DeviceNet Network Scanner DVPDNET-SL
DVP-PLC Application Manual
6
3. Power, MS, NS LED
8. Function switch
4. DIN rail clip
9. DeviceNet connection port
5. Digital indicator
2.3 DeviceNet
Connection
Port
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with
DVPDNET-SL.
PIN
Signal
Color
Content
1 V- Black
0
VDC
2 CAN_L Blue Signal-
3 SHIELD
-
Shielded
4 CAN_H White
5 V+ Red
24
VDC
1
2
3
4
5
2.4 Address
Switch
The switch is used on setting up the node address of DVPDNET-SL on DeviceNet. Range: 00 ~ 63 (64 ~ 99
are forbidden).
Switch setting
Content
0 … 63
Valid DeviceNet node address
64…99
Invalid DeviceNet node address
9
1
6
4
5
0
0
9
1
3
2
7
8
2
5
6
4
3
7
8
Example: If you need to set the node address of DVPDNET-SL to 26, simply switch the corresponding
switch of x10
1
to 2 and the corresponding switch of x10
0
to 6.
Note:
z
Please set up the node address when the power is switched off. After the setup is completed, re-power
DVPDNET-SL.
z
When DVPDNET-SL is operating, changing the setting of node address will be invalid.
z
Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.5 Function
Switch
The function switches are for:
Setting up the work mode (IN0)
Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1
DR0
Baud rate
OFF OFF
125
kbps
OFF ON
250
kbps
ON OFF
500
kbps
ON ON
Incorrect
setting
IN0
ON
When the slave is off-line, the I/O data in
the buffer area will be held.