Delta Controls DSC-1616 Installation Manual Download Page 6

Delta Controls 

Page 6 of 12 

Wiring General 

All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 

transformers. Do not use autotransformers. Determine supply transformer rating by summing total VA of product 

and output loads. 

 

Risk of Electric Shock or Fire 

 

More than one disconnect switch may be required to de-energize the 
equipment before servicing. 

 

Input Class 2 Power Supplies are interconnected. Use only Class 2 
sources suitable for interconnections. 

 

 

 

 

 

All terminals are acceptable for Class 2 Circuit connections only 

 

Use copper conductors only 

 

Apply minimum 6.0 lb-in torque for tightening field wires into the terminal 
blocks 

Power 

This product is designed to use a 24 VAC, Class 2 power supply. The proper specified cabling must be used. 

(18 

– 16 AWG, 2-conductor wire) 

A single transformer may be used to power multiple controllers and/or auxiliary field devices (actuators, etc.) 

provided the following conditions are met: 

 

All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified devices 
will damage both the transformer and connected equipment. 

 

The transformer is properly sized, including line losses for the total VA requirements. 

 

Polarity is observed between controllers (with respect to 24~ and Gnd). 

 

Each controller is grounded as shown in the diagram below. This is important to protect equipment and 
ensure a common ground reference for RS-485 communications. 

 

The transformer secondary is fused for its maximum rated load (4A max for Class 2 circuits). 

 

 

 

Make sure to ground the controller using the ground lug that is available on the 

controller. 

Summary of Contents for DSC-1616

Page 1: ...may be configured as an MS TP SubLAN or a LINKnet network that supports up to 12 Delta BACstats or other Delta LINKnet controllers The 16 universal inputs are jumper configurable and the 16 analog out...

Page 2: ...statically sensitive device Proper ESD protection ground strap should be used when installing this product so that damage to the product does not occur Danger of explosion if the battery is incorrect...

Page 3: ...ing The DSC 1616 includes a plastic enclosure that can be quickly mounted with two screws not provided This controller should be mounted in an appropriate location within packaged equipment or another...

Page 4: ...Delta Controls Page 4 of 12 Board Layout...

Page 5: ...a Subnet of similar controllers This is the setting when the controller is connected to a BACnet MS TP network with other Subnet controllers Note This also determines where the DIP or MAC address is m...

Page 6: ...gned to use a 24 VAC Class 2 power supply The proper specified cabling must be used 18 16 AWG 2 conductor wire A single transformer may be used to power multiple controllers and or auxiliary field dev...

Page 7: ...he proper specified cabling must be used to ensure reliable communications 22 AWG twisted pair 100 120 ohms impedance 17 pF ft or lower capacitance with a braided or aluminum foil shield Controllers s...

Page 8: ...ept the signal used by the input device Place the jumper for each input in the correct location on the Input Type Selector Block The diagram to the right shows the factory default selection of 10 K 4...

Page 9: ...good both LEDs will flash at a high rate Network NET2 MS TP RS485 Communication Status Indicators The green LED flashes to indicate when the controller is transmitting out the port and the red LED fl...

Page 10: ...ation 76800 bps Maximum of 12 LINKnet controllers including up to two DFM controllers Serial RS 232 BACnet PTP Communication 9600 19200 38400 default Service Port RJ 11 Jack Used with Delta Controls s...

Page 11: ...Line Harmonics Class A EN 61000 3 3 1998 Power Line Fluctuations Pst 1 Plt 0 65 EN 50082 1 1997 Generic Immunity Standard Part 1 Residential EN 61000 4 2 1995 ESD Immunity Level B EN 61000 4 3 1996 R...

Page 12: ...l interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at...

Reviews: