This instruction only provides introductory information on electrical specifications, functions, wiring, trouble-shooting 
and peripherals for COA02. Details of CANopen protocol are not included in this sheet. For more information on 
CANopen protocol, please refer to relevant reference or literatures.

   

 

COA02 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity, 

electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or 
specific tools are required to open the enclosure) in case danger and damage on the device may occur.

 

 

COA02 is used for controlling the operating machine and equipment. In order not to damage it, only qualified 

professional staff familiar with the structure and operation of COA02 can install, operate, wire and repair it.

 

 

Please read this instruction sheet carefully before use and follow the sheet to operate COA02 in order to prevent 

damages on the device or injuries to staff.

   

 

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all 
the wiring again before switching on the power and DO NOT touch any terminal when the power is switched on. Make 
sure the ground terminal 

  is correctly grounded in order to prevent electromagnetic interference.

 

 

Introduction

 

1.1 Model 

Explanation 

Thank you for choosing Delta COA02 CANopen slave station communication module. COA02 can be applied to 
the connection between CANopen network and Delta’s programmable logic controller, AC motor drive, servo 
drive, temperature controller and human machine interface. In addition, the custom function of COA02 allows the 
custom equipment with Modbus protocol to be connected to the CANopen network. 

Functions supported: 

 CAN2.0A protocol 

 CANopen DS301 V4.02 

Service supported:

 

 Process Data Object (PDO) 
 Service Data Object (SDO) 

 Special Object Protocol (SOP) 
 Network Management (NMT) 

Nameplate Explanation

 

MODEL :
POWER INPUT : 

COA02000T7020022

VX.XX

COA02
24Vdc  2.0W

DELTA ELECTRONICS, INC                                   MADE IN XXXXXXX

Model name

Power input spec.

Barcode & serial No.

Version

 

Serial No. Explanation

 

Production No.
Production week
Production year (2007)
Production plant (W: Wujiang   T: Taoyuan)
Version No.
Model name

 

 

1.2  Product Profile and Outline 

1

 

 

Communication port 

2

 

 

Address setup rotary switch 

3

 

 

Function setup DIP switch 

4

 

 

Instructions on the DIP switch 

5

 

 

SCAN indicator 

6

 

 

RUN indicator 

7

 

 

ERROR indicator 

8

 

 

CANopen connector 

9

 

 

DIN rail 

 

 

Unit: mm 

 

 

DIN rail clip 

 

 

Specifications

 

CANopen Connector 

Transmission method 

CAN 

Electrical isolation 

500V DC 

Type 

Removable connector (5.08mm) 

Transmission cable 

2 communication cables, 2 power cables and 1 shielded cable 

Communication 

Message type 

PDO, SDO, SYNC (synchronous object), Emergency (emergency object), NMT 

Series transmission 
speed 

10K, 20K, 50K, 125K, 250K, 500K, 800K, 1M bps (bits per second) 

Equipment type 

0 (Non-Profile) 

Company ID 

477 (Delta Electronics, Inc.) 

Electrical Specifications 

Voltage 

11 ~ 25V DC 

Current 

28mA (typical), 125mA impulse current (24V DC) 

Environment 

Standards 

IEC 61131-2, UL508 

Storage/Operation 

Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) 
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity); pollution degree 2 

Shock/Vibration 
immunity 

International Standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 
68-2-27 (TEST Ea) 

Interference immunity 

RS (IEC 61131-2, IEC 61000-4-3): 80MHz ~ 1,000MHz, 10V/m 
EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1KV 
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge 

Certificates CE, 

UL 

 

Components

 

3.1 CANopen 

Connector 

To connecto with CANopen, use the connector enclosed with COA02 or any connectors you can buy in the store 
for wiring. 

PIN 

Signal 

Description 

1 V- 

0V 

DC 

2 CAN_L 

Signal- 

3 SHIELD 

Shielded 

cable 

4 CAN_H 

 

5 V+ 

24V 

DC 

 

            1      2      3      4      5 

3.2  Address Setup Rotary Switch 

The two rotary address setup switches set up the node addresses on 

the CANopen network in hexadecimal form. Setup range: 01 ~ 7F (00 
and 80 ~ FF are forbidden) 

01

2

3

4

5

6

7 8 9 A

B

C

D

EF

H

16

1

H

16

0

01

2

3

4

5

6

7 8 9 A

B

C

D

EF

 

Example: 

If you need to set the communication address of COA02 as 26 (H1A), simply switch the corresponding rotary switch   
×16

to “1” and the corresponding rotary switch ×16

0

 to “A”.

 

Address Setting 

Description 

01 ~ 7F 

Valid CANopen communication address 

00, 80 ~ FF   

Invalid CANopen communication address 

Note:

 The changed value on the switch is only valid when COA02 is re-powered. When COA02 is operating, changing the 

set value of the communication address will be invalid.

 

3.3  Function Setup DIP Switch 

The DIP switch is to be used on the equipment connected to COA02, the 
selection of communication ports and setting up the communication speed 
of COA02 and the master station in CANopen.

 

 

3.3.1  Selecting the Equipment Connected to COA02 

PIN 1 

PIN 2 

PIN 3 

Equipment 

ON 

OFF 

OFF 

AC motor drive 

OFF 

ON 

OFF 

Programmable logic controller (PLC) 

ON ON OFF 

Temperature 

controller 

 

PIN 1 

PIN 2 

PIN 3 

Equipment 

OFF OFF  ON 

Servo 

drive 

ON 

OFF 

ON 

Human machine interface (HMI) 

OFF ON  ON 

Custom 

equipment 

ON 

ON 

ON 

For internal system use 

 

Example:

 

If the equipment connected to COA02 is Delta servo drive, you only need to switch PIN 3 of the DIP switch to “On”, 
PIN 1 and PIN 2 to “Off” and re-power COA02.   

Note:

 The changed setting of the DIP switch is only valid when COA02 is re-powered. When COA02 is operating, changing 

the setting of the DIP switch will be invalid. 

 

3.3.2  Selecting COA02 Communication Mode 

PIN 4 

PIN 5 

Communication Mode 

OFF OFF 

RS-485 

ON ON 

RS-232 

ON OFF 

Incorrect 

setting 

OFF ON 

Incorrect 

setting 

Note:

 The changed setting of the communication mode is only valid when COA02 is re-powered. When COA02 is operating, 

changing the setting of the communication mode will be invalid.

 

3.3.3  Setting up Baud Rate 

PIN 6 

PIN 7 

PIN 8 

Baud Rate 

OFF OFF OFF 

10K 

bps 

ON OFF OFF 

20K 

bps 

OFF ON OFF 

50K 

bps 

ON ON OFF 

125K 

bps 

OFF OFF  ON 

250K 

bps 

ON OFF ON 

500K 

bps 

OFF ON  ON 

800K 

bps 

ON ON ON 

1M 

bps 

Note:

 The changed setting of the baud rate of CANopen is only valid when COA02 is re-powered. When COA02 is operating, 

changing the baud rate will be invalid

 

3.4  Communication Ports on COA02 

The communication ports on COA02 are used for the connection 
with other equipments (Delta PLC, AC motor drive, temperature 
controller, servo drive, HMI and custom equipments).   

PORT1

PORT2

 

3.4.1 PORT1 

PORT1 PIN Definition 

PORT1 Sketch 

Terminal No. 

Description 

1 N.C. 

GND 

3 DATA- 

DATA+ 

5 N.C. 

1

2

3

4

5

6

PORT1

 

N.C. 

Note: 

PORT1 supports RS-485 communication mode only.

 

3.4.2 PORT2 

PORT2 Sketch 

Terminal No. 

RS-232 

RS-485 

1 N.C. 

N.C. 

RXD 

N.C. 

3 TXD 

DATA- 

N.C. 

N.C. 

5 GND 

N.C. 

N.C. 

N.C. 

7 N.C. 

N.C. 

N.C. 

DATA+ 

1

6

2

7

3
8

4

9

5

DB9  male

 

9 N.C. 

N.C. 

Note: 

PORT2 supports RS-232 and RS-485 communication mode only.

 

 

Connectors for COA02 and the Equipments

 

See below communication wirings when COA02 is connected to an equipment through PORT1. 

When connected to Delta AC motor drive 

When connected to Delta PLC 

RS-485 communication mode 

Using standard cable with RJ-12 connectors at its two ends is 

suggested.

 

RS-485 communication mode 

COA02 

RJ-12 (RS-485) 

VFD series AC motor drive 

RJ-12 (RS-485) 

COA02 

RJ-12 (RS-485) 

DVP series PLC 

RS-485 wiring terminal 

1

2

3

4

5

6

RJ-12

RJ-12

DATA-

DATA+

DATA-
DATA+

(3)

(4)

(3)
(4)

1

2

3

4

5

6

 

DATA-

DATA+

DATA-
DATA+

(3)
(4)

1

2

3

4

5

6

RJ-12

+

_

PLC  COM2

 

 

http://www.delta.com.tw/industrialautomation/

 

5011656801-OAE1

2007-05-24

 

CANopen Slave Station Communication Module

Instruction Sheet 

 

Warning

 