Appendix B Accessories
|
VFD-S Series
Revision August 2008, SE09, SW V2.61
B-11
B.3 AC Reactor
B.3.1 AC Input Reactor Recommended Value
230V, 50/60Hz, 1-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max. continuous
Amps
3~5% impedance
0.2 1/4
4
6
6.5
0.4 1/2
5
7.5
3
0.75 1
8
12
1.5
1.5 2
12
18
1.25
2.2 3
18
27
0.8
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max. continuous
Amps
3% impedance
5% impedance
0.4 1/2
2
3
20
32
0.75 1
4
6
9
12
1.5 2
4
6
6.5
9
2.2 3
8
12
5
7.5
B.3.2 AC Output Reactor Recommended Value
115V/230V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max. continuous
Amps
3% impedance
5% impedance
0.2 1/4
4
4
9
12
0.4 1/2
6
6
6.5
9
0.75 1
8
12
3
5
1.5 2
8
12
1.5
3
2.2 3
12
18
1.25
2.5
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max. continuous
Amps
3% impedance
5% impedance
0.4
1/2 2
3
20
32
0.75 1
4
6
9
12
1.5 2
4
6
6.5
9
2.2 3
8
12
5
7.5