unit, the input number of the 1

st

 extension unit is started from the last input   

number of the MPU in sequence and the output number is started form the last output number of the MPU in 
sequence. 

MP U

EXT 1 EXT 2 EXT3 EXT 4

 

PLC 

Model 

Input 

points 

Output   

points 

Input number 

Output number 

MPU  16EH/32EH/64EH  8/16/32 

8/16/32  X0~X7/X0~X17/X0~X37 

Y0~Y7/Y0~Y17/Y0~Y37 

EXT1 

32HP 

16 

16 

X20~X37/X20~X37/X40~X57 

Y20~Y37/Y20~Y37/Y40~Y57 

EXT2 

48HP 

24 

24 

X40~X67/X40~X67/X60~X107 

Y40~Y67/Y40~Y67/Y60~Y107 

EXT3 

08HP 

X70~X73/X70~X73/X110~X113 

Y70~Y73/Y70~Y73/Y110~Y113 

EXT4 

08HN 

Y74~Y103/Y74~Y103/Y114~Y123 

In system application example, if the input/output of the 1

st

 MPU are less than 16, its input/output will be defined 

as 16 and thus there are no corresponding input/output for higher numbers. The input/output number of 
extension number is the sequential number from the last number of the MPU. 

 Power Input Wiring and Specification 

The power input for DVP-EH series PLC is AC input. Please pay particular attention to the following notes: 
1. Connect the AC input (100 ~ 240V) to terminals L and N. Any 110V AC or 220V AC connected to the +24V 

terminal or input points will permanently damage the PLC. 

2. The AC power inputs for the MPU and the I/O Extension Unit should be ON or OFF at the same time. 
3. Please use wires of 1.6mm or above for the grounding of the MPU. 
4. If the power-cut time is less than 10ms, the PLC still operates unaffectedly. If the power-cut time is too long or 

the power voltage drops, the PLC will stop operation and all outputs will be off. Once power is on again, the 
PLC will resume automatically. (There are latched auxiliary relays and registers inside of the PLC, please be 
aware when programming.) 

AC Input 

Type 

L

 

N

 

2.0 A

DC/DC

 

+5V

 

+24V

 

24G

 

S/S

 

X0

 

X1

 

X2

 

100~240VAC

 

 

The +24V supply output is rated at 0.5A as max. from MPU. DO NOT connect external power 
supply to this termianl. Moreover, it takes 6 ~ 7mA to drive each input point, so total of 100mA 
is needed for 16 input points. As a result, the output load of +24V should not exceed 400mA. 

Since the PLC is in control of numerous devices, operation of either one device could affect the operation of 
other devices; therefore, the breakdown of either one device would consequently be detrimental to the whole 
auto control system, and danger will thus be resulted. Please use the recommended wiring below for the power 
input: 

 

Power supply for AC loads 

 

Fuse for circuit  protection (3A  limit) 

 

Power on pilot indicator 

 

Emergency stop:  a manual stop button is provided for emergency 
to disconnect  system power. 

 

Circuit  isolation  device (System Power  Disconnect): use 
electromagnetic  contactor  and the relay to be the isolation unit of 
the power circuit to prevent the  possible instability of the system 
when the power is supplied on and off. 

 

DVP  PLC MPU (main processing unit) 

 

Class  three  grounding. 

OV

24 VDC

MC

MC

N

L

1

1

2

3

4

5

6

6

7

8

Guard
Lim it

 

 

 

Power supply:   

 

AC: 100 ~ 240V AC, 50/60Hz   
DC: 24V DC 

 Input/Output Point Wiring 

Input Point Wiring 

There are SINK and SOURCE types for the input signal of the input point with DC input. Definition as follows: 

Sink = Current flow into common terminal S/S 

Source = Current flows out of common terminal S/S 

S/S

X0

Sinking

 

S/S

X0

Sourcing

 

 

Input point loop equivalent circuit 

Wiring loop 

DC Type 

(DC Signal IN) 

SINK

 Mode 

(Current flows into the 
common terminal S/S) 

24VDC

24G

X0

S/S

+24V

SINK

+5V

 

24G

S/S X0

X1

X2

+24V

Sink Type

 

Input point loop equivalent circuit 

Wiring loop 

DC Type 

(DC Signal IN) 

SOURCE

 Mode 

(Current flows out of 

common terminal S/S) 

24VDC

24G

X0

S/S

+24V

SOURCE

+5V

 

24G

S/S X0

X1

X2

+24V

Source Type

 

Output Point Wiring 

 

  DO NOT wire to the No Function terminals   

   

 

  Fuse 

 

  Diode in reverse direction  to protect the relay*1 

 

  Mutually  exclusive  outputs*2 

 

  Emergency stop:  use  an external switch 

 

  Surge  absorber*3 

 

  Conductive  loading 

 

 

  Incandescent  lamp  (resistive  loading) 

 

  DC supply 

Relay output wiring 

MC2

MC1

9

10

C0

C1

Y0

Y4

C2

Y2

Y3

Y5

Y1

5

2

3

7

8

1

6

7

2

5

4

MC2

MC1

 

 

  AC supply 

*1: There is no protection circuit for the Relay output in the PLC. If DC conductive loading is on, add a diode in reverse direction in 

parallel to extend the life of the Relay. The diode in reverse direction should correspond to the following specification: 

 

- The diode is able to withstand 5~10+ times loading voltage as maximum. 

 

- The forward current of the diode must be greater than loading current. 

*2: Use external hardware interlock and those in the PLC program to secure any emergent errors with safety protection. 
*3: There is no protection circuit for the Relay in  the PLC. If AC conductive loading is on, connect a surge absorber (0.1uF+ “100ohm to 

120ohm”) to reduce interference and extend the life of the Relay. 

 

  DO NOT wire to the No Function terminals   

   

 

  Emergency  stop 

 

  Fuse 

 

  Mutually  exclusive  output*1 

 

  DC apply 

 

  Incandescent  lamp  (resistive  loading) 

 

  Diode in reverse direction  to protect the transistor*2 

 

 

  Conductive  loading 

Transistor output wiring 

MC2

MC1

C0

C1

Y0

Y4

C2

Y2

Y3

Y5

Y1

5

7

8

1

6

6

4

MC2

MC1

2

3

3

9

 

 

  Resistive  loading 

*1: Use external hardware interlock and those in the PLC program to secure any emergent errors with  safety  protection. 
*2: Use Zener diode (39V) inside the PLC to protect the transistor. If conductive loading is on, adding a diode in reverse direction in 

parallel is  recommended. 

 

注意事項 

 

請在使用之前,詳細閱讀本使用說明書。

 

 

本機為開放型

  (OPEN TYPE) 

機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊

/

衝擊

意外之外殼配線箱內。另必須具備保護措施

  (

特殊之工具或鑰匙才可打開

防止非維護人員操作或意外衝

擊本體,造成危險及損壞。

 

 

交流輸入電源不可連接於直流類型之輸入

/

出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認

電源配線。請勿在上電時觸摸任何端子。

 

 

產品簡介 

 

 

謝謝您採用台達

DVP-EH

可程式控制器。

EH 8 ~ 48

點擴充,含主機最大數位輸入

/

輸出擴充分別可達

256

點。

 

 

產品外觀及各部介紹

 

1

3

4

3

5

5

2

7

7

 

2

1

5

5

3

3

4

7

7

 

 

尺寸

  (mm) 

機種名稱

 

 

 

 

DVP08HM11N 

90 

40 

82 

DVP16HM11N 

90 

55 

82 

DVP08HN11R/T 

90 

40 

82 

DVP16HP11R/T 

90 

55 

82 

 

3

4

2

6

6

6

7

7

3

3

8

 9

1

10

11

 

 

尺寸

  (mm) 

機種名稱

 

 

  (w) 

 

DVP32HN00R/T 

90 

143.5 

82.2 

DVP32HP00R/T 

90 

143.5 

82.2 

DVP48HP00R/T 

90 

174 

82.2 

 

1. 

電源、低電壓指示燈

 

5. 

擴充排線

 

  9. 

上蓋

 

2. 

輸出

/

入端子

 

6. 

擴充機連接口上蓋

 

10. 

輸入指示燈

 

3. DIN

軌固定扣

 

7. 

直接固定孔

 

11. 

輸出燈示燈

 

4. DIN

軌固定槽

 

8. 

機種名稱

 

 

 

機種型號

 

輸入單元

 

輸出單元

 

機種

 

電源

 

點數

 

形式

 

點數

 

形式

 

DVP08HM11N 

DVP16HM11N 

16 

 

DVP08HN11R 

DVP08HP11R 

DVP16HP11R 

繼電器

Relay 250V AC/30V DC 2A/1

 

DVP08HN11T 

DVP08HP11T 

DVP16HP11T 

24V DC 

DC Type 

Sink/Source 

電晶體

Transistor  5  ~  30V  DC  0.3A/1

@40°C 

繁體中文 

輸入單元

 

輸出單元

 

機種

 

電源

 

點數

 

形式

 

點數

 

形式

 

DVP32HN00R 

32 

DVP32HP00R 

16 

16 

DVP48HP00R 

24 

24 

繼電器

Relay 250V AC/30V DC 2A/1

 

DVP32HN00T 

32 

DVP32HP00T 

16 

16 

DVP48HP00T 

100 ~ 240V 

AC 

24 

DC Type 

Sink/Source 

24 

電晶體

Transistor  5  ~  30V  DC  0.3A/1

@40

°

 

規格 

 

電氣規格

 

 

機種

 

 

項目

 

08HM11N 
16HM11N 

08HN11R/T  08HP11R/T  16HP11R/T  32HN00R/T  32HP00R/T  48HP00R/T 

電源電壓

 

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ 20%) 

100 ~ 240V AC (-15% ~ 10%), 
50/60Hz 

±

 5% 

消耗電力

 

1W / 1.5W 

1.5W 

1.5W 

2W 

30VA 

30 VA 

30 VA 

24V DC

供應電流

 

NA 

NA 

NA 

NA 

NA 

500 mA 

500 mA 

24V DC

輸出具短路保護

24V DC

輸出具短路保護

 

突波電壓耐受量

 

1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC (Secondary-PE) 

絕緣阻抗

 

5 M

以上(所有輸出

/

入點對地之間

  500V DC

 

雜訊免疫力

 

ESD: 8KV Air Discharge, EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & 
Communication I/O: 250V,   
Digital I/O: 1KV, RS: 26MHz ~ 1GHz, 10V/m 

接地

 

接地配線之線徑不得小於電源端

L, N

之線徑(多台

PLC

同時使用時,請務必單點接地)

 

操作

/

儲存環境

 

操作:

0 ~ 55°C

(溫度),

  50 ~ 95%

(濕度),

 

污染等級

儲存:

-25 ~ 70°C

(溫度),

5 ~ 95%

(濕度)

 

耐振動

/

衝擊

 

國際標準規範

  IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) 

重量(約)

(g) 

124/160 

130/120 

136/116 

225/210 

660/590 

438/398 

616/576 

認證

 

 

 

 

 

 

輸入

/

出點規格

 

輸入點電氣規格

 

輸入點形式

 

直流

 

輸入形式

 

直流(

SINK

SOURCE

 

輸入電壓電流

 

24V DC 5mA 

Off 

 On 16.5V DC

以上

 

動作位準

 

On 

 Off 8V DC

以下

 

反應時間

 

20ms 

電路隔離

/

操作指示

 

光耦合器

/LED On 

 

輸出點電氣規格

 

輸出點形式

 

繼電器

-R 

電晶體

-T 

電流規格

 

1.5A/1

點(

5A/COM

 

55°C 0.1A/1

點、

50°C 0.15A/1

點、

 

45°C 0.2A/1

點、

40°C 0.3A/1

點(

2A/COM

 

電壓規格

 

250V AC,30V DC

以下

 

30V DC 

75VA

(電感性)

 

最大負載

 

90 W

(電阻性)

 

9W 

反應時間

 

10 ms 

Off 

 On 15us   

On 

 Off 25us 

Reviews: